PRO TH2000DV/TH1000DV Series
7
69-2800EFS—01
Setup function
Settings & options (factory default in bold)
5 Heating cycle rate
(CPH: cycles/hour)
TH2110DV, TH1110DV and
TH1100DV
5
For gas or oil furnaces of less than 90% efficiency
1
For steam or gravity systems
3
For hot water systems & furnaces of over 90% efficiency
6
For electric furnaces
[Other cycle rate options: 2 or 4 CPH]
6 Auxiliary heat
cycle rate (CPH)
TH2210DV and TH1210DV
3
For hot water systems & furnaces of over 90%
efficiency
1
For steam or gravity systems
5
For gas or oil furnaces of less than 90% efficiency
6
For electric furnaces
[Other cycle rate options: 2 or 4 CPH]
9 Compressor
cycle rate (CPH)
3
Recommended for most compressors
[Other cycle rate options: 1, 2, 4, 5, or 6 CPH]
13 Early Start (TH2110DV
and TH2210DV)
1
On **See page 8
0
Off
14 Temperature
display
0 Fahrenheit
1
Celsius
15 Compressor
protection
1
Five-minute compressor off time (See page 8)
0
No compressor off time
20 Clock display (TH2110DV
and TH2210DV)
0
12-hour display
1
24-hour display
25 Lower temperature
range (TH1100DV only)
0
Standard range 40°F to 90°F (4.5°C to 32°C)
1
Lower range (for garage mode) 35°F to 90°F
(1.5°C to 32°C)
40 Restore program
schedule to default
(TH2110DV and
TH2210DV)
0 Off
1
On - program schedule default settings are listed in the
operating manual
Installer setup
CAUTION: EQUIPMENT DAMAGE HAZARD
Compressor protection is bypassed during testing. To prevent equipment damage, avoid
cycling the compressor quickly.
NOTE:
The options below may not be available in all models.