Honeywell VisionPRO 8000 Скачать руководство пользователя страница 2

VISIONPRO® 8000 SMART THERMOSTAT

33-00096—05

6

INSTALLATION

Wiring 24 Vac Common

• Single-Transformer System—Connect the common side 

of the transformer to the C screw terminal of the 
thermostat. Leave the metal jumper wires in place 
between R and RC.

• Two-Transformer System—Connect the common side of 

the cooling transformer to the C screw terminal of the 
thermostat. Remove the metal jumper wire between R 
and RC. Connect the hot side of heating transformer to 
R and connect the hot side of cooling transformer to RC.

Selecting Discharge Air 
Temperature Sensor Mounting 
Locations

Refer to the guidelines below and Fig. 3–7 for mounting 
locations of the Discharge Air Temperature Sensor.

Selecting Discharge Air Temperature 
Sensor Mounting Location

1.

Mount the Discharge Air Temperature Sensor on the 
supply duct in a location where the air is mixed well. 
Mount the Discharge Air Temperature Sensor out of 
sight of the A-Coil/Heat Exchanger when possible. 
See Fig. 3.

2.

When possible, mount the Discharge Air Temperature 
Sensor upstream of a Steam Humidifier, a Fan 
Powered Humidifier or a Dehumidifier that is ducted 
to the supply. See Fig. 4–5.

3.

If space does not allow a Discharge Air Temperature 
Sensor upstream of a Steam Humidifier or Fan 
Powered Humidifier, mount the Discharge Air 
Temperature Sensor downstream of the Humidifier. 
See Fig. 4.

4.

If a Bypass Humidifier is installed, mount the 
Discharge Air Temperature Sensor downstream of the 
Bypass Humidifier. See Fig. 6–7.

Selecting Discharge Air Temperature 
Sensor Mounting Location

1.

Install the Discharge Air Temperature Sensor on the 
duct in a location where the air is mixed well. See 
Fig. 3–7.

Fig. 3. 

Fig. 4. 

Model Numbering

TH8321

Stages

3H/2C HP

2H/2C CONV

Residential or Commercial

Powered - C Wire (C-wire adapter 
compatible)

Onboard Humidity Sensor

Number of IAQ Relays

1

Number of Sensor Inputs

1

Economizer / TOD Output

MOUNT DISCHARGE

SENSOR HERE

M35768

HEAT

EXCHANGER

BLOWER

VENTILATOR

OR

DEHUMIDIFIER 

A-COIL

M35769

HEAT

EXCHANGER

BLOWER

HUMIDIFIER

ALTERNATE  MOUNTING LOCATION

FOR DISCHARGE SENSOR.

MOUNT 

DISCHARGE

SENSOR HERE

ABOVE 

CENTER

OF A-COIL

UPSTREAM OF

HUMIDIFIER

VENTILATOR

OR

DEHUMIDIFIER 

Содержание VisionPRO 8000

Страница 1: ...sword Date Code You will need the thermostat password to Make changes to Installer Setup Perform an Installer Test Reset Thermostat to Factory Default Settings The password date code is located on the back of the thermostat see Fig 2 Fig 2 Finding thermostat password You can also find the password date code by pressing MENU selecting Dealer Information and then scrolling down to see the Date Code ...

Страница 2: ...le mount the Discharge Air Temperature Sensor upstream of a Steam Humidifier a Fan Powered Humidifier or a Dehumidifier that is ducted to the supply See Fig 4 5 3 If space does not allow a Discharge Air Temperature Sensor upstream of a Steam Humidifier or Fan Powered Humidifier mount the Discharge Air Temperature Sensor downstream of the Humidifier See Fig 4 4 If a Bypass Humidifier is installed m...

Страница 3: ... wires to S1 terminal at the thermostat 4 Setup the S1 terminal in the Installer Setup at the thermostat Fig 8 Mounting Discharge Air Sensor M35770 HEAT EXCHANGER BLOWER ALTERNATE MOUNTING LOCATION FOR DISCHARGE SENSOR MOUNT DISCHARGE SENSOR HERE ABOVE CENTER OF A COIL UPSTREAM OF DEHUMIDIFIER DEHUMIDIFIER HEAT EXCHANGER BLOWER VENTILATOR OR DEHUMIDIFIER MOUNT DISCHARGE SENSOR HERE BYPASS HUMIDIFI...

Страница 4: ...On those models pull evenly along the sides and bottom of the thermostat to separate it from the wallplate Fig 10 Separate wallplate from thermostat 2 Position and level the wallplate for appearance only 3 Use a pencil to mark the mounting holes 4 Remove the wallplate from the wall and if drywall drill two 3 16 in holes in the wall as marked For firmer material such as plaster drill two 7 32 in ho...

Страница 5: ...ce Fig 15 Mount thermostat Finding Your Password Date Code to Access Installer Options You need a password Date Code to access Installer Options Installer Options allow you to Make changes to the Installer Setup Perform an Installer Test Reset the thermostat to Factory Default settings The password Date Code is located on the back of the thermostat It can also be found by following these steps 1 T...

Страница 6: ... 1502 http yourhome honeywell com Commercial Commerciale 1 888 245 1051 http customer honeywell com Honeywell Golden Valley MN 55422 RoHs Compliant Conformité RoHs Assembled in Mexico Assemblé au Mexique TH8321WF1001 1 1524 M37810A M35343B Password Date Code Scroll to see Installer Setup Installer Test Reset To Defaults Device Info Table 1 Installer Options Menu Item Description Installer Setup Se...

Отзывы: