Honeywell TotalZone TZ-4 Скачать руководство пользователя страница 16

TZ-4 TOTALZONE® ZONE CONTROL PANEL

68-0259-1

16

Thermostat Operation

Conventional Thermostats

Conventional (R,W,Y,G) heat/cool thermostats can be used 

with the TZ-4 to control single or multi-stage gas, electric or oil 

systems and heat pumps with auxiliary heat. 

The panel can be configured to control second stage heat and 

cool and third stage heat using a 5-60 minute timer, or staging 

can be controlled by the percentage of zones calling. 

When using conventional thermostats on heat pump 
applications, set DIP switch 5-1 to Off for heat pump 
equipment. Set DIP switch 5-7 for correct reversing valve 
operation. See Table 7.

Heat Pump Thermostats

HEAT PUMP THERMOSTATS WITH SINGLE Y OUTPUT

Thermostats that have a single Y terminal for first stage heat 

and cool and those with separate Y1 and W1 can be used. 

Thermostats of either wiring type can be used on any zone.

For thermostats with a single Y, the reversing valve wire must 

be connected to O/B: 

— Connect the thermostat Y terminal to Y1 on the panel. 

— If the thermostat energizes O on a call for cool, connect the 

O/B jumper located near the thermostat wiring terminals.

—  If the thermostat energizes B on a call for heat, leave the 

O/B jumper disconnected.

HEAT PUMP THERMOSTATS WITH SEPARATE Y1 AND W1 
TERMINALS

Heat pump thermostats with separate Y1 and W1 terminals for 

first stage heat and cool are wired to Y1 and W1/E. Leave the 

O/B jumper, located near the thermostat wiring terminals, 

disconnected.

Emergency Heat Control

Emergency heat is defined as using an auxiliary heat source 

without using the heat pump. When the Em Heat switch is in 

the emergency heat position, the heat pump is locked out and 

calls for heat are sent to the W1/E equipment terminal for 

fixed stage emergency heat. Second stage emergency heat 

energizes equipment terminals W3/Aux. Second stage 

emergency heat is configured with DIP switch S41 and 2. 

When the panel is in the heat pump mode, W1/E is energized 

only in emergency heat.

A recommended heat pump thermostat can also control 

emergency heat from the thermostat system switch. See 

Table 1.

Multi-Stage Thermostats

Use multi-stage thermostats to control up to three stages of 

heat and two stages cool with the W1/E,W2, W3/AUX, Y1, 

and Y2 thermostat terminals. 

Manual and Automatic Changeover Thermostats

Manual or automatic changeover thermostats can be used. 

The panel determines the call for heat or cool based on which 

was called for first. Subsequent calls for heat or cool are 

honored when the initial call is satisfied, or 20 minutes has 

elapsed. 

Rebooting Microprocessor 

To reset the panel, press and release the Boot button.The 

system reboots and enters the Purge mode. 

Discharge Air Temperature Sensor

The C7735A1000 Discharge Air Temperature Sensor (not 

included) is a supply-duct-mounted temperature probe used 

to control capacity and prevent high limit or coil-icing. The 

sensor attaches to the two DATS terminals on the panel. 

When a high or low limit is reached, the panel shuts off the 

equipment and keeps the fan operating for 2-1/2 minutes. 

After this time, it re-energizes the equipment after the 

discharge air recovers by 10 degrees. When the DATS 

exceeds the high or low limit, the Heat (red) or Cool (green) 

LED flashes.

Set the temperature from 110 °F to 160°F. See Fig. 23. The 

recommended setting for fossil fuel/ electric systems is 160°F 

(default factory setting). For heat pump systems, the 

recommended setting is 120°F.   When using a heat pump 

with dual fuel activated (DIP 5-8), the high limit will auto-

matically be set for 120 degrees when the outputs call for 

compressor only operation. When the outputs call for non-

heat pump operation, the high limit will be set to the adjustable 

110° to160°F setting.

The cooling temperature limit can be set at 40°F or 48°F. 

Fig. 23. DATS high-limit temperature dial.

IMPORTANT

Be sure the Discharge Air Temperature Sensor wir-

ing does not run parallel with line voltage wiring 

unless more than 12 in. of separation exists or 

shielded cable is used.

130  F

MAX DUCT

TEMP

M19079A

120  F

110  F

140  F

150  F

160  F

Содержание TotalZone TZ-4

Страница 1: ...s and can be expanded up to 32 zones with Add A Zone Control Panels Uses Honeywell four wire single stage multi stage or select heat pump thermostats Zone A Lone central setback feature Purge timer protects equipment between calls for heat or cool with choice of panel or HVAC equipment controlled fan System and zone damper LEDs indicate system and damper status Individual zone fan control Discharg...

Страница 2: ...ed Wiring 18 gauge wire for all equipment and system connections Wiring Connections Thermostat R C W1 E W2 W3 AUX Y1 Y2 G L O B Dampers M6 Closed M4 Open M1 Common Discharge Air Temperature Sensor C7735A1000 DATS DATS Zone A Lone OC OC Outdoor Temperature OT OT Transformer 1 R hot C common Transformer 2 T1 hot T2 common Equipment Rc Rh W1 E W2 W3 AUX Y1 Y2 G O B Thermostats See Table 1 Most conven...

Страница 3: ... maximum of five dampers per zone when using two 40 VA transformers Use SDCR and 40 VA transformer for additional dampers required on one zone Dampers are connected to M1 Common M4 Open and M6 Closed see Fig 7 10 for hookups Accessories For required accessories see Table 3 Table 1 Recommended Thermostats System Non Programmable Programmable Single Stage T87F1859 Q539A1014 T87F4010 Q539A4026 T8501D...

Страница 4: ...as shown in Fig 7 10 3 Connect C7735A Discharge Air Temperature Sensor not supplied to the DATS terminals The wires are not polarized See Fig 13 4 Connect Add A Zone panels if used to the AZ1 and AZ2 terminals 5 Connect the HVAC equipment to the EQUIP terminals on the panel See Fig 15 21 6 Connect a 40 VA 24 volt transformer to R hot and C common This must be a dedicated transformer and each TAZ 4...

Страница 5: ...s a zone thermostat See Fig 4 for hookup This thermostat can be used to control up to 2 heat and 2 cool stages of conventional equipment When used to control heat pump equipment the W8900A is recommended Connect a jumper on the W8900 from Rc to Rh as shown in Fig 4 Wire terminals R and C to a transformer If the system current draw is within specifications the R and C on the W8900 could alternately...

Страница 6: ... 4 disconnected and wire as shown in Fig 5 If the PC8900 W8900 Thermostat is used in a heat pump application use the W8900A not the W8900B and wire as shown in Fig 4 M20508B W8900A C IS RECOMMEDED FOR CONVENTIONAL AND HEAT PUMP APPLICATIONS THE W8900B CANNOT SWITCH THE PANEL TO EMERGENCY HEAT LEAVE O B JUMPER ON TZ 4 DISCONNECTED TZ 4 THERMOSTAT CONNECTORS 1 2 1 S1 S T1 T OUT OUT LED G Y2 Y1 W1 W2...

Страница 7: ... to the panel as shown in Fig 8 Multiple dampers can be wired in parallel Use these dampers on systems up to 2000 cfm AOBD Dampers Wire the AOBD dampers to the panel as shown in Fig 9 Two AOBD can be wired in tandem as shown in Fig 10 More than two AOBD dampers require the Slave Damper Control Relay SDCR Fig 6 Heat pump thermostat with single Y thermostat wiring M20506B G C R Y W1 L W2 E B O COMMO...

Страница 8: ...tion indication Use the MARD or D643 with the ML6161 on systems above 2000 cfm Fig 11 Wiring MARD Damper or ML6161 Actuator to panel M20891 G C R Y1 Y2 L W3 E B O COMMON C TERMINAL IS USED ONLY ON THERMOSTATS THAT REQUIRE A COMMON WIRE ALTERNATIVELY JUMPER E THERMOSTAT TERMINAL TO Y1 FOR EMERGENCY HEAT CONNECT O B JUMPER ON TZ 4 WHEN USING O OR DISCONNECT WHEN USING B FOR CHANGEOVER FIELD INSTALLE...

Страница 9: ... Relay SDCR Fig 13 Wiring transformer s to panel Discharge Air and Outdoor Temperature Sensors Wire the C7735A Discharge Air Temperature Sensor DATS to the panel as shown in Fig 14 The Purge LED yellow flashes in all modes except purge if no DATS is connected to the TZ 4 or if there is a problem with the DATS or the wiring For dual fuel applications connect the C7089 Outdoor Temperature Sensor as ...

Страница 10: ...elay has powered terminals remove the Rh Rc jumper Set DIP switch 5 6 to off to energize the fan with a call for heat Oil Heat Wire the oil primary T T terminals to the Rh and W equipment terminals If the oil primary has powered terminals remove the Rh Rc jumper Multi Stage Wire the equipment as shown in Fig 16 using the W2 and W3 terminals for second and third stages of heat Wire Y2 for second st...

Страница 11: ...MIN 0 1 0 40 MIN 0 0 1 50 MIN 0 0 0 60 MIN ON OFF 1 0 CONV HP 40F 48F 2 0 MIN 3 5 MIN HVAC PANEL NO CHG OPEN HVAC PANEL COOL HEAT DISABLED ENABLED RH RC W1 E W2 W3 AUX ZONE LEDs ON Damper open or opening OFF Damper closed or closing MOMENTARY PUSH BUTTONS Boot Clears microprocessor Purge Overide Bypass Purge Mode BOOT PURGE OVERRIDE Single Transformer Heating Cooling systems require a jumper to be...

Страница 12: ...second stage of compressor to Y2 See Fig 22 M20521B HVAC Equipment RH RC W1 E W2 W3 AUX Single Transformer Heating Cooling systems require a jumper to be installed connecting RH and RC factory installed Y1 Y2 G O B Heating Transformer 24 VAC Equip Cooling Transformer Auxiliary Heat Compressor Reversing Valve Fan Relay 1 1 FIELD INSTALLED JUMPER M20522B HVAC Equipment RH RC W1 E W2 W3 AUX Single Tr...

Страница 13: ... zone two LED turns green 7 Repeat for zones three and four 8 Alternately lower the setpoint to call for cooling Verify that the green cool LED illuminates OPERATION Identifying DIP Switches This panel has two banks of DIP switches DIP switch 4 S4 and DIP switch 5 S5 Each bank has eight individual switches that are identified by two numbers the first number is the bank number 4 or 5 and the second...

Страница 14: ...tage configuration Note that second and third stage can be controlled differently Set stages not used to Off DIP Switch bank 4 switches 1 4 are used to configure the staging method Switches 1 and 2 configure second stage control See Table 4 Switches 3 and 4 configure third stage control See Table 5 When stage two or three is not used disable that stage by turning off the corresponding switches Sin...

Страница 15: ... the fossil fuel mode IMPORTANT A C7089B1000 Outdoor Temperature Sensor and a C7735A1000 Discharge Air Temperature Sensor are required for dual fuel operation Table 4 DIP Switch Bank 4 Stage 2 Configuration Operation Switch 4 1 Switch 4 2 Thermostat On On Timer On Off of Zones Off On Off Off Off Table 5 DIP Switch Bank 4 Stage 3 Configuration Operation Switch 4 3 Switch 4 4 Thermostat On On Timer ...

Страница 16: ...ode W1 E is energized only in emergency heat A recommended heat pump thermostat can also control emergency heat from the thermostat system switch See Table 1 Multi Stage Thermostats Use multi stage thermostats to control up to three stages of heat and two stages cool with the W1 E W2 W3 AUX Y1 and Y2 thermostat terminals Manual and Automatic Changeover Thermostats Manual or automatic changeover th...

Страница 17: ...tects the panel against shorts in the thermostat and damper wiring It does not protect against shorts in the wiring of the HVAC equipment into the panel When the circuit breaker is tripped none of the LEDs illuminate and the yellow rectangular component located left of the R and C terminals is hot to touch Remove power to the panel for at least five minutes to allow the circuit breaker to cool off...

Страница 18: ...rminal wiring Incorrectly configured Verify DIP switch configuration Verify position of O B thermostat type jumper Erratic Operation Emergency Heat switch on Turn off down Emergency Heat switch Zone A Lone Feature on Turn off up Zone A Lone Heat LED flashing High limit reached LED stops flashing with ten degree fall and 2 1 2 minute delay Cool LED flashing Low limit reached LED stops flashing with...

Страница 19: ... call No cool calls Low limit reached Purge Amber Purge mode Not in Purge mode DATS failure slow flash OT failure fast flash DATS and OT failure alternating fast and slow flash Fan Green Fan only call No fan only call EM Heat Red Emergency Heat mode or dual fuel mode Not in emergency Heat mode or dual fuel mode Zones 1 2 3 4 Green Damper is open or opening Damper is closed or closing ...

Страница 20: ...tomation and Control Solutions Honeywell Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Scarborough Ontario M1V 4Z9 Printed in U S A on recycled paper containing at least 10 post consumer paper fibers ...

Отзывы: