Oscillation
Maximum oscillation under all circumstances:
±
0.5 mbar.
Tap sensitivity of outlet pressure set point
For all gases the maximum deviation may be 1 mbar.
Repeatability of outlet pressure set point
For all gases the maximum deviation from set point is:
±
0.3
mbar or
±
3% of the set point value, whichever is the greatest.
Design life
500.000 cycles for safety and main valve operator.
Cycle frequency maximum 100 cycles /hour.
Total set point shift
*
)
For other versions see the applicable handbook
Temperature sensitivity VK41../81..VE type:
-15 ... 70°C : 4% of flow
Table 14: Total set point shift servo regulator on/off
version*
)
Pressure range
Tolerance
1.5 ... 20
2 ... 37
6% of the set point value or 1 mbar
whichever is the greatest
5 ... 50
6% of the set point value or 1.5 mbar
whichever is the greatest