background image

V4055F,G FLUID POWER ACTUATOR WITH MANUAL CONTROL

5

65-0029—01

Mount Actuator On Valve

Check the final position of the valve body to be sure that the 

actuator will be in the proper position when mounted on the 

valve.

If two smaller size valves are mounted very close together, as 

in an Industrial Risk Insurers (formerly F.I.A.) type valve train, it 

may be necessary to mount the actuator “off center” to provide 

adequate clearance.

Slip the bottom collar of the actuator over the valve bonnet 

assembly. Rotate the actuator to the desired position and use a 

5/32 inch Allen wrench to tighten the two setscrews securely 

(50 to 60 Ib.-in. [5.7 to 6.8 N.m]).

WIRING

Disconnect power supply before making wiring connections to 

prevent electrical shock and equipment damage. Wiring must 

comply with all applicable electrical codes, ordinances, and 

regulations. Wiring to the actuator must be NEC Class 1.

Connect the power supply to terminals 1 and 2 on the V4055 

terminal strip. Refer to Fig. 3 for auxiliary switch connections. 

For typical system hookups, refer to instructions packed with 

device used to control valve.

When all wiring connections are complete, replace the actuator 

faceplate.

Fig. 3. External connections to the V4055 actuator.

Adjust The Auxiliary Switch (If Used)

The auxiliary switch is adjustable throughout the stroke of the 

actuator. With the switch installed in the actuator, turn the 

adjusting screw (Fig. 2) clockwise 

 to cause the switch to 

operate earlier in the stroke or counterclockwise 

 to 

cause the switch to operate later in the stroke.

NOTE: The valve-closed indication switch is not adjustable.

CHECKOUT AND SERVICE

CAUTION

Only a trained, experienced, flame safeguard 

control service technician should check out and 

service this control.

Checkout

After the installation is complete, cycle the valve several times 

with the manual fuel shutoff cock closed before testing the 

system in actual operation.

Service

The actuator is not field repairable, except for replacing the 

auxiliary switch, valve-closed indication switch, and READY 

TO OPEN light. See INSTALLATION section for procedure. Do 

not disassemble the valve actuator.

If the actuator should fail to operate properly, replace it.

1.

Turn off the gas supply at the manual shutoff valve 

located upstream from the valve(s) being serviced. 

2.

Shut off all electrical power to the valve actuator(s). 

3.

Mark and disconnect the wires from the actuator termi-

nals. Remove conduit and disengage the damper link-

age assembly (if applicable. 

4.

Loosen the two set screws from the valve to lift off the 

actuator.

5.

If the actuator is to be replaced and it did not leak 

hydraulic fluid, skip to Step 11.

NOTE: It is good practice to inspect the inside of the 

valve whenever the actuator is replaced. To do 

so, remove the bonnet assembly, inspect the 

valve and bonnet. If all is well, proceed to Step 7.

6.

If the actuator leaked hydraulic fluid onto the valve (the 

fluid is red), it must be cleaned off from the valve and 

bonnet assembly.

a. Wipe off the outer valve body.

b. Remove the valve bonnet bolts and lift off the bonnet.

NOTE: V5055/V5097C and E Valves have additional 

internal springs that will push the bonnet up as 

the bolts are loosened.

c. Inspect the inside of the valve.

IMPORTANT

If fluid is present on the inside surfaces of the valve 

body or bonnet surfaces, the bonnet assembly or 

entire valve must be replaced. See Table 3 below for 

the bonnet assembly part number.

1

2

3

2

1

1

2

AUXILIARY

SWITCH

L1

HOT

L2

POWER SUPPLY. PROVIDE OVERLOAD PROTECTION AND 

DISCONNECT MEANS AS REQUIRED.

SWITCH BETWEEN THESE TWO LEADS IS CLOSED WHEN 

VALVE IS SHUT (DE-ENERGIZED).

3 SWITCH BETWEEN THESE TWO LEADS IS OPEN WHEN 

VALVE IS SHUT (DE-ENERGIZED).

NO

NC

C

NO

NC

C

PROOF-OF-CLOSURE

SWITCH

2

3

M7334A

Содержание V4055F

Страница 1: ...ow only when the gas valve is fully closed Ambient temperature rating of 40 F to 150 F 40 C to 66 C Valve and actuator may be mounted in any position Optional field adjustable spdt auxiliary switch rated at 112 hp 0 37 kW may be added in the field Standard enclosure meets NEMA 1 IP30 general purpose requirements Red light indicates when valve is ready to open Rocker switch allows manual operation ...

Страница 2: ...0 Hz and 50 60 Hz models Mounting Means Actuator mounts directly to valve bonnet with 2 setscrews positioned 90 angular degrees apart Valve and actuator can be mounted in any position Mounting Dimensions See Fig 1 Replacement Parts 130928 Red Indicator Lamp Accessories 133568 Auxiliary Switch Bag Assembly 133569 Valve Closed Indication Switch Bag Assembly Approvals UL and FM IRI Approvable Electri...

Страница 3: ...HOLES 8 ON 3 3 4 95 RADIUS M23960 3 4 1 1 1 4 1 1 2 2 2 1 2 3 4 VALVE SIZE INCH 13 1 8 13 1 8 13 1 8 13 1 8 13 1 4 13 3 4 13 3 4 16 3 16 333 5 333 5 333 5 333 5 336 5 349 0 349 0 411 0 2 3 4 2 3 4 2 3 4 2 3 4 2 7 8 3 3 8 3 3 8 5 13 16 70 0 70 0 70 0 70 0 73 0 85 5 85 5 128 0 8 3 16 8 3 16 8 3 16 8 3 16 8 5 16 8 13 16 8 13 16 11 7 32 208 0 208 0 208 0 208 0 211 1 224 0 224 0 285 0 5 3 4 5 3 4 5 3 4...

Страница 4: ... seal Fig 2 V4055 actuator with cover removed NOTE A V5055A B or D valve can also be fitted with a bon net assembly with 2 seals to provide a valve seal overtravel interlock The SPDT valve closed indication switch is installed to make or break a circuit when the valve is in the closed position The switch is not adjustable NOTE Mark the actuator or valve to indicate any changes made To install the ...

Страница 5: ...he installation is complete cycle the valve several times with the manual fuel shutoff cock closed before testing the system in actual operation Service The actuator is not field repairable except for replacing the auxiliary switch valve closed indication switch and READY TO OPEN light See INSTALLATION section for procedure Do not disassemble the valve actuator If the actuator should fail to opera...

Страница 6: ...ds 12 Replace the damper crank arm assembly 13 Re attach the wires removed from the actuator terminals and turn on the electrical power 14 With the gas still off cycle the actuator to check for proper mechanical operation CAUTION Be sure to perform a bonnet seal and seat leak check after installation Be sure to read and follow all instructions that come with the actuators valves seal and bonnet ki...

Страница 7: ...V4055F G FLUID POWER ACTUATOR WITH MANUAL CONTROL 7 65 0029 01 ...

Страница 8: ... Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Toronto Ontario M1V 4Z9 customer honeywell com V4055F G FLUID POWER ACTUATOR WITH MANUAL CONTROL U S Registered Trademark 2007 Honeywell International Inc 65 0029 01 M S Rev 06 07 ...

Отзывы: