 62-0271—07

2

Communications

The wall modules use a sensor bus (S-BUS) for 

communications with the programmable controller. Wire the 

two S-BUS terminals according to these installation 

instructions.

The wall modules have a network bus port for L

ON

M

ARK

® or 

BACnet® communications. If network communication is 

needed, connect the building LON network wires to the two 

terminals (NET-1 and NET-2), according to these installation 

instructions. A network bus port is accessible at the bottom of 

the wall module by removing the jack plug. See Fig. 1.

The network bus and S-BUS terminals (see Fig. 6 on page 4) 

are insensitive to polarity, minimizing installation errors due to 

mis-wiring.

BEFORE INSTALLATION

Fig. 1. LCD Wall Module features.

CAUTION

Erratic System Operation Hazard.

Failure to follow proper wiring practices can 

introduce disruptive electrical interference (noise).

Keep wiring at least one foot away from large inductive 

loads such as motors line starters, lighting ballasts, 

and large power distribution panels.

Shielded cable is required in installations where these 

guidelines cannot be met.

Ground the shield only to the grounded controller 

case.

IMPORTANT

All wiring must comply with local electrical codes and 

ordinances or as specified on installation wiring dia-

grams.

— Wall module wiring can be sized from 18 to 24 AWG (0.82 

to 0.20 sq. mm), depending on the application.  For 

multiple Zios on the same S-BUS, 24 AWG wire is 

recommended.

— For S-BUS wiring, the Zio may be mounted up to 200 ft. 

(61 m) from the programmable controller. If multiple Zios 

are installed, the total distance from the controller to the 

last Zio should not exceed 200 ft.

— Twisted pair wire is recommended for wire runs longer than 

100 ft. (30.5 m).

— All wiring is polarity insensitive.

— The cover for the wall module is packed separately from 

the subbase for ease of installation.

INSTALLATION

Mount the wall module on an inside wall approximately 54 in. 

(1372 mm) from the floor (or in the specified location), to allow 

exposure to the average zone temperature. Do not mount the 

wall module on an outside wall, on a wall containing water 

pipes, or near air ducts. Avoid locations that are exposed to 

discharge air from registers or radiation from appliances, 

lights, or the sun.

The wall module can be mounted on a wall, on a standard 

utility conduit box using No. 6 (3.5 mm) screws or on a 60 mm 

wall outlet box (see Fig. 3). When mounting directly on a wall, 

use the type of screws appropriate for the wall material.

Fig. 2. Subbase mounting holes and locking tabs.

LCD PANEL

M27344

SOFTKEYS (3)

UP/DOWN 

ARROW KEYS

NETWORK BUS PORT (ON BOTTOM OF CASE)

2-3/8 (60)

2-3/8

(60)

3-1/4

(83)

M27345

LOCKING 

TABS (4)

2-3/8 (60)

3-3/8 (95)

4-1/8

(105)

Содержание TR70

Страница 1: ...tions tenant access contractor access access to controller parameters setpoint override fan and other parameters TR70 and TR71 have the ability to access and adjust virtually any parameter in the programmable controller except Scheduling TR75 can additionally access and adjust the controller schedule The TR71 has roughly twice the memory capacity for parameters as the TR70 and the TR75 has more th...

Страница 2: ...es or as specified on installation wiring dia grams Wall module wiring can be sized from 18 to 24 AWG 0 82 to 0 20 sq mm depending on the application For multiple Zios on the same S BUS 24 AWG wire is recommended For S BUS wiring the Zio may be mounted up to 200 ft 61 m from the programmable controller If multiple Zios are installed the total distance from the controller to the last Zio should not...

Страница 3: ... from the conductor See Fig 5 for wiring multiple Zios 2 Insert the wire in the required terminal location and tighten the screw to complete the termination 3 Review and verify the terminal connection wiring illustrated in Fig 6 NOTE The recommended wire size for the network bus and S BUS is Level IV 22 AWG 0 34 sq mm ple num or non plenum rated unshielded twisted pair solid conductor wire However...

Страница 4: ...ng Wall Module from Subbase POWER UP After the wall module is properly wired to the controller it will power up Upon initial power up the wall module LCD panel displays the phrase PLEASE LOAd see Fig 8 This phrase alternates with bus address model and version number TR71 and TR75 only and any onboard sensor display such as temperature humidity etc Refer to the Zio Zio Plus LCD Wall Modules Operati...

Отзывы: