Installation
2.5 Mounting
Physical Considerations
The controller can be mounted on either a vertical or tilted panel using the mounting kit
supplied. Adequate access space must be available at the back of the panel for installation
and servicing activities.
•
Overall dimensions and panel cutout requirements for mounting the controller are
shown in Figure 2-2.
•
The controller’s mounting enclosure must be grounded according to CSA standard
C22.2 No. 0.4 or Factory Mutual Class No. 3820 paragraph 6.1.5.
•
The front panel is moisture rated NEMA3 and IP55 rated and can be easily upgraded
to NEMA4X and IP66. (See Mounting Method, page 19)
Overall Dimensions
Max. panel thickness
19,1
.75
Panel
Cutout
92,0 + 0,8
- 0,00
3,62 + 0,03
-0,00
92,0 + 0,8
- 0,00
3,62 + 0,03
-0,00
mm
inches
17,9
0,70
113,1
4,45
90,6
3,57
108,6
4,28
9,0
0,35
Figure 2-2 Mounting Dimensions (not to scale)
Mounting Notes
Before mounting the controller, refer to the nameplate on the outside of the case and
make a note of the model number. It will help later when selecting the proper wiring
configuration.
18
UDC3200 Universal Digital Controller Product Manual
12/04
Содержание UDC3200 series