Honeywell VP513A Скачать руководство пользователя страница 2

MAINTENA

CLEANING INSPECTION

Remove all dirt and grease accumulation from 

Inspect top of packing nut around stem for signs of

side of operator and around packing nut and stem. Use leakage. Repack the valve if necessary. See REPAIR,
solvent if necessary. Packing Replacement

CAUTION

Do not allow solvent to come into contact with
diaphragm, as it can cause serious damage.

Work in well ventilated room to prevent breathing

toxic fumes of solvent.

TROUBLESH

TING

1. Observe room tempera

setting up or down to
perature.

ture and move thermostat

simulate high or low tem-

2. Check air pressure at valve and water flow. Normal

conditions are shown in Table 1.

a.

 [fair pressure is opposite normal condition, 

check

thermostat operation and calibration. When air
pressure is lower than normal, check for proper
air supply pressure and for air leaks in piping or
diaphragm (see

REPAIR, Diaphragm Replace-

ment). Replace Series 

1

 models with new oper-

ators or replace both diaphragm and cover.

b. If 

air pressure is cowect and water is not flowing

when it should be, 

check for pump operation,

air lock, closed hand valves, or stuck valve.

c. If 

air pressure is correct and water is flowing when

it should not be, 

check for a bad disc or seat,

something lodged under the disc, or water pressure
exceeding valve close-off rating.

Replace stems and discs by disassembling valve (see

REPAIR, Stem and Disc Holder Replacement). Replace
seats on VP5 13B valves by using special tool, Part No.

CCM3833. Replace the entire valve body if the seat on
a VP5 13A valve is defective.

3. Visually inspect the valves for leakage at stem. If

repacking is necessary, see REPAIR, Packing Replace-
ment.

Table 

1

 -Normal Operating Conditions of  VP5 134 & B.

Application Room Temp. Air Pressure Water Flow

Model No. Hot W.

Ch. W. High

High

Low

F l o w  

No. Flow

VP5 13A (N.O.)

VP51 3B (NC,)

X X X X

- -

X X X X

X X X X

X X X X

X X X X

X X X X

X X X X

X X X X

75-1707 2

Содержание VP513A

Страница 1: ...ERATURE 250 F 121 C VP5 13B 1 0 1 6 or 2 5 Cv SIZE MAXIMUM SAFE OPERATOR AIR PRESSURE 2 5 VP513A 1 2 in nominal for 5 8 in O D copper lb in2 172 kPa APPLICATION The VP5 13A normally open and VP5 13B normally closed water valves provide proportional control of unit air conditioners using hot and or cold water as the con trolled medium OPERATION See Fig 1 An increase in control air pressure from the...

Страница 2: ...ping or diaphragm see REPAIR Diaphragm Replace ment Replace Series 1models with new oper ators or replace both diaphragm and cover b If air pressure is cowect and water is not flowing when it should be check for pump operation air lock closed hand valves or stuck valve c If air pressure is correct and water is flowing when it should not be check for a bad disc or seat something lodged under the di...

Страница 3: ...the b et CAUTION The controlled medium pressure holds the O ring seal in place DO NOT depress valve stem while repacking 1 2 3 4 5 5 6 With the operator removed inset r a nail awl pin or similar instrument into the 1 16 in diameter hole near the top of the valve stem Prevent stem from turning and remove the stem button Impor tant DO NOT remove the setscrew from the top of the button Pull s up and ...

Страница 4: ... and packing components as previ ously discussed Remove bonnet Fig 2 4 VP5 13A models 5 VP5 13B models a Remove valve seat with special tool Part No CCM3833 and lift out stem assembly b Replace components as required by removing disc holder mounting screw See PARTS LIST for parts ordering information a Remove stem and disc holder assembly from valve body b Remove throttling plug Fig 2 6 Reassemble...

Страница 5: ...HER RETAINER 315413 SPIDER UPPER pF SPIDER BASE 9 SCREW 1 4 20 X 3 8 SOCKET SET 2 SCREW 1 4 20 X 3 4 SOCKET HD 2 A 1 STANDARD HARDWARE ITEM OBTAIN LOCALLY WHEN POSSIBLE WHEN REPLACING THE SERIES 1 OPERATOR COVER AND OR DIAPHRAGM UPDATE TO A SERIES 2 AND 3 VERSION COVER AND DIAPHRAGM WHEN REPLACING THE SERIES 1 UPPER SPIDER UPDATE TO A SERIES 2 AND 3 UPPER SPIDER COVER DIAPHRAGM AND MOUNTING SCREWS...

Страница 6: ...PLUG 1 2 V A L V E 14003228 001 3 1 3 0 9 4 SERIES 1 313102 SERIES 2 315936 315800A 3 1 5 9 3 7 1 0 CV 315972 1 6 CVV 315056 315971 2 5 C V 3 1 3 2 6 5 315938 n n r STANDARD HAPDWARE ITEM OBTAIN LOCALLY WHEN POSSIBLE N O T E PARTS FOR OBSOLETE VALVES ANGLE PATTERN AND 1 2 IN OD ARE NO LONGER AVAILABLE SUBSTITUTE VP527A FOR SMALL CV S T VALVES X506 Fig 6 VP5 13 Parts List Continued HONEYWELL Mlnnea...