V5097A-E INDUSTRIAL GAS VALVES

65-0230—07

2

ORDERING INFORMATION

When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the 

TRADELINE® Catalog or price sheets for complete ordering number.

If you have additional questions, need further information, or would like to comment on our products or services, please write or 

phone:

1.

Your local Honeywell Automation and Control Products Sales Office (check white pages of your phone directory).

2.

Honeywell Customer Care

1885 Douglas Drive North

Minneapolis, Minnesota 55422-4386

In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Toronto, Ontario M1V 4Z9.

International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, 

Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.

SPECIFICATIONS

IMPORTANT

The specifications in this publication do not include 

normal manufacturing tolerances; therefore, an 

individual unit may not exactly match the 

specifications listed. Also, this product is tested and 

calibrated under closely controlled conditions, and 

some minor differences in performance can be 

expected if those conditions are changed.

a

Refer to Table 3 or actual pressure ratings of the various combinations of valves and actuators.

b

Valve guide has notches to determine valve flow characteristics guide; provides a more linear relationship between stem travel 

and gas flow.

c

Valve seal overtravel interlock. Valve has two seals, and actuator has a proof-of-closure switch.

d

These combinations have higher pressure ratings; see Table 3.

e

Verify flow curve requirements to application requirements.

Models: 

See Table 2.

Table 1. Usual Combinations of Fluid Power Actuators and V5055 Industrial Gas Valves.

Fluid Power Actuators/

Industrial Gas Valves

Low pressure

a

High Pressure

a

V5097A

V5097B

V5097C

V5097D

V5097E

Type

Model

Pressure 

Rating

a

On-Off

Characterized 

Guide

b

VSOI

c

On-Off

VSOI

c

V4055

On-Off

A

Low

B

High

d

d

d

D

c

Low

E

c

High

d

d

V4062

Hi-Lo-Off

A

Low

D

c

Low

V9055

Modulating

A

Low

D

c

Low

e

e

Содержание V5097A-E

Страница 1: ...uid Power Actuators to provide proof of closure switch and valve seal overtravel interlock V5097D E Valves are for high pressure applications see Table 2 Two valve body types small and large applicable to seven pipe sizes Small body type for 3 4 in 19 mm 1 in 25 mm 1 1 4 in 32 mm 1 1 2 in 38 mm and 2 in 51 mm pipes Large body type for 2 in 51 mm 2 1 2 in 64 mm and 3 in 76 mm pipes Eight pipe adapt...

Страница 2: ...mal manufacturing tolerances therefore an individual unit may not exactly match the specifications listed Also this product is tested and calibrated under closely controlled conditions and some minor differences in performance can be expected if those conditions are changed a Refer to Table 3 or actual pressure ratings of the various combinations of valves and actuators b Valve guide has notches t...

Страница 3: ...dy Valve 8 0 lb 3 64 kg Small Body Pipe Adapters 67 lb 0 3 kg Large Body Pipe Adapters 2 125 lb 97 kg Replacement Parts 133393A Replacement Seal Assembly Includes valve seal bonnet seal and tube of lubricant for Small Body Valves 133392A Replacement Seal Assembly Includes valve seal bonnet seal and tube of lubricant for Large Body Valves For all pipe adapter sizes see Table 4 Replacement Bonnet As...

Страница 4: ...0 86 86 86 8 3 16 8 3 16 8 3 16 8 3 16 8 5 16 8 5 16 8 5 16 208 208 208 208 211 211 211 8 1 4 8 1 4 8 1 4 8 1 4 11 3 4 11 3 4 11 3 4 210 210 210 210 298 298 298 IN MM IN MM IN MM 62 62 62 62 91 91 91 5 5 5 5 8 8 8 127 127 127 127 203 203 203 58 58 58 58 113 113 113 23 23 23 23 38 38 38 100 100 100 100 165 165 165 71 71 71 71 114 114 114 3 4 1 1 1 4 1 1 2 2 2 1 2 3 M11682A ALLOW 2 IN 51 MM CLEARANC...

Страница 5: ...1 2 to 3 13 880 High Pressure Valves V5097D E 3 4 to 2 5 340 40 2700 75 5 25 1 6 62 4 75 5 2 to 3 13 880 45 3 15 1 21 1 4 45 3 6 3 4 171 1 9 32 33 D DIM A DIM B DIM C DIM D DIM E DIM F DIM G DIM H DIM J G E C A H F J OCTAGON OCTAGON 5 127 VALVE SIZE IN IN MM IN MM IN MM IN MM IN MM IN MM IN MM 11 1 8 11 1 8 11 1 8 11 1 8 11 3 4 11 3 4 11 3 4 283 283 283 283 298 298 298 2 3 4 2 3 4 2 3 4 2 3 4 3 3 ...

Страница 6: ...from step 4 for determining the gas valve size in Fig 4 6 Determine the maximum pressure drop across the valve and draw a horizontal line at this pressure in Fig 4 7 Draw a vertical line in Fig 4 at the capacity cfh previously determined Use the corrected capacity for a gas with a specific gravity other than 0 64 8 Use the valve size at the intersection of the horizontal and vertical lines If the ...

Страница 7: ...ed on 0 72 sp gr gas is required What valve capacity based on 0 64 sp gr gas will be required On the vertical scale of Fig 3 find 0 72 specific gravity left side of figure Draw a line horizontally from that point to the right to intersect the curve then move straight down the chart to the bottom scale and read the conversion factor 1 06 in this example Multiply the 2670 cfh by the conversion facto...

Страница 8: ...valve body The retained water is effectively excluded from the valve stem and spring chamber by a functional seal that is incorporated into the NEMA 4 rated actuator When Installing this Product 1 Read these instructions carefully Be sure to carefully fol low Warning information 2 Check the ratings given in the instructions and on the product to make sure the product is suitable for your applicati...

Страница 9: ...ate in the combustion chamber for longer than a few seconds without igniting to prevent an explosive mixture from accumulating WARNING Explosion Hazard Can cause serious injury or death 1 Do not put the system into service until you have satisfactorily completed the following Valve Leak Test all applicable tests described in the Checkout section of the instructions for the flame safeguard control ...

Страница 10: ...uator 1 Turn off the gas supply at the manual shutoff valve located upstream from the valve s being serviced 2 Shut off all electrical power to the valve actuator s 3 Mark and disconnect the wires from the actuator termi nals Remove conduit and disengage the damper link age assembly if applicable 4 Loosen the two set screws from the valve to lift off the actuator 5 If the actuator is to be replace...

Страница 11: ...r mechanical operation CAUTION Be sure to perform a bonnet seal and seat leak check after installation Be sure to read and follow all instructions that come with the actuators valves seal and bonnet kits Valve Bonnet Replacement The entire valve bonnet can be replaced without removing the valve body from the gas line Do not disassemble the valve bonnet assembly because the valve seat is not replac...

Страница 12: ... Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Toronto Ontario M1V 4Z9 customer honeywell com V5097A E INDUSTRIAL GAS VALVES U S Registered Trademark 2009 Honeywell International Inc 65 0230 07 M S Rev 08 09 ...

Отзывы: