Honeywell VP525A Скачать руководство пользователя страница 1

VP525A,C

Pneumatic Radiator Valve 

INSTALLATION INSTRUCTIONS 

B

C

2-1/4 DIAMETER (57) 

2-1/4 DIAMETER (57)

AIR CONNECTION 
FOR1/4 IN. (6 mm) 
O.D. PLASTIC TUBING 

AIR CONNECTION 
FOR1/4 IN. (6 mm) 
O.D. PLASTIC TUBING 

COVER FASTENER 

COVER FASTENER 

BEFORE INSTALLATION 

This normally-open, single-seated, straight-through, 

pneumatic valve provides two-position or proportional control 

of two-pipe hot water or steam systems. 

The valve can be installed in any position. The direction of 

flow must be in the same direction as the arrow cast on the 

valve body. 

Refer to Fig. 1 for dimensions to determine the space required 

for proper installation. Be sure to allow enough clearance 

around the actuator top for servicing after installation. 

1-1/2 

(38)  1 

1  1-1/2 in. (38 mm) MINIMUM CLEARANCE TO REMOVE 

ACTUATOR.  2 1/2 in. (63 mm) MINIMUM CLEARANCE 

TO FACILITATE STRAIGHT ON TUBING CONNECTION. 

IF CLEARANCE IS LESS THAN  2 1/2 in. (63 mm) 

USE AN ELBOW. 

SPECIFICATIONS 

Body Pressure Rating: 

150 psi (1034 kPa) maximum. 

Controlled Medium Temperature (maximum):

VP525A: 180°F (82°C) maximum. 

VP525C: 240°F (116°C) maximum. 

Maximum allowable difference (alternating hot and cold 

water): 140°F (78K). 

Maximum Safe Air Pressure: 

30 psi (207 kPa). 

Maximum Differential Pressure for Quiet Service: 

Water: 20 psi (138 kPa).

 

Steam (VP525C): 10 psi (69 kPa).

 

Close Off Ratings:

VP525A: See Fig. 2. 

VP525C: See Fig. 3. 

1-1/2 
(38)  1 

BODY STYLE 

SIZE NPT 

STRAIGHT THRU œ 
MALE UNION OUTLET 

1/2 

3-1/2 (90)  1-3/8 (35)  2-1/2 (63)  1-3/8 (35) 

3/4  (19) 

3/4 

3-1/2 (90)  1-3/8 (35)  3 

(76)  1-5/8 (41)  1-1/8 (29) 

ANGLE œ MALE 
UNION OUTLET 

1/2 

3-1/4 (83)  1 

(25)  2-5/8 (66)  1-1/8 (29) 

3/4 

3-1/8 (80)  1 

(25)  3 

(76) 1-1/4 (32) 

M16449A 

Fig. 1. VP525 threaded union body dimensions in in. (mm). 

® U.S. Registered Trademark 
Copyright © 2002 Honeywell International Inc. 
All Rights Reserved 

95-5544EF-1 

Содержание VP525A

Страница 1: ...OVE ACTUATOR 2 1 2 in 63 mm MINIMUM CLEARANCE TO FACILITATE STRAIGHT ON TUBING CONNECTION IF CLEARANCE IS LESS THAN 2 1 2 in 63 mm USE AN ELBOW SPECIFICATIONS Body Pressure Rating 150 psi 1034 kPa maximum Controlled Medium Temperature maximum VP525A 180 F 82 C maximum VP525C 240 F 116 C maximum Maximum allowable difference alternating hot and cold water 140 F 78K Maximum Safe Air Pressure 30 psi 2...

Страница 2: ...body 23 28 159 193 Use proper piping methods when installing the threaded union 25 30 172 207 0 20 40 60 80 100 120 140 body to prevent distortion of the valve body see Fig 5 0 138 276 414 552 689 827 965 CLOSE OFF DIFFERENTIAL The union tail piece with the union nut in place is attached to PRESSURE RATINGS PSI kPa C7714A the radiator with a suitable spud wrench The valve body is threaded into the...

Страница 3: ...NEXT TO PIPE M16447 VISE MAY SQUEEZE VALVE SEAT OUT OF ROUND IF VISE IS USED GRIP ONLY THE HEX NEXT TO PIPE BEING INSERTED VISE HOLDS PIPE SECURELY AGAINST TURNING PARALLEL JAW WRENCH GRIPS HEX OR FLATS NEXT TO PIPE Fig 5 Proper threaded valve installation practice TYPICAL OPERATION An increase in control air pressure moves the valve stem toward the closed position modulating the flow through the ...

Страница 4: ...nc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Scarborough Ontario M1V 4Z9 95 5544EF 1 B B Rev 12 02 Printed in U S A on recycled paper containing at least 10 post consumer paper fibers www honeywell com ...

Страница 5: ... la Fig 1 déterminer l espace nécessaire pour l installation de la vanne S assurer de laisser un espace suffisant au dessus de l actionneur pour l entretien de la vanne lorsqu elle sera installée 38 1 1 2 1 MF16449A CARACTÉRISTIQUES TECHNIQUES Pression nominale maximale du corps 1034 kPa 150 psi Température maximale du fluide à régler VP525A 82 C 180 F VP525C 116 C 240 F Différence maximale admiss...

Страница 6: ...18 103 138 15 20 117 152 17 22 131 165 19 24 145 179 21 26 159 193 0 20 40 60 80 100 120 140 recommandées pour empêcher le gauchissement du corps de PRESSION DIFFÉRENTIELLE MAXIMALE la vanne Voir la Fig 5 ADMISSIBLE EN kPa PSI CF7714A L embout du raccord et l écrou vissé sont d abord fixés au Fig 3 Pression différentielle maximale nominale radiateur au moyen d une clé à ergots de la bonne dimensio...

Страница 7: ...47 L ÉTAU POURRAIT ÉCRASER LE SIÊGE DE VANNE AVEC L ÉTAU SERRER SEULEMENT L ÉCROU HEXAGONAL AU BOUT DU TUYAU INSÉRER LE TUYAU EST BIEN FIXÉ DANS L ÉTAU ET NE PEUT TOURNER LA CLÉ M CHOIRES PARALLÊLES SERRE LA PARTIE DE L ÉCROU HEXAGONAL DU CÏTÉ DU TUYAU Fig 5 Méthode recommandée pour l installation d une vanne avec raccord fileté FONCTIONNEMENT TYPIQUE Une hausse de la pression d air de commande po...

Страница 8: ...cyclé contenant au moins 10 www honeywell com de fibres post consommation By using this Honeywell literature you agree that Honeywell will have no liability for any damages arising out of your use or modification to the literature You will defend and indemnify Honeywell its affiliates and subsidiaries from and against any liability cost or damages including attorneys fees arising out of or resulti...