Honeywell VCZA Series Скачать руководство пользователя страница 2

4. To replace a cartridge, 

isolate flow to the valve

 using installed shut 

off valves or other service equipment designed for this purpose. 

Remove old cartridge with 40007029-002 wrench supplied with 

the replacement unit. It may be necessary to use pliers or other 

tools to remove the old cartridge due to calcium or dirt buildup in 

the valve body.

5. Clean the valve surfaces marked 

*

 and 

**

 in Figure 6 to  ensure 

the new cartridge O-rings seal at these points.  Use care to avoid 

damage to these surfaces ( ** for 3-way valves only).

6. Remove the pre-lubricated cartridge assembly from its plastic 

bag. Thread it by hand into the valve body and tighten it down 

with the enclosed wrench until it bottoms out. DO NOT OVER 

TIGHTEN: maximum torque is 40 in-lb. [4.5 Nm]. The top 

surface of the cartridge should be flush with the top edge of the 

body casting.

7. Replace valve actuator by following the procedure in the "To Install 

Actuator" below.  

8. Reconnect leadwires or Molex™ connector if necessary.
9. Refill hydronic system or restore system flow by opening isolating 

valves.

10. Restore power, and checkout operation of cartridge in valve, making 

sure of no internal seat leakage or external body leakage.

Restore system pressure slowly to the valve to allow any trapped 

air to escape. Check for leaks. Re-install the actuator.

TO INSTALL ACTUATOR

NOTE: 

Installation of a new actuator does not require draining the 

system, provided the valve body and valve cartridge assembly 

remain in the pipeline.  Wiring may be done either before or after 

the actuator is installed.
Refer to the VC Actuator Installation and Instruction sheet for 

detailed wiring and check-out instructions.

1. The actuator head is automatically latched to the  valve.  Align 

the coupling hole in the bottom of the actuator with the valve 

stem.  Press the actuator down towards the body with moderate 

hand force and turn the actuator counter-clockwise by 1/8 turn 

(45 degrees) to line up the actuator with the piping.  The lock will 

click when engaged (See Figure 7).

NOTE:

 The actuator can also be installed at right angles to the 

valve body but in this position the lock mechanism will not 

engage.

2. Connect leadwires.
3. Restore power and check operations.

       Figure 7 - Lock Mechanism to detach Actuator

Figure 5 - Installing Cartridge             Figure 6

  

SERVICE

This valve should be serviced by a trained, experienced service 

technician.

1. 

If the valve is leaking, drain system 

OR 

isolate valve from the 

system. Do not remove valve body from plumbing.

2.

 Check to see if the cartridge needs to be replaced.

3.

 If the motor or other internal parts of the actuator is damaged, 

replace the entire actuator assembly.

NOTE:  

Honeywell VC series hydronic valves are designed and 

tested for silent operation in properly designed and installed 

systems.  However, water noises may occur as a result of 

excessive water velocity.  Piping noises may also occur in high 

temperature (over 212

o

F [100

o

C]) systems with insufficient water 

pressure.

*

*

**

Automation and Control Solutions

Environmental Control Products

1985 Douglas Drive North

Golden Valley, MN 55422-3992

In Canada:

Honeywell Limited-Limitee

35 Dynamic Drive, Toronto, ON M1V 4Z9

Отзывы: