Modbus Read, Write and Override Parameters plus Exception Codes
10.7 Configuration Parameters
Overview
Listed on the next pages are the identifying codes for the parameters in the various Set-up
Groups in the UDC3200 Process Controller. Most of the parameters are configurable
through the hosts. Some are Read Only and are indicated as such and cannot be changed.
Reading or Writing
Do a Read or Write, depending on your requirements, using the identifying code and
format code listed in the tables. The range or selection available for each range is listed in
the tables.
10.7.1 Tuning
Table 10-9 lists all the register addresses and ranges or selections for the function
parameters in the Set-up Group Tuning.
Table 10-9 Set-up Group – Tuning
Parameter
Description
Register
Address
Data
Type
Access
Data Range or
Enumerated Selection
Hex
Decimal
Gain #1 or PB
Note 1
0001
001
FP
R/W
0.01 to 1000 Gain
0.1 to 1000 PB
Rate #1
Note 1
0002
002
FP
R/W
0.00 to 10.00
Reset #1
Note 1
0003
003
FP
R/W
0.02 to 50.00
Manual Reset
000D 013
FP
R/W
–100 to +100
Gain #2 or PB #2
Note 1
0004
004
FP
R/W
0.01 to 1000 Gain
0.1 to 1000 PB
Rate #2
Note 1
0005
005
FP
R/W
0.00 to 10.00
Reset #2
Note 1
0006
006
FP
R/W
0.02 to 50.00
Cycle Time #1
0015
21
INT
R/W
1 to 120 seconds
Cycle Time #2
0016
22
INT
R/W
1 to 120 seconds
192
UDC3200 Universal Digital Controller Product Manual
12/04