TB8220 COMMERCIAL VISIONPRO™ PROGRAMMABLE THERMOSTAT
5
63-2625—3
Fig. 8. Install wallplate.
WIRING
CAUTION
Electrical Shock Hazard.
Can cause electrical shock or equipment damage.
Disconnect power supply before connecting wiring.
IMPORTANT
— All wiring must agree with applicable codes,
ordinances and regulations.
— Use 18 gauge thermostat wire. Shielded cable is not
required.
NOTES:
—
Refer to Table 5 for terminal designation
descriptions.
—
See Fig. 12 through 22 for wiring diagrams for
specific equipment applications.
1.
Select set of terminal identifications that correspond to
your system type (conventional or heat pump). See Fig. 9.
Fig. 9. Terminal identifications for system type.
2.
Loosen screw terminals used for the application.
3.
Insert the wires into the terminal block and tighten each
screw terminal. See Fig. 10.
Fig. 10. Insert wires into terminal block.
4.
Push excess wire back into the wall opening and restrict
wires to the shaded area. See Fig. 11.
5.
Plug the wall opening with nonflammable insulation to
prevent drafts from affecting the thermostat.
Fig. 11. Restrict wires to shaded area of wire hole.
Table 4. Wiring Diagrams.
WALL
MOUNTING
HOLES
M19916
MOUNTING
SCREWS (2)
WALL ANCHORS (2)
WIRES THROUGH WALL
AND WIRE SLOT
CONVENTIONAL
SCREW TERMINALS
HEAT PUMP
M22780
Y2
L
A
W1
S1
S2
Y2
W2
S1
S2
RC
R
O/B
Y
G
C
RC
R
W
Y
G
C
System Type
Wallplate Terminal
Identifications
Wiring Diagram
Figure
Standard Heat/Cool Conventional
Heat Only
Conventional
Heat Only with Fan Conventional
Cool only
Conventional
Standard Multistage
up to 2 Heat/2 Cool
Conventional
Heat Pump
(No Auxiliary Heat)
Heat Pump
Heat Pump
(with Auxiliary Heat)
Heat Pump
Multiple T7770A
Sensors
—
Multiple C7189U
Sensors
—
M19917
WALLPLATE
M22266
WALL OPENING
WIRE
SHADED AREA