EN1R--9170 0109R1--NE

·

Adjust the CO

2

% at the desired value at low output with

offset adjustment screw. Turn offset adjustment screw

clockwise to increase CO

2

%.

·

Operate boiler on high output.

·

Turn the throttle adjustment screw with a until the burner

pressure required is recorded on the pressure gauge.

·

Adjust CO

2

% with throttle adjustment screw at the desired

value. Turn screw driver

either way

to increase CO

2

%.

·

Replace cap screw and tighten pressure taps.

WARNING

High inlet pressures as used for gas G30 or G31, can

cause oscillation. This is dependent on type of

appliance.
The oscillation shall not exceed 10 % of the outlet

pressure, measured at maximum inlet pressure

according to EN 483.
The oscillation has to be verified for the complete

modulation band of the appliance.
Please contact your Honeywell representative if the

maximum of 10 % is exceeded.
Oscillation outlet pressure to be recorded with

oscilloscope etc. via transducer without damping.

CHECKOUT

Final checkout of the installation

·

After any adjustment, check pressure taps and gas

connections with an approved leak detection fluid for gas

leakage.

·

After installation and any adjustment start the appliance

and observe a complete cycle to ensure that all burner

components function correctly.

MAINTENANCE AND SERVICE

Under normal circumstances no maintenance or service is

required.

WARNING

Do not disassemble the gas control; it contains no

replaceable components.
Attempted disassembly or repair may damage the gas

control
Screws on the valve that have been sealed must

never be removed.

Home and Building Control

Combustion Controls Center Europe

Honeywell BV
Phileas Foggstraat 7

7821 AJ Emmen
The Netherlands

Tel: +31 (--)591 695911
Fax: +31 (--)591 695200

http://europe.hbc.honeywell.com

Содержание VR4611VA1007

Страница 1: ...lation low capacity and with two automatic shut off valves for intermittent pilot ignition IP applications Dimensions See fig 1 Ambient temperature 0 70 _C Pressure regulation function Class C according to EN 88 Pipe size Pipe connections are designed to meet the bending stress of group 2 according to EN 161 Inlet and outlet 1 2 ISO 7 1 internal parallel pipe thread Inlet and outlet can also be ma...

Страница 2: ... Electrical data Power consumption at 220 240 V 1st operator 3 6 4 7 W 2nd operator 3 4 4 5 W Current at 220 240 V 1st operator 32 36 mA 2nd operator 20 4 24 mA A Cap screw offset adjustment screw B 6 3 AMP terminals C Inlet pressure tap D Throttle adjustment screw E Outlet pressure tap F Pilot outlet connection G M5 air pressure connection 36 M 5 5 1 2 d 127 21 118 d 30 1 2 ISO 7 1 d 36 3 4 ISO 7...

Страница 3: ...in intermittent ignition IP system The appliance manufacturer s instructions should always be followed Perform gas leak test WARNING FIRE OR EXPLOSION HAZARD CAN CAUSE PROPERTY DAMAGE SEVERE INJURY OR DEADTH Check for gas leaks with a rich soap and water solu tion any time work is done on a gas control Gas leak test Paint all pipe connections upstream of the gas control with with a rich soap and w...

Страница 4: ...nce Please contact your Honeywell representative if the maximum of 10 is exceeded Oscillation outlet pressure to be recorded with oscilloscope etc via transducer without damping CHECKOUT Final checkout of the installation After any adjustment check pressure taps and gas connections with an approved leak detection fluid for gas leakage After installation and any adjustment start the appliance and o...

Отзывы: