51-52-03-07
Page 8
Specifications
(continued)
Environmental and Operating Conditions
Parameter
Reference
Rated
Operative Limits
Transportation and storage
Ambient
Temperature
25
±
3
˚C
77
±
5
˚
F
15 to 55
˚
C
58 to 131
˚
F
0 to 55
˚
C
32 to 131
˚
F
-40 to 66
˚
C
-40 to 151
˚
F
Relative Humidity
10 to 55*
10 to 90*
5 to 90*
5 to 95*
Vibration
Frequency (Hz)
Acceleration (g)
0
0
0 to 70
0.1
0 to 200
0.5
0 to 200
0.5
Mechanical Shock
Acceleration (g)
Duration (ms))
0
0
1
30
5
30
20
30
Voltage (Vdc)
+24
±
1
20 to 27
20 to 27
- -
Voltage (Vac)
90 to 264Vac
(CSA models rated to 250V max.)
24Vac
120
±
1
240
±
2
24
±
1
90 to 264
20 to 27
90 to 264
20 to 27
- -
- -
- -
Frequency (Hz)
(For Vac)
50
±
0.2
60
±
0.2
49 to 51
59 to 61
48 to 52
58 to 62
- -
- -
*
The maximum rating only applies up to 40˚C (104˚F). For higher temperatures, the RH specification is derated to maintain constant moisture content.
Table 1 - Input Actuations
Range
PV Input
˚F
˚C
Thermocouples
B*
E*
E (low)
J
J (low)
K
K (low)
NiNiMoly (NNM)
NiNiMoly (NNM low))
NIC (Nicrosil Nisil)
R
S
T
T (low)
W5W26
W5W26 (low)
0
to 3300
-454
to 1832
-200
to 1100
0
to 1600
20
to 770
0
to 2400
-20
to 1000
32
to 2500
32
to 1260
0
to 2372
0
to 3100
0 to 3100
-300
to 700
-200
to 500
0
to 4200
0 to 2240
-18
to
1815
-270
to
1000
-129
to
593
-18
to
871
-7
to
410
-18
to
1316
-29
to
538
0
to
1371
0
to
682
-18
to
1300
-18
to
1704
-18
to
1704
-184
to
371
-129
to
260
-18
to
2316
-18
to
1227
RTD
(IEC) ALPHA = 0.00385
100 Ohms
100 Ohms (low)
500 Ohms
-300
to 1200
0
to 300
-300
to 1200
-184
to
649
-18
to
149
-184
to
649
Radiamatic RH
1400
to 3400
760
to 1871
Linear**
Milliamps
Millivolts
Volts
4
to 20 mA
0
to 10 mV
10
to 50 mV
1
to 5V
0
to 10V
Optional 2nd Input
Milliamps
Volts
Slidewire for Position
Proportioning
4
to 20 mA
1
to 5V
100
to 1000
Ω
* May require Field calibration to achieve rated accuracy below 1000
˚
F for type B and below -200
˚
F for type E thermocouple.
** Not available on FM approved Limit models.