Honeywell TROL-A-TEMP Q674B Скачать руководство пользователя страница 9

9

69-0580—2

Checkout

TABLE 5—SYSTEM SET-UP FOR THERMOSTAT CHECKOUT.

Heating

Cooling

Control

Zones Other

Zones Other

Panel

Zone 1

Than Zone 1

Zone 1

Than Zone 1

Mini-zone

Set thermostat

Move the heating set

Set thermostat

Move the cooling set

MABS II

system switch to

point lever 10

°

 F

system switch to

point lever 10

°

 F

MABS II-L

HEAT; set fan switch

[6

°

 C] below room

COOL; set fan

[6

°

 C] above room

to AUTO. Move the

temperature.

switch to AUTO.

temperature.

heating set point

Move the cooling

lever 10

°

 F [6

°

 C]

set point lever 10

°

 F

below room

[6

°

 C] above room

temperature.

temperature.

MABS XX

On all zone thermostats, set the system

On all zone thermostats, set the system

switch to HEAT; set the fan switch to AUTO.

switch to COOL; set the fan switch to AUTO.

Move the heating set point lever 10

°

 F [6

°

 C]

Move the cooling set point lever 10

°

 F [6

°

 C]

below room temperature.

above room temperature.

NOTE: The control panel provides a three-

NOTE: The control panel provides a three-

minute time delay when 24V is applied to

minute time delay when 24V is applied to

the control panel and at the end of each

the control panel and at the end of each

equipment cycle. The high-speed fan runs

equipment cycle. The high-speed fan runs

during this time delay.

during this time delay.

HEATING

NOTE: If a plenum fan control is used in the heating

system, there will be a short delay on a call for heat to
allow the furnace to heat the plenum. The fan starts
immediately in electric heat systems. Allow 30 seconds
for the damper to open or close completely.

Make sure all zone thermostats are set as instructed in

the  Heating column in Table 5. Check each zone thermo-
stat as follows:

1. If thermostat has a fan switch, set it to ON. See

Fig. 13. After 30 seconds, place your hand in front of an
air register in that zone to check for air flow at the register.

2. Reset fan switch, if provided, to AUTO. After 30 sec-

onds, make sure air flow at register has stopped.

3. Move heating set point lever on zone thermostat

10

°

 F [6

°

 C] above room temperature to call for heat.

4. After 30 seconds (longer, if necessary, for time delay

on plenum fan control), check for warm air at the register.

5. Move heating set point lever on the zone thermostat

10

°

 F [6

°

 C] below room temperature to end a call for heat.

After 30 seconds (longer, if necessary, for time delay on
plenum fan control or control panel), check that air flow at
the register has stopped.

6. Repeat steps 1-5 for each zone thermostat.

COOLING

CAUTION

Do not operate cooling equipment if outdoor
temperature is below 50

°

 F [10

°

 C]. Refer to

manufacturer recommendations.

Make sure all zone thermostats are set as instructed in

the Cooling column in Table 5. Check each zone thermo-
stat as follows:

1. Move cooling set point lever on the zone thermostat

10

°

 F [6

°

 C] below room temperature to call for cooling.

2. After 30 seconds, place your hand in front of an air

register in that zone to check for cool air at the register.

3. Move the cooling set point lever on the zone thermo-

stat 10

°

 F [6

°

 C] above room temperature to end the call for

cooling. After 30 seconds (longer, if necessary, for time
delay on control panel), check that air flow at the register
has stopped.

4. Repeat steps 1-3 for each zone thermostat.

When system checkout is complete, return all thermo-

stats to the desired settings for normal system operation.

!

Before beginning checkout of thermostat operation,

set switches on the control panel for the desired system
operation. See instructions provided with the control panel.

To set up the system for thermostat checkout, adjust

each thermostat settings as shown in Table 5.

Содержание TROL-A-TEMP Q674B

Страница 1: ...d control in the trash Contact your local waste management authority for instructions regarding recycling and the proper disposal of this control or of an old control containing mercury in a sealed tube If you have questions call Honeywell at 1 800 468 1502 M3375 Installation Instructions for the Trained Service Technician TABLE 1 THERMOSTAT SUBBASE AND SYSTEM COMPATIBILITY Thermostat Application ...

Страница 2: ...irectly on the wall 1 To mount on a horizontal outlet box install the sub base on the outlet box as shown in Fig 1 For a wall installation hold the subbase in position and mark holes for the anchors Fig 2 Obtain wall anchors locally Take care that the wires do not fall back into the wall opening Set aside subbase Drill two 3 16 in 4 8 mm holesandgentlytapanchorsintotheholesuntilflushwiththe wall 2...

Страница 3: ...mostat Q674B D Subbase in single stage heating cooling two zone system POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED ZONE 1 O AND B TERMINALS MUST BE CONNECTED FOR PROPER SYSTEM OPERATION JUMPER RC AND RH TERMINALS TOGETHER AND WIRE AS SINGLE R TERMINAL DO NOT CONNECT W2 AND Y2 TERMINALS TO CONTROL PANEL 1 1 M1633 HEAT RELAY COOL RELAY ZONE 1 RELAY ZONE 2 RELAY Y2 Y1 O ...

Страница 4: ...ult Fig 7 Typical hookup for MABS II and MABS II L Control Panels with T874A Thermostat Q674B D Subbases in single stage heating cooling zone system MABS II Control Panel shown MABS II L Control Panel hookup is the same 4 M1634 Y 2 1 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED JUMPER RC RH TOGETHER AND WIRE AS SINGLE R TERMINAL ZONE 1 O AND B TERMINALS MUST BE CONNECT...

Страница 5: ...G DO NOT CONNECT W2 Y1 O G2 G1 RC RH B W2 W1 E ADD A ZONE EM HEAT RELAY SECOND STAGE RELAY FAN RELAY HEAT RELAY COOL RELAY CAC RELAY ZONE 1 RELAY ZONE 2 RELAY ZONE 3 RELAY A4 A3 A2 A1 T8 T7 T6 T5 T4 M6 M4 M1 ZONE 3 T8 T7 T6 T5 T4 M6 M4 M1 ZONE 2 T8 T7 T6 T5 T4 M6 M4 M1 ZONE 1 O1 G1 B1 E1 2 1 CHANGEOVER CONTROL COOL FAN HEAT EM HEAT 24 V 40 VA TRANSFORMER 4 5 6 Z DAMPER ACTUATOR 1 2 3 X 4 5 6 Z DAM...

Страница 6: ...T HAS R RC RH TERMINALS JUMPER TOGETHER AND WIRE AS SINGLE R TERMINAL DO NOT CONNECT THERMOSTAT O AND B TERMINALS TO CONTROL PANEL 2 ZONE 1 ZONE 2 ZONE 3 O B RC RH 1 2 G Y R W M6 M4 M1 VO VC ZONE 1 G Y R W M6 M4 M1 VO VC ZONE 2 G Y R W M6 M4 M1 VO VC ZONE 3 OPEN CLOSE DAMPER ZONE SYS ZONE 1 OPEN CLOSE DAMPER ZONE SYS ZONE 2 OPEN CLOSE DAMPER ZONE SYS ZONE 3 FAN FAN FAN G Y1 Y2 R W1 W2 O T874A THER...

Страница 7: ...r ...

Страница 8: ...Settings ...

Страница 9: ...set it to ON See Fig 13 After 30 seconds place your hand in front of an air register in that zone to check for air flow at the register 2 Reset fan switch if provided to AUTO After 30 sec onds make sure air flow at register has stopped 3 Move heating set point lever on zone thermostat 10 F 6 C above room temperature to call for heat 4 After 30 seconds longer if necessary for time delay on plenum f...

Страница 10: ...eter to sense the area temperature compare the readings Be care ful not to touch the thermometer or breathe on it 4 If the readings are the same replace the cover and put the system into operation 5 If the readings are different insert a small screw driver in the thermometer slot Fig 14 and turn it until the thermometers have the same reading 6 Replace the thermostat cover and put the system into ...

Отзывы: