VisionPRO
TM
TH8000 Series
7
69-2389—03
ENGLISH
Installer setup
Setup functions
Settings & Options
(factory default in
bold
)
0120
Year
(first two digits)
20
(
20
00-
20
99)
21 (
21
01-
21
78)
0130
Year
(second two digits)
10
(20
10
)
[Other options: 00-99]
0140
Month
6
[Other options: 1-12]
0150
Date
15
[Other options: 1-31]
0160
Schedule format
4 7-day programming
0 Non-programmable
0165
Restore energy saving
0 No
1 Yes
0170
System type
1 1 heat/1 cool conventional
2 1 heat/1 cool heat pump (no aux. heat)
3 Heat only (2-wire systems)
4 Heat only with fan
5 Hot water Series 20 system (power to open & close zone
valves/normally open zone valves)
6 Cool only
7 2 heat/1 cool heat pump (with aux. heat)
8 2 heat/2 cool multistage conventional
9 2 heat/1 cool multistage conventional
10 1 heat/2 cool multistage conventional
11 2 heat/2 cool heat pump (no aux. heat)
12 3 heat/2 cool heat pump (with aux. heat)
0173
Heat Pump Type
0 Air to Air heat pump
1 Geothermal heat pump
0180
Fan control
(heating)
0 Gas/Oil heat (equipment controls heating fan)
1 Electric furnace (thermostat controls heating fan)
0190
Changeover valve
(O/B terminal)
0 O/B terminal controls valve in cooling
1 O/B terminal controls valve in heating
0200
Auxiliary heat
0 Electric backup heat
1 Fossil fuel backup heat
0210
External fossil
fuel kit
1 External fossil fuel kit controls backup heat
0 Thermostat controls backup heat (outdoor sensor required)
0220
1st stage com-
pressor cycle rate
3 Recommended for most compressors
[Other options: 1, 2, 4, 5 or 6 CPH]
0230
2nd stage com-
pressor cycle rate
3 Recommended for most compressors
[Other options: 1, 2, 4, 5 or 6 CPH]
0240
1st stage heat
cycle rate (CPH=
cycles per hour)
5 Gas or oil furnaces of less than 90% efficiency
1 Steam or gravity systems
3 Hot water systems & furnaces of 90%+ efficiency
9 Electric furnaces
[Other options: 2, 4, 6, 7, 8, 10, 11, 12 CPH]
0250
2nd stage heat cycle
rate (CPH)
5 Gas or oil furnaces of less than 90% efficiency
1
Steam or gravity systems
3
Hot water systems & furnaces of 90%+ efficiency
9
Electric furnaces
[Other options: 2, 4, 6, 7, 8, 10, 11, 12 CPH]
0260
3rd stage heat
cycle rate (CPH)
9 Electric auxiliary heat or electric furnaces
1
Steam or gravity systems
3
Hot water systems & furnaces of 90%+ efficiency
5
Gas or oil furnaces of less than 90% efficiency
[Other options: 2, 4, 6, 7, 8, 10, 11, 12 CPH]
Continued on next page