background image

L/5192/D
May 2009
© 2009 Honeywell International Inc. 

ORDERING

5192SD

Addressable Photoelectric Smoke Detector

5192SDT

Addressable Photoelectric Smoke Detector with Integral Heat Sensor

SPECIFICATIONS

5192SD/5192SDT

V-PLEX™ SMOKE DETECTOR 

Installation

The 5192 Series smoke detectors are
supplied with a convenient mounting
bracket that allows the detector to 
be mounted to a variety of electrical
junction boxes. A removable terminal
block, that accepts 14 to 22 gauge wire
to provide easy wiring connections. The
detectors are designed to meet 
all applicable requirements for UL
Commercial and Residential Fire
installations as well as NFPA 72
requirements when installed in
compliance with the National 
Electric Code and approved/listed control
panels.

CompatibilIty

These smoke detectors are compatible
with all VISTA control panels that support
V-Plex (addressable) polling 
loop technology. The detectors support
DIP switch or serial number addressing.
DIP switch configuration are compatible 
with 5140XM, VISTA-40, and 
VISTA-50P controls. 

Serial number addressing is supported on
VISTA-32FB, 128BP, 128FBP, 250BP,
250FBP, 100-24 and FAP FA1600C,
FA1660C and FA1700C controls. (Refer to
control panel and smoke detector
installation instructions for details.)

Automatic Maintenance 

Reporting Compatibility

The automatic maintenance feature is
compatible with the following control
panels:

– VISTA-32FB
– VISTA-128BP
– VISTA-128FBP
– VISTA-250BP
– VISTA-250FBP
– FA1600C
– FA1660C
– FA1700C

The automatic maintenance may be
disabled for all other controls that 
do not support this feature. Refer 
to control panel and smoke detector
Installation Instructions for details.

Electrical:

• System voltage range: 7-14 V

Standby current (maximum @ 12V):
– LED off: 1.2mA
– LED on: 2.8mA

Mechanical:

• Diameter: 5.5 inches (140mm) (including

mounting bracket)

• Height: 1.7 inches (43mm) 

(including mounting bracket)

• Weight: 5.3 ounces (150 grams)

Environmental:

• Installation temperature range:

32° to 100°F (0° to 38°C)

• Installation humidity range:

10% to 93% RH, non-condensing

• Heat sensor (5192SDT only):

135°F fixed temperature 
electronic thermistor

• EMI: Meets or exceeds the 

following requirements:
– FCC Part 15, Class B Device
– IEC EMC Directive

Agency Listings

• UL268 Commercial System 

Smoke Detector

• Meets UL 217 Requirements 

for Residential

VIST

A

SERIES UL

LISTED

COMP

A

TIBLE CONTROL

P

ANEL

REMOVABLE
TERMINAL BLOCK

DIP
SWITCH

Wiring diagram for 5192SD/SDT smoke detector