OPERATING INSTRUCTIONS 

VM242A BASICMES-2 

 

Honeywell • All rights reserved 

MU2H-1054GE25 R0411 

Operation 

Command 

Key 

New presetting and kv-value are shown in display and are 

immediately used for flow calculation

 

 

How to change presetting during measurement: 

Operation 

Command 

Key 

Increase presetting value 

 UP 

Decrease presetting value 

 DOWN 

New presetting and kv-value are shown in display and are 

immediately used for flow calculation

 

 

3.2

 

Flow Measurement after Direct Input 
of kv-value 

 
The process is similar as described above. However, instead 
of selecting a valve option “Direct kv input” is selected. 
How to access direct kv-input option: 

Operation 

Command 

Key 

Stop ongoing measurement 

Stop 

ON 

Change to main menu 

Menu 

ESC 

“Select valve” is first menu point and already highlighted

 

Select “Select valve” 

Ok 

ON 

Highlight “Direct kv input” 

↑↓

 UP/DOWN 

Select “Direct kv input” 

Ok 

ON 

The BasicMes-2 automatically returns to main screen 

where kv-value can be changed. Default value is last value 

used

 

Change kv-value 

↑↓

 UP/DOWN 

A cursor appears at first position. 

Move to digit which should be 
changed 

 ON 

Increase or decrease value 

↑↓

 UP/DOWN 

Continue with next digit, etc. When finished volume unit 

can also be changed:: 

Move cursor to right until unit 
is highlighted 

 ON 

Change unit 

↑↓

 UP/DOWN 

Confirm kv-value and unit and 
return to measuring mode 

Ok ON 

 

4

 

FUNCTION OVERVIEW 

 
The function overview is based on the main menu of the 

BasicMes-2. Functions are explained in the same order as 
they appear in the main menu. 
 

4.1

 

How to access the Main Menu 

 
When switched on the BasicMes-2 shows the main screen as 
a default. How to access the main menu and a menu item: 

Operation 

Command 

Key 

Stop ongoing measurement 

Stop 

ON 

Change to main menu 

Menu 

ESC 

Operation 

Command 

Key 

Highlight menu item 

↑↓

 UP/DOWN 

Select menu item 

Ok 

ON 

 

The main menu has the following menu items: 

Table 4.  Menu items of main menu 

Menu item 

Purpose 

Select valve 

Select valve from database 

Select project 

Select project from database 

Hydr. balancing 

Tag measuring result for printing 
and/or saving 

Temp. measurement 

Save temperature measurements 
and tag for printing and/or saving 

Leakage test 

Set parameters and perform 
leakage test 

Data logging 

Set parameters and start data log 

DP measurement 

Display of differential pressure 
only (no flow) 

USB data exchange 

Activate data exchange with PC 

Print 

Print results via pocket printer 

Save measurements 

Save tagged measurements 

Data management 

Delete projects or risers 

Setup Change 

setup 

options 

Calibration 

Access calibration menu 

 

4.2

 

Valve Selection (“Select valve”) 

 
Used to select a valve from internal database. 

Operation 

Command 

Key 

Highlight manufacturer 
(e.g. “Honeywell”) 

↑↓

 UP/DOWN 

Select manufacturer 

Ok 

ON 

Highlight and select valve and 
valve size in the same way 

↑↓

 / Ok 

UP/DOWN 

/ ON 

The BasicMes-2 automatically returns to the main screen 

where the valve presetting can be changed. Default 

presetting is the lowest presetting stored in the database

 

 

4.2.1

 

Setting presetting after valve selection 

 

Operation 

Command 

Key 

Restart measurement 

Proceed 

ON 

Increase presetting value 

 UP 

Decrease presetting value 

 DOWN 

New presetting and kv-value are shown in the display and 

are immediately used for flow calculation

 

 

4.2.2

 

Changing presetting during flow 
measurement 

 

Operation 

Command 

Key 

Increase presetting value 

 UP 

Содержание VM242A BasicMes-2

Страница 1: ... Direct Input of kv value 5 4 Function overview 5 4 1 How to access the Main Menu 5 4 2 Valve Selection Select valve 5 4 3 Project Function Select project 6 4 4 Flow Measurement Hydr balancing 6 4 5 Temperature Measurement 7 4 6 Leakage Test 7 4 7 Data Logging 7 4 8 DP Measurement 7 4 9 USB Data Exchange 8 4 10 Print 8 4 11 Save Measurements 8 4 12 Data management 8 4 13 Setup 8 4 14 Calibration 8...

Страница 2: ...nd adjustment work may only be carried out by authorized persons Immediately rectify any malfunctions which may influence safety WARNING Attention has to be paid when hoses are removed from valve after measuring When quick connection is pulled off remaining hot media may leak presenting danger of scalding CAUTION Media gas water oil do not mix 2 BASIC INFORMATION 2 1 Intended Use The BasicMes 2 ha...

Страница 3: ...cified ambient temperature see data sheet in appendix only Batteries will be exhausted if left for a long period of time after being charged Battery charger can be used as mains power supply for device e g during data logging if device is equipped with rechargeable batteries Device does not work when not equipped with batteries Also not when battery charger is connected WARNING Battery charger mus...

Страница 4: ... 7 11 Menu bar The following descriptions assume the main screen as starting point 3 1 Flow Measurement using Valve Database Select valve and valve size from device database Compare valve presetting with presetting shown in display of the BasicMes 2 Values must be identical Connect the BasicMes 2 to valve red hose is installed to higher pressure outlet before orifice or valve seat blue hose is ins...

Страница 5: ...BasicMes 2 shows the main screen as a default How to access the main menu and a menu item Operation Command Key Stop ongoing measurement Stop ON Change to main menu Menu ESC Operation Command Key Highlight menu item UP DOWN Select menu item Ok ON The main menu has the following menu items Table 4 Menu items of main menu Menu item Purpose Select valve Select valve from database Select project Selec...

Страница 6: ...eady been stored for this riser which should not be overwritten Decline to overwrite existing data No ESC Operation Command Key The BasicMes 2 returns to riser selection where either another riser can be selected to store measurement or a new riser can be defined to store measurement or function can be left without storing measurement The measurement stays in the buffer memory of the BasicMes 2 un...

Страница 7: ...ge test time with following options Operation Command Key Return to main menu without starting the test Esc ESC Select data field UP DOWN Change data ON The test consists of three parts Switch on and or set pump speed Stabilisation period indicated by a countdown clock Leakage test during which a graph is drawn Operation Command Key Confirm that pump has been switched on and set to correct speed P...

Страница 8: ...t overwrite old data No ESC Device returns to riser selection screen Overwrite old data Yes ON Information screen appears Confirm notification Ok ON Device returns to main menu 4 12 Data management Used for following functions Menu item Purpose Print protocol Print measurements saved within a project over optional pocket printer Delete riser Delete single riser of a project Delete project Delete c...

Страница 9: ...ign supply and return temperature 5 3 2 Riser Used for input of data concerning a riser distribution pipe or heat consumer Short description or name of riser free text field Design flow in l h or m h Selection of valve for this riser see below Remarks free text field 5 3 2 1 Selection of valve from valve database How to select a valve from the valve database Operation Command Open valve database S...

Страница 10: ...options are available Deletion of one certain size Deletion of all sizes of a certain valve type Deletion of all valves of a certain manufacturer Deletion of all valves To delete a valve size valve type manufacturer or all valves from the database right click onto the respective point in the tree structure then click onto the delete option NOTE Deleted elements are immediately erased and cannot be...

Страница 11: ...PERATING INSTRUCTIONS VM242A BASICMES 2 Honeywell All rights reserved 11 MU2H 1054GE25 R0411 7 ILLUSTRATIONS ABBILDUNGEN FIGURES FIGURA Fig 1 Fig 2 Fig 3 Fig 4 Fig 5 Fig 6 Fig 7 1 2 3 Fig 8 Fig 9 Fig 10 ...

Страница 12: ...VM242A BASICMES 2 OPERATING INSTRUCTIONS MU2H 1054GE25 R0411 12 Honeywell All rights reserved 8 MENU STRUCTURE ...

Страница 13: ...OPERATING INSTRUCTIONS VM242A BASICMES 2 Honeywell All rights reserved 13 MU2H 1054GE25 R0411 9 HONEYWELL IN EMEA AND ASIA PACIFIC ...

Страница 14: ...VM242A BASICMES 2 OPERATING INSTRUCTIONS MU2H 1054GE25 R0411 14 Honeywell All rights reserved 10 DATA SHEET ...

Страница 15: ...s as well as some common valves of other manufacturers are stored in an internal database Manual input of the kv value is also possible Apart from differential pressure and flow measurement the BasicMes 2 has the following functions Two temperature sensor inputs for simultaneous using two sensors or successive using one sensor temperature measurements Data logging function with programmable interv...

Страница 16: ...ate Normal 1Hz average value of four scans time slot four seconds Fast 4Hz no averaging Interface USB HP IR for communication with pocket printer Weight 2 5kg including accessories and carry case Dimensions 470 x 370 x 110mm length x width x height Pressure units mbar bar hPa kPa mH2O inH2O psi Temperature units C F Flow display up to 5mbar no display 0 1 000l h resolution 1l h 1 100m3 h resolutio...

Страница 17: ...omputer Device only without accessories carry case or batteries VMS242A001 USB interface cable VMS242A005 Battery charger VMS242A006 Pressure hose Pressure hose assembly for all VM242 including bypass assembly red and blue pressure hose fittings and ballvalve VMS242A002 Spare filters set of two VMS242A003 SafeConTM plug for blue hose VMS242A008 SafeConTM plug with ball valve for red hose VMS242A00...

Страница 18: ... Fax 49 6261 81393 www honeywell com EN0H 2323GE25 R0111 January 2011 2011 Honeywell International Inc Subject to change without notice Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl Z A La Pièce 16 1180 Rolle Switzerland or its Authorized Representative ...

Отзывы: