VISIONPRO
®
IAQ TOTAL HOME COMFORT SYSTEM
13
68-0287—1
4.
See screen below to review how the thermostat keys are
used during Installer Setup. See Table 3–4 for the
Installer Setup Numbers and Settings.
5.
Press the Done key to exit the Installer Setup screen.
DONE
O
MON
WED
THU
FRI
SAT
AAT
SUN
INSTALLER
SETUP
NUMBER
CURRENT
SETTING
ADVANCE TO NEXT
INSTALLER SETUP
PRESS TO EXIT
INSTALLER SETUP
CHANGE THE
CURRENT
SETTING
M22443
A
U
Table 3. Installer Setup Menu.
ISU
Parameter
Number
Installer Setup
Name
Settings
(Factory Defaults Shown in Bold)
Notes
110
Zone Number
0
1–9
Not zoned
Zone number
Select zone number.
Zone 0 = not zoned
Zone 1 = master zone controller
Zone 2–9 = satellite thermostat
120
USU
Date (Year
Upper)
20
21
Select first two digits of current calendar year (
20
06 for
example) - (2001-2178 available).
130
USU
Date (Year
Lower)
01-99
Default = 06
Select last two digits of current calendar year (20
06
for
example) - (2001-2178 available).
140
USU
Date (Month)
1-12
Select number that represents current calendar
month.
Default = 06
150
USU
Date (Day)
1-31
Select number that represents current calendar
date.
Default = 15
160
USU
Schedule Options
4
0
Seven-day programmable
Non-programmable
165
USU
Restore Energy
Star Schedule
0
1
No
Yes
172
System Selection
1
2
3
E
Conventional
Heat Pump
Heat Only No Fan
Auto Discover
Selection of a specific system setting will automatically
modify some default settings and/or hide other installer
setup options that follow.
174
Number of Cool/
Compressor
Stages
0
1
2
E
none
1
2
Auto Discover
Not shown if ISU172 = 3.
Conventional systems = number of cooling stages.
Heat Pump systems = number of compressor stages.
176
Number of
Conventional
Heat or Heat
Pump Aux Stages
0
1
2
3
E
none
1
2
3
Auto Discover
Conventional systems = number of heating stages
(maximum of 3).
Heat Pump systems = number of
auxiliary heat
stages (maximum of 2).
180
Fan Operation
Conventional
heat only
0
1
2
E
Gas or oil furnace equipment controls fan in
heating
Electric furnace—thermostat controls fan in
heating
Equipment controls stage 1; thermostat controls
stage 2+
Auto Discover
Only shown if ISU172 = 1 (conventional system).
Use 0 for fossil fuel systems (equipment controls fan).
Use 1 for electric systems (thermostat controls fan).
Use 2 if stage 1 is radiant heating and stage 2+ is a hot
water fan coil.
190
Reversing Valve
O/B
0
1
Changeover valve—O/B terminal is energized
in cooling
Changeover valve—O/B terminal is energized in
heating
Only shown if ISU172 = 2.