U2 COMBINATION VIEWING HEAD AND SIGNAL PROCESSORS
66-2071—02
10
IRDA
Enables or disables communications through the palm.
Enabled by default.
RS485
Sets modbus to either READ ONLY or read and writable
(WRITE OK). Read and writable by default.
0 OR 4-20
Sets the current output to either a 0-20mA output or a 4-20mA
output scale. The 4-20mA output scale is used by default.
Table 4. Basic MODBUS Registers Map.
Register
Name
Description
Minimum Maximum Size
40001
FLAMECOUNT Flame count of active channel (read only)
0
3425
16 bit
40002
PROCSTATUS
Bit mask: only 4th bit (4 of 20) is writable, other bits are read
only
Not used
(0000 0001) don’t care
Relay
(0000 0010) 1=on, 0=off
Not lockout
(0000 0100) 1=not lockout, 0=lockout
Not panel lock
(0000 1000) 1=unlocked, 0=locked
4 to 20 (output) (0001 0000) 1 (default)=4-20mA, 0=0-
20mA
File
(1110 0000) 3 bits are the file in use (0-7)
0
255
8 bit
40003
FLAMEON
Flame On setting for current active file
51
3425
16 bit
40005
FLAMEOFF
Flame Off setting for current active file
50
3424
16 bit
40007
OUTPUTGAIN
Gain of the0/4-20mA output for the current active file
0
99
8 bit
40010
IRGAIN
IR sensor gain setting for current active file
0
99
8 bit
40011
IRFILT
High pass IR sensor filter setting for current active file. 0=8Hz
(default), 1=16Hz, 2=24Hz, 3=33Hz, 4=52Hz, 5=75Hz,
6=100Hz, 7=155Hz, 8=215Hz, 9=300Hz
0
9
8 bit
40012
UVTGAIN
UV tube gain setting for current active file
0
99
8 bit
40015
UVSSFILT
High pass solid state UV sensor filter setting for current active
file. File 0=8Hz (default), 1=16Hz, 2=24Hz, 3=33Hz, 4=52Hz,
5=75Hz, 6=100Hz, 7=155Hz, 8=215Hz, 9=300Hz
0
9
8 bit
40016
UVSSGAIN
Solid state UV sensor gain setting for current active file
0
99
8 bit
40019
TEMPERATURE Current internal temperature of U2 (read only)
-67
261
16 bit
40021
TIMEDELAY
Time Delay setting (in seconds) for current active file
0
3
8 bit
40022
FFRT
FFRT (flame failure response time) setting (in seconds) for
current active file
1
3
8 bit
40023
VERSION
Firmware version (read only)
-32768
32767
16 bit
40085
BAUD
Baud rate setting (bits/second). Only affects RS-485
communication, not IRDA. Default is 9600. The U2 and the
master device must have the same baud settings.
24
1152
16 bit
40086
PARITY
Parity setting. Only affects RS-485 communication, not IRDA.
0-no parity (default), 1=odd parity, 2=even parity
0
2
8 bit
40087
ADDRESS
Modbus address of U2 used by RS-485 and IRDA. Each flame
monitor must have a unique address.
0
247
8 bit
40092
NUMFILES
User set limit on the number of files able to be used. Default=8. 1
8
8 bit
40093
FILE
Current active file number. Default=0.
0
7
8 bit
40095
TUBEFLAME
Flame count from the UV tube sensor only (read only)
-32768
32767
16 bit
40096
IRFLAME
Flame count from the IR sensor only (read only)
-32768
32767
16 bit
40097
SSUVFLAME
Flame count from the solid state UV sensor only (read only)
-32768
32767
16 bit