Honeywell UV100E1043 Скачать руководство пользователя страница 3

UC100 ULTRAVIOLET SYSTEM REPLACEMENT BULB/HANDLE ASSEMBLY

3

69-1444—5

Fig. 4. Position lamp handle for insertion back into 

the lamp base.

8.

Rotate the lamp handle clockwise until it snaps into 

place with the light indicator aligned with the raised 

button on the unit cover. See Fig. 5.

Fig. 5. Snap lamp handle into place.

9.

Reconnect power to your UV System.

10.

For UV Air Treatment System SmartLamp™ models, 

wait ten minutes for the airflow sensor to calibrate. 

During this time, the furnace fan must remain off.

NOTE: Failure to wait ten minutes for the airflow sensor to 

calibrate before powering the system fan causes the 

airflow sensor to incorrectly calibrate and the device 

to incorrectly function. If this occurs, remove power 

to the furnace or turn off the system fan, wait ten 

minutes, and then resume normal fan operation.

WARNING

UV Light Hazard.

Harmful to bare skin and eyes.

Can cause temporary or permanent loss of vision.

Never look at bulbs while illuminated. 

View illumination only through light indicator located 

on lamp handle.

To prevent exposure to ultraviolet light, disconnect 

power to Ultraviolet System before servicing any part 

of heating and air conditioning system.

11.

Verify that your ultraviolet bulbs are operating by 

viewing only through the lamp light indicator on the lamp 

handle. Never look directly at your lamp while it is 

illuminated.

12.

Reconnect the power to your heating and cooling

system.

13.

For SmartLamp™ models, press and hold the reset 

button for five seconds to reset the internal timers.

M22847

M22849

Table 1. Replacing Your Bulb(s) and Handle Assembly.

Unit Description

Replacement Bulb/

Handle Assembly

SnapLamp™ 

Replacement Bulb

Wattage

UV100E1001 and UV100E1043 

Air Treatment Systems 

UC100E1006

UC18W

18W

UV100E1019 and UV100E2009 

Air Treatment Systems (dual lamp)

UC100E1030 (2 needed)

UC36W (two bulbs required)

36W

UV100E1027 Surface Treatment System 

UV100A1021

N/A

25W

UV100E1035 and UV100E3007 

Surface Treatment Systems

UC100E1030

UC36W

36W

UV100A1000 Air Treatment System

UC100A1005

UC18W

18W

UV100A1018 Air Treatment System (dual lamp)

UC100A1054 (2 needed)

UC36W (two bulbs required)

36W

UV100A1026 Surface Treatment System

UC100A1021

N/A

25W

UV100A1059 Surface Treatment System

UC100A1054

UC36W

36W

UV100A2008 Surface Treatment System

UC100A1054

UC36W

36W

Содержание UV100E1043

Страница 1: ...te check out product operation as provided in these instructions CAUTION Personal Injury Hazard Power supply can cause electrical shock Disconnect power supply before replacing ultraviolet bulb s Do not open base unit or lamp handle there are no user serviceable components inside WARNING UV Light Hazard Harmful to bare skin and eyes Can cause temporary or permanent loss of vision Never look at bul...

Страница 2: ...s Annual replacement of your bulbs is required To replace your bulbs 1 Select and obtain the correct replacement bulb for your unit See Table 1 2 Disconnect the power to your heating and cooling system 3 Unplug or turn off power to your UV System and allow the bulbs to cool for at least 15 minutes 4 Rotate the lamp handle counterclockwise and gently pull the lamp handle to remove the bulb See Fig ...

Страница 3: ... exposure to ultraviolet light disconnect power to Ultraviolet System before servicing any part of heating and air conditioning system 11 Verify that your ultraviolet bulbs are operating by viewing only through the lamp light indicator on the lamp handle Never look directly at your lamp while it is illuminated 12 Reconnect the power to your heating and cooling system 13 For SmartLamp models press ...

Страница 4: ...Control Solutions Honeywell International Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Toronto Ontario M1V 4Z9 customer honeywell com U S Registered Trademark 2006 Honeywell International Inc 69 1444 5 M S Rev 10 06 ...

Отзывы: