5
EN2R--9012 9412R0--NE
SPECIFICATIONS
Models
The VG series consists of a series
manually operated safety solenoid
valves from
3
/
8
” upto and including 3”
connection.
VG series solenoid valves
VG .010A (DN 10)
VG .015A (DN 15)
VG .020A (DN 20)
VG .025A (DN 25)
VG .032A (DN 32)
VG .040A (DN 40)
VG .050A (DN 50)
VG .065A (DN 65)
VG .080A (DN 80)
Pipe sizes 1000 series
Inlet and outlet
3
/
8
” up to and including
3” internal parallel pipe thread
according to
ISO 7--1
Pipe sizes 3000 series
Flanged connection 2
1
/
2
” and 3”
according to PN 16 UNI 2278--67
Torsion and bending stress
Pipe connections meet Group 2
according EN 161 requirements.
Ambient temperature
--15
E
C ... 60
E
C
Supply voltage
24 V, 50/60 Hz
110 V, 50/60 Hz
220 V, 50/60 Hz
240 V, 50/60 Hz
The applicable voltage is led to the
solenoid coil via a rectified circuit.
Dimensions
1000 series: See page 9
3000 series: See page 10
Electrical connection
Wiring on terminal block on box.
Cable entry Pg 11.
Coil insulation safety solenoid
valves
Insulation material according class F
Enclosure
IP 54
IP 65 on request
Capacity
See page 7 and 8
Maximum operating pressure
Model
Maximum operating
pressure (mbar)
VG .010
500
VG .015
500
VG .020
500
VG .025
500
VG .032
500
VG .040
500
VG .050
500
VG .065
350
VG .080
350
Power Consumption (W)
24 V, 50/60 Hz
110 V, 50/60 Hz
220 V, 50/60 Hz
240 V, 50/60 Hz
Model
number
At nominal
voltage
At 110% of
nominal
voltage
At nominal
voltage
At 110% of
nominal
voltage
At nominal
voltage
At 110% of
nominal
voltage
At nominal
voltage
At 110% of
nominal
voltage
VG .010
4
5
4
6
4,3
5
3
4
VG .015
4
5
4
6
4,3
5
3
4
VG .020
4
5
4
6
4,3
5
3
4
VG .025
4
5
4
6
4,3
5
3
4
VG .032
4
5
4
6
4,3
5
3
4
VG .040
4
5
4
6
4,3
5
3
4
VG .050
12,5
15
13
16
15,3
16
15
18
VG .065
12,5
15
13
16
15,3
16
15
18
VG .080
12,5
15
13
16
15,3
16
15
18