Honeywell UVL-COIL-60D Скачать руководство пользователя страница 5

UVL-COIL ULTRAVIOLET LAMP KITS FOR AHU COILS

5

31-00402—02

INSTALLATION

When Installing This Product…

1.

Read these instructions carefully. Failure to follow 
them could damage the product or cause a hazard-
ous condition.

2.

Check the ratings given in the instructions and on the 
product to make sure the product is suitable for your 
application.

3.

Installer must be a trained, experienced service tech-
nician.

4.

After installation is complete, check out product 
operation as provided in these instructions.

WARNING

Electric Shock Hazard.
Can cause electrical shock or equipment damage.

Do not connect to power before installation is 
complete.

Assemble Conduit Framework

1.

Measure and cut tubing to length then slide on con-
duit/lamp clamps (Fig. 5.), do not fully tighten bolts 
yet.

Fig. 5. Slide on Hardware.

2.

Use self-tapping screws to attach L-brackets to the 
air handler wall or supporting structure. Then use the 
½ inch pip clamps to attach the tubing sections to 
the L-Brackets. (Fig. 6.)

Fig. 6. Mount L-bracket and Tubing.

3.

An optional vertical support adds strength to the 
conduit tubing to support framework and prevents 
sagging on installations with three or more lamps per 

tubing length. Measure the distance from floor to 
ceiling then measure and cut tubing 1.75 inches less 
than that length. Use ½ inch pipe coupling to extend 
the vertical support to the floor and ceiling for a snug 
fit. (Fig. 7.)

Fig. 7. Optional Vertical Support.

Install UV Lamps

Snap UV Lamps into the lamp/conduit clamps. Be sure to 
clamp to the rubber lamp connector on one end and the 
ceramic lamp tip on the other end. DO NOT clamp onto the 
lamp glass. Use black nylon zip-ties to secure lamp cables 
to tubular rack components and/or supports.

CAUTION

Breakable Glass Hazard.
Can cause personal injury.

Be careful when inserting bulb(s) into lamp base. 
Wear protective gloves when handling bulb(s).

MERCURY NOTICE

This device contains mercury in the sealed 
ultraviolet bulb(s). Do not place your used bulb(s) in 
the trash. Dispose of properly.

Broken Bulb Cleanup

Do not use a household vacuum. Sweep debris into a 
plastic bag and dispose of properly.

Contact your local waste management authority for 
instructions regarding recycling and the proper disposal of 
old bulb(s).

Conduit

Conduit/
conduit 
Clamp

Vertical Support

1/2” Pipe Coupling

1/2” Pipe Coupling

Содержание UVL-COIL-60D

Страница 1: ...nside of air handlers or the exposed conditions of outdoor packaged air conditioning systems The number and placement of lamps is determined by the coil dimensions FEATURES UV C light irradiates coil air handler interior killing mold bacteria and viruses Scalable design allows wide variety of multi lamp configurations High quality water resistant lamps Mounts using off the shelf inch EMT conduit t...

Страница 2: ...mm length UV C Power UVL 32 LAMP 28 W UVL 60 LAMP 54 W Output at 1 Meter UVL 32 LAMP 250 μW cm2 UVL 60 LAMP 395 μW cm2 Spectrum 100 254 nm Germicidal UV C Bulb Type Shielded Quartz Hot Filament Bulb Life 18 000 hours Accessories UVL 32 LAMP 32 inch replacement lamp UVL 60 LAMP 60 inch replacement lamp Table 1 Models Power supply not available for purchase outside of kit Part Number Description Rep...

Страница 3: ...unting use optimal irradiation distance Fig 2 and lamp spacing Fig 3 diagrams to confirm than when installed the UV lamps will be positioned properly The UV lamps are mounted onto a framework of EMT tubing When two or more UV lamps are supported on a single length of EMT it is recommended to add an optional vertical support Fig 4 Table 2 Sizing Based on Coil Dimensions Table 3 Sizing Based on Unit...

Страница 4: ...based on coil size WARNING Be careful of damage to equipment Ultraviolet light can cause color fading or degraded structure of plastic material found in HVAC equipment avoid plastic material or equipment with unknown performance against ultraviolet light in the area of irradiation WARNING UV Light Hazard Harmful to bare skin and eyes Can cause temporary or permanent loss of vision Do not look at t...

Страница 5: ...h to the conduit tubing to support framework and prevents sagging on installations with three or more lamps per tubing length Measure the distance from floor to ceiling then measure and cut tubing 1 75 inches less than that length Use inch pipe coupling to extend the vertical support to the floor and ceiling for a snug fit Fig 7 Fig 7 Optional Vertical Support Install UV Lamps Snap UV Lamps into t...

Страница 6: ...ower supply to the main power Fig 10 Electrical Connections Connect Lamps and Cables Arrange cables as needed for installation If necessary use cable strain relief fittings or other means to pass cables through the cabinets or air system walls When UV lamps power supplies and cables are in place join the lamp and power supply cables by aligning the electrical pins and flanges on the rubber connect...

Страница 7: ...upply off then on 6 Install New UV Lamp s 7 Consult Factory UV Lamp s Flickering 1 UV Lamp s have reached end of effective service life Install new lamp s of same type 2 If unit is new check remote cables to ensure they are properly con nected 3 Reset power switch on power supply off then on 4 If new lamps still flicker consult factory UV Lamps Have burned Out Prematurely 1 Consult Factory Power S...

Страница 8: ...well Building Technologies In the U S Honeywell 715 Peachtree Street NE Atlanta GA 30308 customer honeywell com buildingcontrols honeywell com U S Registered Trademark 2020 Honeywell International Inc 31 00402 02 M S Rev 09 20 Printed in United States ...

Отзывы: