VisionPRO

TM 

TH8000 Series 

7

69-2389—03

ENGLISH

Installer setup

Setup functions 

Settings & Options 

(factory default in 

bold

)

0120

Year  

(first two digits)

20

 (

20

00-

20

99)

21 (

21

01-

21

78)

0130

Year  

(second two digits)

10

 (20

10

)

 

[Other options: 00-99]

0140

Month

6

  [Other options: 1-12]

0150

Date

15

  [Other options: 1-31]

0160

Schedule format

4  7-day programming

0 Non-programmable

0165

Restore energy saving

0 No

1 Yes

0170

System type

1  1 heat/1 cool conventional

2  1 heat/1 cool heat pump (no aux. heat)
3  Heat only (2-wire systems)
4  Heat only with fan
5  Hot water Series 20 system (power to open & close zone 

valves/normally open zone valves)

6  Cool only
7  2 heat/1 cool heat pump (with aux. heat)
8  2 heat/2 cool multistage conventional
9  2 heat/1 cool multistage conventional
10  1 heat/2 cool multistage conventional
11  2 heat/2 cool heat pump (no aux. heat)
12  3 heat/2 cool heat pump (with aux. heat)

0173

Heat Pump Type

0  Air to Air heat pump

1  Geothermal heat pump

0180

Fan control  

(heating)

0  Gas/Oil heat (equipment controls heating fan)

1  Electric furnace (thermostat controls heating fan)

0190

Changeover valve 

(O/B terminal)

0  O/B terminal controls valve in cooling

1  O/B terminal controls valve in heating

0200

Auxiliary heat

0  Electric backup heat

1  Fossil fuel backup heat

0210

External fossil  

fuel kit

1  External fossil fuel kit controls backup heat

0  Thermostat controls backup heat (outdoor sensor required)

0220

1st stage com- 

pressor cycle rate

3  Recommended for most compressors 

[Other options: 1, 2, 4, 5 or 6 CPH]

0230

2nd stage com- 

pressor cycle rate

3  Recommended for most compressors 

[Other options: 1, 2, 4, 5 or 6 CPH]

0240

1st stage heat  

cycle rate (CPH= 

cycles per hour)

5  Gas or oil furnaces of less than 90% efficiency

1  Steam or gravity systems
3  Hot water systems & furnaces of 90%+ efficiency
9  Electric furnaces 

[Other options: 2, 4, 6, 7, 8, 10, 11, 12 CPH]

0250

2nd stage heat cycle 

rate (CPH)

5  Gas or oil furnaces of less than 90% efficiency

1

 

Steam or gravity systems

3

 

Hot water systems & furnaces of 90%+ efficiency

9

 

Electric furnaces

 

[Other options: 2, 4, 6, 7, 8, 10, 11, 12 CPH]

0260

3rd stage heat  

cycle rate (CPH)

9  Electric auxiliary heat or electric furnaces

1

 

Steam or gravity systems

3

 

Hot water systems & furnaces of 90%+ efficiency

5

 

Gas or oil furnaces of less than 90% efficiency

 

[Other options: 2, 4, 6, 7, 8, 10, 11, 12 CPH]

Continued on next page

Содержание VisionPRO TH8000 Series

Страница 1: ...call Honeywell Customer Care toll free at 1 800 468 1502 This thermostat contains a Lithium battery which may contain Perchlorate material Perchlorate Material special handling may apply See www dtsc ca gov hazardouswaste perchlorate MERCURY NOTICE If this product is replacing a control that contains mercury in a sealed tube do not place the old control in the trash Contact your local waste manage...

Страница 2: ... Wallplate installation 1 Separate wallplate from thermostat 2 Mount wallplate as shown below Grasp top and bottom of wallplate and pull to remove from thermostat Drill 3 16 holes for drywall Drill 7 32 holes for plaster Wall anchors Wire hole Mounting screws ...

Страница 3: ...t relay W2 2nd stage heat relay Y 1st stage compressor contactor Y2 2nd stage compressor contactor G Fan relay S1 S2 Optional outdoor remote discharge sensor U1 U1 Optional IAQ device Heat Pump Terminal Letters R System power Connect to secondary side of system transformer C Common wire from secondary side of system transformer Y 1st stage compressor contactor Y2 2nd stage compressor contactor E A...

Страница 4: ... outdoor remote discharge sensor U1 U1 Optional IAQ relay 2H 2C System 1 transformer Y2 Cool relay 2 W2 Heat relay 2 R Power 1 6 W Heat relay 1 Y Cool relay 1 G Fan relay C 24VAC common 2 S1 S2 Optional outdoor remote discharge sensor U1 U1 Optional IAQ relay Heat Only System With Fan R Power 1 6 W Heat relay G Fan relay C 24VAC common 2 S1 S2 Optional outdoor remote discharge sensor U1 U1 Optiona...

Страница 5: ...or any humidifier with its own transformer R Power 1 U1 Humidifier relay 7 U1 Humidifier relay 7 Bypass flow through humidifier or any humidifier that uses the system trans former R Power 1 U1 Field jumper R to U1 7 U1 Humidifier relay 7 Whole house dehumidifier R Power 1 U1 Dehumidifier relay 7 U1 Dehumidifier relay 7 A C with low speed fan R Power 1 U1 Field jumper R to U1 7 U1 Dehumidifier rela...

Страница 6: ...ermostat Set date and time Press st to set time Press st to set date Press st to set month Press st to set year Installer setup Press DONE to save changes Press DONE to save and exit SCHED HOLD TUE FAN AUTO Inside 70 aM 6 00 SYSTEM HEAT DONE 20 0120 DONE CANCEL aM 6 00 SYSTEM HEAT MCR29745 DONE 20 0120 1 Press SYSTEM Press DONE to save exit 2 Press and hold for 5 seconds 3 Change settings see p 7 ...

Страница 7: ...ing fan 0190 Changeover valve O B terminal 0 O B terminal controls valve in cooling 1 O B terminal controls valve in heating 0200 Auxiliary heat 0 Electric backup heat 1 Fossil fuel backup heat 0210 External fossil fuel kit 1 External fossil fuel kit controls backup heat 0 Thermostat controls backup heat outdoor sensor required 0220 1st stage com pressor cycle rate 3 Recommended for most compresso...

Страница 8: ...s 0347 Droop temperature 2 2 F 1 C Other options 2 5 2 F to 5 F 1 C to 2 5 C 0350 Heat pump compressor lockout 0 No heat pump compressor lockout Other options 5 60 F 15 C to 15 5 C See page 11 0360 Heat pump auxiliary lockout 0 No heat pump auxiliary lockout Other options 5 65 F 15 C to 18 5 C See page 11 0371 Indoor Air Quality de vice on U1 U1 0 None 1 Humidification 2 Dehumidification 3 Ventila...

Страница 9: ...limit Other options 30 to 60 or 100 P Meets ASHRAE 62 2 standard F Does not meet ASHRAE 62 2 standard 0405 Ventilation fan action 1 Ventilation on forces fan on 2 Ventilation does not force fan on 0430 Ventilation lockout 0 Off 1 Lockout for high temperatures See page 11 2 Lockout for low temperatures See page 11 3 Lockout for high and low temperatures See page 11 0431 Ventilation high tem peratur...

Страница 10: ...an timer heat 0 Off Other options Fan runs for 30 60 90 or 120 seconds after call for heat ends 0660 Extended fan timer cool 0 Off Other options Fan runs for 30 60 90 or 120 seconds after call for cool ends 0670 Keypad lock 0 Keypad unlocked fully functional 1 Partially locked access to temperature settings only 2 Fully locked 0680 Heat temperature control 2 Standard temperature control recommende...

Страница 11: ... to dehumidification the U1 U1 relay can be set to control dehumidification Heat Pump Control Electric Backup Setup Functions 0350 0360 If an outdoor temperature sensor is installed select a compressor lockout temperature Function 0350 Below this temperature only electric heat operates Also select an auxiliary lockout temperature Function 0360 Above this temperature only the compressor operates Be...

Страница 12: ...60Hz Running Current W Heating 20 30 Vac 0 02 1 0 A Powerpile 750 mV DC 100 mA DC W2 Heating 20 30 Vac 0 02 0 6 A Y Cooling 20 30 Vac 0 02 1 0 A Y2 Cooling 20 30 Vac 0 02 0 6 A E Aux Auxiliary Emergency heat 20 30 Vac 0 02 1 0 A O B Changeover 20 30 Vac 0 02 0 6 A L Heat pump reset 20 30 Vac 0 02 0 6 A U1 U1 IAQ relay 20 30 Vac 20 30 Vac 0 02 0 6 A Specifications Please contact your distributor to...

Отзывы: