Honeywell VisionPRO TH8320U Скачать руководство пользователя страница 9

TH8320U AND TH8321U TOUCH SCREEN PROGRAMMABLE THERMOSTATS

9

69-1706

OPERATION

System and Fan Settings

The System default setting is Heat and the Fan default 
setting is Auto. 

SYSTEM SETTINGS

Heat: Thermostat controls heating system.
Off: Both heating and cooling are off.
Cool: Thermostat controls cooling system.
Auto: Thermostat automatically changes between 
heating and cooling systems, depending on indoor 
temperature. (See Installer Setup section.)
Em Heat: Emergency heat cycles to maintain 
temperature. Compressor is locked out. (Used only for 
heat pump systems with backup heat.)

FAN SETTINGS

The Fan setting can be programmed into the thermostat 
schedule for each period (Wake, Leave, Return, Sleep). 
See the Owners’ Guide for additional information.

LED Indication (Requires 24 Vac Common 
Connection)

An LED indicator is located in the upper right corner of 
the thermostat. It is only visible when lighted:
• It indicates when the thermostat is in the Emergency 

Heat mode. When in Em. Ht. mode, the L terminal is 
continuously energized and the LED is on. 

• When the L terminal is wired to an equipment monitor, 

the LED signals when a check or fail signal is sent to 
the thermostat from the system. See Fig. 21. (This 
can occur only when the thermostat is not in Em. Ht. 
mode.)

Fig. 21. L terminal switch to R (power) side of system 

transformer.

Preprogrammed Settings

Table 3 shows the default program settings. See Owners’ 
Guide for complete instructions on changing the 
program.

INSTALLER SETUP

This Universal Thermostat works with many different 
system types. To operate correctly, the thermostat must 
be set up to operate the installed heating and/or cooling 
system. 

Installer Setup Menus

Main Menu:

 Offers the most commonly used options.     

It is necessary to enter this menu to set the 
thermostat to the type of system it is operating. Many 
applications use only the Main Menu.

Regional Menu:

 Offers choices often changed due to a 

particular area or region. For example, temperature 
display in Fahrenheit or Celsius is offered in this menu.

Advanced Settings Menu:

 Offers more settings to fully 

customize the thermostat. Many of these settings do not 
require changing from the factory settings.

Entering Installer Setup

1.

Thermostat must be powered either with Alkaline 
AAA batteries or with 24 Vac Common wire.

2.

From the home screen, press System key. (Press 
Done or Cancel key to return to home screen.)

3.

Five blank touch keys show on the bottom of the 
screen between the Done and Cancel keys. Press 
and hold the two blank keys on either side of the 
center blank key for approximately five seconds 
until screen changes. See Fig. 22.

Fig. 22. Entering Installer Setup.

Table 3. Default Program Settings.

Schedule 

Period

Time

Setpoints

Fan 

Setting

Heat Cool 

Wake

6:00AM

70

°

(21

°

C)

78

°

(25.5

°

C)

Auto

Leave

8:00AM

62

°

(16.5

0

C)

85

°

(29.5

0

C)

Auto

Return

6:00PM

70

°

(21

°

C)

78

°

(25.5

°

C)

Auto

Sleep

10:00PM 62

°

(16.5

°

C)

82

°

(28

°

C)

Auto

M19907

EQUIPMENT

MONITOR

L

TO R

TO C

C

DONE

CANCEL

MON

TUE

WED

THU

FRI

SAT

AAT

SUN

PM

SYSTEM

EM HEAT

OFF

COOL

Following
Schedule

Inside

Set To

M19923

Содержание VisionPRO TH8320U

Страница 1: ...fully Failure to follow the instructions can damage the product or cause a hazardous condition 2 Check the ratings given in the instructions to make sure the product is suitable for your application 3 Installer must be a trained experienced service technician 4 After completing installation use these instructions to check out the product operation Selecting Location Install the thermostat about 5 ...

Страница 2: ... FIG 5 16 All wiring must comply with local electrical codes and ordinances 1 Select set of terminal identifications Table 2 that corresponds with system type conventional or heat pump in Fig 3 2 Loosen the screws for the appropriate system type selected see Table 2 Insert wires in the terminal block under the loosened screw See Fig 4 3 Securely tighten each screw 4 Push excess wire back into the ...

Страница 3: ...HEAT RELAY FAN RELAY R C POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED REMOVE FACTORY INSTALLED JUMPER OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR AVAILABLE ON SELECT MODELS WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE 1 1 3 2 3 OPTIONAL 24 VAC COMMON CONNECTION Y2 RC S1 R S2 W W2 Y G C 2 CONVENTIONAL M19897 OUTDOOR INDOOR TEMPERATURE SENSOR HEAT RELAY R C PO...

Страница 4: ...R SERIES 20 MOTOR OR VALVE M19900 OUTDOOR INDOOR TEMPERATURE SENSOR FAN RELAY R C POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED FACTORY INSTALLED JUMPER OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR AVAILABLE ON SELECT MODELS WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE 1 1 3 2 3 OPTIONAL 24 VAC COMMON CONNECTION Y2 RC S1 R S2 W W2 Y G C 2 CONVENTIONAL COMPRESS...

Страница 5: ...NSTALLED JUMPER REMOVED OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR AVAILABLE ON SELECT MODELS WIRES MUST HAVE A CABL SEPARATE FROM THE THERMOSTAT CABLE OPTIONAL 24 VAC COMMON CONNECTION MUST COME FROM THE COOLING TRANSFORMER 3 OUTDOOR INDOOR TEMPERATURE SENSOR RC R O B Y G C Y2 L E AUX SI S2 HEATPUMP COMPRESSOR M19903 CHANGEOVER VALVE FAN RELAY R C 1 1 2 2 3 4 3 3 4 OPTIONAL 24 VAC COMMON CONNECTION...

Страница 6: ...R INDOOR REMOTE SENSOR AVAILABLE ON SELECT MODELS WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE OUTDOOR INDOOR TEMPERATURE SENSOR R O B Y G C Y2 L E AUX SI S2 HEATPUMP COMPRESSOR RELAY M19905 CHANGEOVER VALVE FAN RELAY HEAT 2 RELAY AUXILIARY HEAT R C 1 1 2 2 3 4 5 6 6 6 4 5 5 OPTIONAL 24 VAC COMMON CONNECTION EQUIPMENT MONITOR POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECT...

Страница 7: ...he device See Fig 17 Fig 17 Installing batteries on thermostat back Mounting the Thermostat 1 Align the terminal screw blocks with the pins on the back of the thermostat 2 Push the thermostat straight onto the wallplate See Fig 18 R O B Y G C Y2 L E AUX SI S2 HEATPUMP COMPRESSOR 2 COMPRESSOR 1 M19906 CHANGEOVER VALVE FAN RELAY HEAT 2 RELAY AUXILIARY HEAT R C 1 1 2 2 3 4 5 6 6 6 3 5 5 OPTIONAL 24 V...

Страница 8: ... on the back of the thermostat in the lower left corner must be removed for this feature to be active Using the Thermostat The thermostat has a touch screen interface Words or symbols appear highlighting the keys as necessary to complete tasks Always press the keys with your finger tips Sharp instruments like a pen or pencil point can damage the thermostat 1 Use the arrow keys to set the Year Mont...

Страница 9: ...tructions on changing the program INSTALLER SETUP This Universal Thermostat works with many different system types To operate correctly the thermostat must be set up to operate the installed heating and or cooling system Installer Setup Menus Main Menu Offers the most commonly used options It is necessary to enter this menu to set the thermostat to the type of system it is operating Many applicati...

Страница 10: ...omize themselves as you make selections to the Installer Setup Therefore not all Installer Setup Selections are shown or are available to change DONE O MON WED THU FRI SAT A AT SUN INSTALLER SETUP NUMBER FACTORY SETTING ADVANCE TO NEXT INSTALLER SETUP PRESS TO EXIT INSTALLER SETUP CHANGE THE FACTORY SETTING M19922 A U Table 4 Main Installer Setup Menu Select Installer Setup Number Factory Setting ...

Страница 11: ... to electric Reversing Valve O B Operation 0190 0 O B terminal is energized for reversing valve in cooling 1 O B terminal is energized for reversing valve in heating Only shown if heat pump system is chosen Backup Heat Source Auxiliary Heat 0200 0 Heat pump backup heat source is electric 1 Heat pump backup heat source is fossil fuel Only shown if 2 heat 1 cool or 3 heat 2 cool heat pump is chosen ...

Страница 12: ... this stage changes default cph for 2nd stage heat Cycles per hour cph for 2nd Stage Heat 0250 5 Cycles per hour cph for 2nd Stage Conventional Heat or Auxiliary Heat for 2 H 1C Heat Pump Systems 1 12 1 12 available typical settings 1 1 cph used for steam orgravity system 3 3 cph for hot water systems or high efficiency 90 or better fossil fuel forced air systems 5 5 cph for standard fossil fuel f...

Страница 13: ...s 5 5 cph for standard fossil fuel forced air systems 9 9 cph for electric heat systems Onlyshownif 2 heat 1 cool or 3 heat 2 cool heat pump is selected Continuous Backlight 0280 0 Backlight not on continuously Thermostat backlight comes on with each key press 1 Backlight is on continuously thermostat must have a common wire attached for this function Option is always shown however continuously on...

Страница 14: ...setpoints can be set no closer than 3 F 1 5 C 2 thru 9 Heating and cooling setpoints can be set no closerthanchosen value 2 2 F 1 C 3 3 F 2 C 4 4 F 2 5 C 5 5 F 3 C 6 6 F 3 5 C 7 7 F 4 C 8 8 F 4 5 C 9 9 F 5 C Shown only if automatic changeover is selected Temperature Indication Scale 0320 0 Temperature is displayed in F 1 Temperature is displayed in C Daylight Savings 0330 1 Daylight savings enable...

Страница 15: ...5 40 45 No lockout 15 F 9 5 C 20 F 6 5 C 25 F 4 C 30 F 1 C 35 F 1 5 C 40 F 4 5 C 45 F 7 C Default depends on other selections Shown if Outdoor Temperature for control is selected See Advanced Features section for more information Heat Pump Auxiliary Lockout 0360 0 No heat pump auxiliary lockout 40 45 50 55 60 No lockout 40 F 4 5 C 45 F 7 C 50 F 10 C 55 F 13 C 60 F 15 5 C Shown if electric is chose...

Страница 16: ...e Number of Periods 0540 4 Four periods available Wake Leave Return Sleep 2 Two periods available Wake and Sleep Not shown if non programmable is selected 2 or 4 applies to all days of the week Minimum Compressor Off Time 0580 5 Five minute minimum off time for compressor 0 2 3 4 Minimum number of minutes compressor is off between calls for compressor Heat Temperature Range Stop 0600 90 Highest he...

Страница 17: ... temperature overshoot Choose 3 if getting temperature undershoot Temperature Control in Cool 0690 2 Standard temperature control in cooling 1 3 1 less aggressive temperature control could cause temperature undershoot 3 more aggressive temperature control could cause temperature overshoot Applies to recovery ramp Choose 1 if getting temperature overshoot Choose 3 if getting temperature undershoot ...

Страница 18: ...g Installer System Test Avoid cycling compressor quickly Table 7 System Test s Select Installer Setup Number Factory Setting Other Choices Comments Options Description Options Description Installer Test Cool Test 1 0 Cool is off 1 2 0 cooloff 1 cool stage 1 turns on 2 cool stages 1 and 2 on System selection determines which tests are available and the number of stages shown Installer Test Fan Test...

Страница 19: ...here is only one source of non compressor heat and the E terminal is jumped to the Aux terminal Heat Pump with Electric Auxiliary Backup Heat and Outdoor Temperature Sensor 1 Choose correct heat pump application in Installer Setup Number 0170 2 Choose Electric as Auxiliary Backup Heat Source in Installer Setup Number 0200 3 Choose Outdoor Temperature Sensor for Control Option in Installer Setup Nu...

Страница 20: ... locked Check Installer Setup Number 0670 to change keypad locked options Heating or cooling does not come on Thermostat minimum off time is activated Wait up to five minutes for the system to respond System selection is not set to Heat or Cool Set system Selection to correct position O B terminal is not set correctly Heat Pumps only Check Installer Setup Number 0190 and set correctly System type ...

Отзывы: