If recalibration appears necessary, proceed as

follows:

1. Place the temperature setting lever at the same setting

as the thermometer. Remove cover.

2. Insert 104994A Calibration Wrench (order separately)

onto the hex nut under the coil. See Fig. 6. Holding the setting
lever so it does not move, turn the wrench clockwise

                        until

the mercury drops to the right end of the tube. Remove
wrench and replace cover.

To ensure accurate temperature control, do not touch or

breathe on bimetal or thermometer.

3. Move the setting lever to a low setting. Wait at least

five minutes for temperature to stabilize.

4. Slowly move the setting lever until it reads the same as

the thermometer.

5. Remove cover. Holding the setting lever so it does not

move, reinsert wrench and carefully turn
counterclockwis

e                       

until the mercury drops to the le

ft

of the tube, but no farther.

6. Recheck calibration. Set the thermostat system switch

for desired operation and replace cover.

7. Adjust temperature setting lever so mercury bulb is in

position. See Fig. 1

8. Carefully replace thermostat cover.

Fig. 6—Recalibration procedure.

5

69-0434—5

COOLING

CAUTION

Do not operate cooling if outdoor temperature is
below 50

°

  F [10

°

  C]. Refer to manufacturer’s

recommendations.

NOTE: To prevent compressor short cycling, some manufac-

turers’ equipment includes a minimum off-timer to pro-
vide a five-minute time delay before activating the com-
pressor when the thermostat last turned the compressor
off, or from when the system first received power. This
delay protects the compressor.

With the system switch set at COOL and the fan switch  set

at AUTO, move the temperature setting lever about
10

°

 F [6

°

 C] below room temperature. Cooling and fan should

start (see NOTE above). Move the temperature setting lever
about 10

°

 F [6

°

 C] above room temperature. Cooling and fan

should shut off.

FAN

With the system switch set at OFF, and the fan switch at

ON, the fan should run continuously. Move the fan switch to
AUTO. In gas- or oil-fired systems, fan operation is con-
trolled by the thermostat in cooling and by the plenum fan
control in heating. In single-stage heat pump and central
electric heat systems, fan operation is controlled by the
thermostat in both heating and cooling.

RECALIBRATION

These thermostats are calibrated at the factory and should

not need recalibration. If the thermostat seems out of adjust-
ment, first check for accurate leveling. To check calibration,
proceed as follows.

1. Move the temperature setting lever to the left end (low

end) of the temperature scale. System switch must be placed
at OFF. Wait at least five minutes.

2. Remove the thermostat cover. Move the setting lever

until the switch just makes contact. The mercury in the switch
will drop to the left end of the tube.

3. Replace cover and wait five minutes for the cover

and the thermostat to lose the heat it has gained from your
hands. If the thermometer pointer and the setting lever
indicator read approximately the same, no recalibration
is needed.

CALIBRATION
WRENCH

COIL SHOWN WITHOUT
HEAT ANTICIPATOR

M2044

Содержание TRADELINE T834C1137

Страница 1: ... equipment damage Contact your local waste management authority for in structions regarding recycling and the proper disposal of this control or of an old control containing mercury in a sealed tube If you have questions call Honeywell Inc at 1 800 468 1502 J H Rev 2 93 Honeywell Inc 1993 Form Number 69 0434 5 T834C Heating CoolingThermostat TRADELINE Application T834C Thermostats control 24 to 30...

Страница 2: ...ble heat anticipator indicator to match the current draw of the primary heating control or as recom mended by the equipment manufacturer see Heat Anticipa tor Setting 4 Connect the wires to the terminals on the back of the thermostat See Figs 3 5 for internal schematic and typical hookup diagrams If using electric heat compatible thermo stat in central electric heat applications jumper terminals 1...

Страница 3: ... O 2 G R 1 2 CHANGEOVER RELAY COOL 3 4 4 Fig 4 Internal schematic and typical hookup for T834C1541 in gas or oil fired or central electric heat system Fig 5 Internal schematic and typical hookup for T834C2267 in gas or oil fired single stage heat pump or central electric heat system M2690 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED IN ELECTRIC HEAT OR SINGLE STAGE HEA...

Страница 4: ...emperature setting lever so mercury bulb is in horizontal position See Fig 1 10 Carefully replace thermostat cover IMPORTANT Anincorrectlyleveledthermostatwillcause the temperature control to deviate from setpoint Setting andAdjustment TEMPERATURE SETTING Push the temperature setting lever to the desired control point on the temperature scale The same lever controls both heating and cooling SYSTEM...

Страница 5: ...stat last turned the compressor off or from when the system first received power This delay protects the compressor WiththesystemswitchsetatCOOLandthefanswitch set at AUTO move the temperature setting lever about 10 F 6 C belowroomtemperature Coolingandfanshould start see NOTE above Move the temperature setting lever about10 F 6 C aboveroomtemperature Coolingandfan should shut off FAN With the sys...

Страница 6: ...Automation and Control Solutions Honeywell Internationals Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley Minnesota 55422 Scarborough Ontario M1V 4Z9 ...

Отзывы: