Honeywell VC7900 Series Скачать руководство пользователя страница 5

VC7900 - WIRING, OPERATIONS 

NOTE:   The actuator can also be installed at right angles to the 

valve body but in this position the latch mechanism will 
not engage. 

5. Install the new actuator by reversing the process in (4). 
6. Reconnect leadwires or Molex

TM

 connector. 

7. Restore power, and check-out operation. 

MANUAL OPENER 
The manual opener can be manipulated only when in the up 
position.  The "A" port can be manually opened by firmly pushing 
the white manual lever down to midway and in.  In this position both 
the "A" and "B" ports are open, and with auxiliary switch models the 
switch is closed.  This "manual open" position may be used for 
filling, venting and draining the system, or for opening the valve in 
case of power failure.  The valve can be restored manually to the 
closed position by depressing the white manual lever lightly and 
then pulling the lever out.  The valve and actuator will return to the 
automatic position when power is restored. 

NOTE:   If the valve is powered open, it cannot be manually 

closed, unless actuator is removed. 

WIRING 

See figures 6a and 6b for single unit wiring details. 
Multiple valves may be connected in parallel to a single controller 
and transformer, up to the current rating of the controller and 
transformer. 

Fig. 6a - Connector Pin Configuration for Molex‘ Model 

and 0 / 2 – 10  Vdc Controllers (Series 70). 

+

0 -

10  Vdc 

6 5  4  
3 2  

L1 

(HOT) 

L2 

Fig. 6b - Wiring Colour Code for Cable Models and 

0 / 2 – 10  Vdc Controllers (Series 70). 

Brown 

Black 

Blue 

� 

� 

� 

L1 

(HOT) 

L2 

0 -

10  Vdc 

CONDUIT CONNECTION 

VC7934 may be installed as a plenum-rated cable model.  Where 
local codes require conduit , the conduit adapter may be used with 
empty 3/8" flexible conduit to provide mechanical protection for the 
wiring.  All wiring connections must be made in an approved 
electrical junction box.  Refer to figure 7. 

Fig.7 - VC valve actuator electrical conduit installation 

OPERATION 

WITH SERIES 70, 0 / 2 - 10 VDC  CONTROLLER 
(refer to figure 8) 
In the VC7900, an electronic circuit compares the voltage of the 
feedback potentiometer to the signal voltage.  If they are different, 
then the circuit closes the appropriate triac and drives the motor in 
the direction that will bring the circuit back into balance.  In 
addition, the standard limit switches maintain the travel to the 
normal operating range. 

Fig. 8 - Wiring Schematic of the VC7900 Series Actuators 

24 Vac 

0 -10  Vdc 

Motor 

Feedback

 Pot 

LS1 

LS2 

Blue 

Black 

Brown 

95C-10830-2

Содержание VC7900 Series

Страница 1: ...tems with temporary high head pressure Actuator is constructed of moisture and humidity resistant materials Motor de energiszes when valve not in motion extending service life Manualopenerandpositionindicator This manualopener may be used for filling venting and draining the system Twist lock actuator can be installed after plumbing work has been completed which makes for more efficient on site in...

Страница 2: ... actual 2 to 9 Vdc Input impedance 47 5 kΩ Power Consumption 4 Watts Max at nominal voltage during valve position change Note Use 24 V Class 2 transformer Provide 6 VA for connec tion wire sizing Maximum duty cycle 15 Nominal Timing Opens in 2 minutes 60Hz Actual full stroke timing is 140 sec Note Timing is approximately 20 longer 50Hz Electrical Termination 3 Versions Available 1 Molex header 39 ...

Страница 3: ... BSPP ext 94 3 11 16 113 4 7 16 22mm Compression 112 4 7 16 113 4 7 16 1 SWEAT 94 3 11 16 113 4 7 16 1 F NPT 94 3 11 16 113 4 7 16 1 BSPP int ext 94 3 11 16 113 4 7 16 28mm Compression 116 4 9 16 113 4 7 16 C E Dimensions Pipe fitting sizes mm Inches mm Inches 3 8 FLARE no adapter 98 3 7 8 136 5 11 32 1 2 SWEAT 98 3 7 8 136 5 11 32 1 2 F NPT 98 3 7 8 136 5 11 32 1 2 FLARE no adapter 98 3 7 8 136 5...

Страница 4: ... operation of this product good installation practice includes initial system flushing and the installation of 50 micron or finer system side stream filter s Fig 4 Plumbing the VC Valve COMPRESSION MODELS For compression fitted models tighten the compression nuts enough to make a watertight seal TAKE CARE NOT TO OVER TIGHTEN Maximum torque limit is 45 Nm 33 ft lb for the 22 mm compression fitting ...

Страница 5: ...lves may be connected in parallel to a single controller and transformer up to the current rating of the controller and transformer Fig 6a Connector Pin Configuration for Molex Model and 0 2 10 Vdc Controllers Series 70 0 10 Vdc 1 6 5 4 3 2 L1 HOT L2 Fig 6b Wiring Colour Code for Cable Models and 0 2 10 Vdc Controllers Series 70 Brown Black Blue L1 HOT L2 0 10 Vdc CONDUIT CONNECTION VC7934 may be ...

Страница 6: ...sted for silent operation in properly designed and installed systems However water noises may occur as a result of excessive water velocity Piping noises may also occur in high temperature over 212 F 100 C systems with insufficient water pressure IMPORTANT Do not use boiler additives which are petroleum based or contain mineral oil hydrocarbons or ethylene glycol acetate Compounds which can be use...

Отзывы: