Honeywell V4044C Скачать руководство пользователя страница 2

V4044C, V4044F 

EN0H-0325GE25 R0906 

Honeywell • All rights reserved 

Function 

V4044C and V4044F  2-position hydronic valves are used in 

domestic and small commercial applications to control the 

flow of hot or cold water. They consist of an actuator and a 

valve. 
With the manual opener set to AUTO and the actuator 

energized, port A of the valve is opened and port B is closed. 

When the actuator is de-energized, a spring-return 

mechanism drives the ball to close port A, opening port B. 

Port A can also be opened with no electrical power by moving 

the manual opening lever over the stop and pushing slowly 

and firmly to the MAN. OPEN position. The stop permits the 

valve to be locked with port A in the open position. The valve 

returns to the automatic position when the valve is energized. 

A power failure will leave the valve at the spring-returned 

position. When power is restored, the valve will respond to 
controller demand. 

 

 

Fig. 1.  V4044C/F in 

energized position (AB-A) 

Fig. 2.  V4044C/F in de-

energized position (AB-B) 

 
NOTE:  Port AB is always open 

 
 

Wiring 

 

 

 

Fig. 3.  Wiring diagram for V4044C 

Fig. 4.  Wiring diagram for 

V4044F1034 

Fig. 5.  Wiring diagram for 

V4044F1000 

 

Table 1.  Cable colour coding 

a b c d e h 

brown blue 

green/yellow 

orange grey  white 

 
NOTE:  The V4044C has no end switch. It is equipped with a 3 wire cable (line, neutral, earth) 
 

The V4044F1034 has an SPST end switch. It is equipped with a 5-wire cable (line, neutral, earth, end switch). The end 

switch closes when the valve is in position AB – B 

 

The V4044F1000 has an SPDT end switch. It is equipped with a 6-wire cable (line, neutral, earth, end switch NO, end 
switch NC) 

 

The length of all cables is 1m 

 

Содержание V4044C

Страница 1: ...tage SPST controller such as a room thermostat aquastat or flow switch The actuator head is removable without affecting the integrity of the water system Features Rugged design Control by a line voltage SPST controller Actuator head installation does not require draining of the system High flow rate capacity Indifferent to dirt in system Specifications Medium Water or water glycol mixture max 50 g...

Страница 2: ...valve returns to the automatic position when the valve is energized A power failure will leave the valve at the spring returned position When power is restored the valve will respond to controller demand Fig 1 V4044C F in energized position AB A Fig 2 V4044C F in de energized position AB B NOTE Port AB is always open Wiring Fig 3 Wiring diagram for V4044C Fig 4 Wiring diagram for V4044F1034 Fig 5 ...

Страница 3: ...ar 1 96 46 128 NOTE All dimensions in mm if not otherwise stated Ordering Information Table 3 Order information and OS Nos OS Ordering System Order text Size End switch Packing unit OS No 1 2 1 pc V4044C1452 3 4 1 pc V4044C1460 V4044C motorized zone valve 1 1 pc V4044C1478 3 4 SPST 1 pc V4044F1000 V4044F motorized zone valve with end switch 1 SPDT 1 pc V4044F1034 3 4 SPST 10 pcs V4044F1000B V4044F...

Страница 4: ...393 www honeywell com EN0H 0325GE25 R0906 September 2006 2006 Honeywell International Inc Subject to change All rights reserved Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl Ecublens Route du Bois 37 Switzerland or by its Authorized Representative ...

Отзывы: