Modbus Read, Write and Override Parameters plus Exception Codes
10.7.7 Input
2
Table 10-15 lists all the register addresses and ranges or selections for the function
parameters in Set-up Group Input 2.
Table 10-15 Set-up Group – Input 2
Parameter
Description
Register
Address
Access
Data Range or
Enumerated Selection
Hex Decimal
Input 2 Type
00AA 170
INT
R/W
0 = Disable
1 = B TC
2 = E TC H
3 = E TC L
4 = J TC H
5 = J TC M
6 = J TC L
7 = K TC H
8 = K TC M
9 = K TC L
10 = NNM H
11 = NNM L
12 = Nicrosil H TC
13 = Nicrosil L TC
14 = R TC
15 = S TC
16 = T TC H
17 = T TC L
18 = W TC H
19 = W TC L
20 = 100 PT RTD
21 = 100 PT LO RTD
22 = 200 PT RTD
23 = 500 PT RTD
24 = Radiamatic RH
25 = Radiamatic RI
26 = 0-20 mA
27 = 4-20 mA
28 = 0-10 mV
29 = 0-50 mV
30 = 0-100 mV
31 = 0-5 Vdc
32 = 1-5 Vdc
33 = 0-10 Vdc
34 = Slidewire
35 = Unused
36 = Unused
37 = Thermocouple Differential
ATTENTION
Changing the Input Type will result in the loss of Field Calibration
values and will restore the Factory Calibration values.
Data
Type
206
UDC3200 Universal Digital Controller Product Manual
12/04