Honeywell V5097A-E Скачать руководство пользователя страница 10

V5097A-E INDUSTRIAL GAS VALVES

65-0230—07

10

Table 6. V5097 Valve Allowable Leakage Rate.

a

Based on air at standard conditions, test pressures provided 

by ANSI Z21.21, Section 2.42 and a maximum of 235 

cc/h/in. of seal-off diameter (not pipe size).

Fig. 5. Valve leak test.

NOTE: For international leak test requirements, contact the 

appropriate approval agency.

After the Test

1.

Close the upstream manual gas cock (

A

).

2.

Close the test petcock (

F

), remove the test apparatus, 

and replace the leak test tap (

D

).

3.

Open the upstream manual gas cock (

A

) and energize 

the V5097 Valve actuator through the safety system.

4.

Test with rich soap and water solution to make sure there 

is no leak at the test tap (

D

) or any pipe 

adapter/valve mating surfaces.

5.

De-energize the V5097 Valve (

C

).

6.

Open the downstream manual gas cock (

E

).

7.

Restore the system to normal operation. If two safety 

shutoff valves are used, check each V5097 Valve for clo-

sure tightness.

SERVICE INFORMATION

WARNING

Explosion Hazard And Electrical Shock Hazard.

Can cause explosion, serious injury or death.

1. Turn off the gas supply and disconnect all electrical 

power to the valve actuator before servicing.

2. Properly position and seat the seals in the valve 

body to prevent a hazardous gas leak.

3. Do not disassemble the valve bonnet assembly 

because the valve seat is not replaceable.

IMPORTANT

Only trained, experienced flame safeguard control 

technicians should attempt to service or repair flame 

safeguard controls and burner assemblies.

Scheduled Inspection and Maintenance

Set up and follow a schedule for periodic inspection and 

maintenance for the burner, all other controls, and the valve(s) 

and actuator(s) for leaking oil. It is recommended that the valve 

leak test in the Operation and Checkout section be included in 

this schedule. Refer to the instructions for the primary safety 

control for more information.

Valve Checkout for Oil Leakage from Actuator

1.

Turn off the gas supply at the manual shutoff valve 

located upstream from the valve(s) being serviced. 

2.

Shut off all electrical power to the valve actuator(s). 

3.

Mark and disconnect the wires from the actuator termi-

nals. Remove conduit and disengage the damper link-

age assembly (if applicable).

4.

Loosen the two set screws from the valve to lift off the 

actuator.

5.

If the actuator is to be replaced and it did not leak 

hydraulic fluid, skip to Step 11.

NOTE: It is good practice to inspect the inside of the 

valve whenever the actuator is replaced. To do 

so, remove the bonnet assembly, inspect the 

valve and bonnet. If all is well, proceed to Step 7.

6.

If the actuator leaked hydraulic fluid onto the valve (the 

fluid is red), it must be cleaned off from the valve and 

bonnet assembly.

a. Wipe off the outer valve body.

b. Remove the valve bonnet bolts and lift off the bonnet.

NOTE: V5055/V5097C and E Valves have additional 

internal springs that will push the bonnet up as 

the bolts are loosened.

c. Inspect the inside of the valve.

IMPORTANT

If fluid is present on the inside surfaces of the valve 

body or bonnet surfaces, the bonnet assembly or 

entire valve must be replaced. For part numbers, see 

Table 5.

d. If the inside surfaces are clear of hydraulic fluid, 

clean the bonnet assembly and be sure to remove all 

hydraulic fluid from the inside and outside of the 

actuator mounting curb. This is the “cup-like” area 

V5097 

Pipe 

Adapter 

Size (in.)

Medium

Allowable 

Leakage 

SCCH

Maximum 

No. of 

Bubbles in 

10 sec. )

Minimum 

No. of 

Seconds 

for 10 

bubbles 

3/4, 1, 

1-1/4, 

1-1/2, 2

0.64 gas

573

14

6.7

1.00 air

a

458

9

10.2

1.57 LP

366

9

10.5

2, 2-1/2, 3 0.64 gas

940

24

4.1

1.00 air

a

752

16

6.2

1.57 LP

602

15

6.4

M9547F

GAS

SUPPLY

UPSTREAM

MANUAL

GAS COCK

DOWNSTREAM

MANUAL

GAS COCK

BURNER

   D

A

B

C

E

F

PRV

MANUAL

TEST

PETCOCK

SSOV

1/4 IN. (6 MM) 

FLEXIBLE

TUBING
1/4 IN. (6 MM)

ALUMINUM OR 

COPPER PILOT 

TUBING

JAR OR GLASS

WITH WATER

CUT AT

45 DEGREE

ANGLE

CAN ALSO BE A PERMANENT PETCOCK.

PRV = PRESSURE REGULATING VALVE.

SSOV = SAFETY SHUTOFF VALVE.

 USE ONLY ONE OF THE DOWNSTREAM TAPS ON THE SS0V.

1

2

3

4

4

2

3

1

1

2

(13 MM)

LEAK 

TEST 

TAP

Содержание V5097A-E

Страница 1: ...uid Power Actuators to provide proof of closure switch and valve seal overtravel interlock V5097D E Valves are for high pressure applications see Table 2 Two valve body types small and large applicable to seven pipe sizes Small body type for 3 4 in 19 mm 1 in 25 mm 1 1 4 in 32 mm 1 1 2 in 38 mm and 2 in 51 mm pipes Large body type for 2 in 51 mm 2 1 2 in 64 mm and 3 in 76 mm pipes Eight pipe adapt...

Страница 2: ...mal manufacturing tolerances therefore an individual unit may not exactly match the specifications listed Also this product is tested and calibrated under closely controlled conditions and some minor differences in performance can be expected if those conditions are changed a Refer to Table 3 or actual pressure ratings of the various combinations of valves and actuators b Valve guide has notches t...

Страница 3: ...dy Valve 8 0 lb 3 64 kg Small Body Pipe Adapters 67 lb 0 3 kg Large Body Pipe Adapters 2 125 lb 97 kg Replacement Parts 133393A Replacement Seal Assembly Includes valve seal bonnet seal and tube of lubricant for Small Body Valves 133392A Replacement Seal Assembly Includes valve seal bonnet seal and tube of lubricant for Large Body Valves For all pipe adapter sizes see Table 4 Replacement Bonnet As...

Страница 4: ...0 86 86 86 8 3 16 8 3 16 8 3 16 8 3 16 8 5 16 8 5 16 8 5 16 208 208 208 208 211 211 211 8 1 4 8 1 4 8 1 4 8 1 4 11 3 4 11 3 4 11 3 4 210 210 210 210 298 298 298 IN MM IN MM IN MM 62 62 62 62 91 91 91 5 5 5 5 8 8 8 127 127 127 127 203 203 203 58 58 58 58 113 113 113 23 23 23 23 38 38 38 100 100 100 100 165 165 165 71 71 71 71 114 114 114 3 4 1 1 1 4 1 1 2 2 2 1 2 3 M11682A ALLOW 2 IN 51 MM CLEARANC...

Страница 5: ...1 2 to 3 13 880 High Pressure Valves V5097D E 3 4 to 2 5 340 40 2700 75 5 25 1 6 62 4 75 5 2 to 3 13 880 45 3 15 1 21 1 4 45 3 6 3 4 171 1 9 32 33 D DIM A DIM B DIM C DIM D DIM E DIM F DIM G DIM H DIM J G E C A H F J OCTAGON OCTAGON 5 127 VALVE SIZE IN IN MM IN MM IN MM IN MM IN MM IN MM IN MM 11 1 8 11 1 8 11 1 8 11 1 8 11 3 4 11 3 4 11 3 4 283 283 283 283 298 298 298 2 3 4 2 3 4 2 3 4 2 3 4 3 3 ...

Страница 6: ...from step 4 for determining the gas valve size in Fig 4 6 Determine the maximum pressure drop across the valve and draw a horizontal line at this pressure in Fig 4 7 Draw a vertical line in Fig 4 at the capacity cfh previously determined Use the corrected capacity for a gas with a specific gravity other than 0 64 8 Use the valve size at the intersection of the horizontal and vertical lines If the ...

Страница 7: ...ed on 0 72 sp gr gas is required What valve capacity based on 0 64 sp gr gas will be required On the vertical scale of Fig 3 find 0 72 specific gravity left side of figure Draw a line horizontally from that point to the right to intersect the curve then move straight down the chart to the bottom scale and read the conversion factor 1 06 in this example Multiply the 2670 cfh by the conversion facto...

Страница 8: ...valve body The retained water is effectively excluded from the valve stem and spring chamber by a functional seal that is incorporated into the NEMA 4 rated actuator When Installing this Product 1 Read these instructions carefully Be sure to carefully fol low Warning information 2 Check the ratings given in the instructions and on the product to make sure the product is suitable for your applicati...

Страница 9: ...ate in the combustion chamber for longer than a few seconds without igniting to prevent an explosive mixture from accumulating WARNING Explosion Hazard Can cause serious injury or death 1 Do not put the system into service until you have satisfactorily completed the following Valve Leak Test all applicable tests described in the Checkout section of the instructions for the flame safeguard control ...

Страница 10: ...uator 1 Turn off the gas supply at the manual shutoff valve located upstream from the valve s being serviced 2 Shut off all electrical power to the valve actuator s 3 Mark and disconnect the wires from the actuator termi nals Remove conduit and disengage the damper link age assembly if applicable 4 Loosen the two set screws from the valve to lift off the actuator 5 If the actuator is to be replace...

Страница 11: ...r mechanical operation CAUTION Be sure to perform a bonnet seal and seat leak check after installation Be sure to read and follow all instructions that come with the actuators valves seal and bonnet kits Valve Bonnet Replacement The entire valve bonnet can be replaced without removing the valve body from the gas line Do not disassemble the valve bonnet assembly because the valve seat is not replac...

Страница 12: ... Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Toronto Ontario M1V 4Z9 customer honeywell com V5097A E INDUSTRIAL GAS VALVES U S Registered Trademark 2009 Honeywell International Inc 65 0230 07 M S Rev 08 09 ...

Отзывы: