This manual is intended as a quick reference installation guide.  Please refer 

to the control panel installation manual for detailed system information.

GENERAL INFORMATION

The TC810E series of modules are a family of microprocessor controlled 

interface devices permitting the monitoring and/or control of auxiliary 

devices.  The TC810E1040, TC810E1040-KO and TC810E1057 are output 

modules, providing 250VAC 5A rated voltage free contacts, both normally 

open and normally closed.

SPECIFICATIONS

Operating Voltage Range: 

15 to 30VDC (Min 19.5VDC to ensure LED  

 

 

operation - TC810E1040-KO 17.5VDC)

Maximum Standby Current (µA):  275µA - No Communication

 

445µA - Communication LED blink enabled - 5 secs

 

375µA - Read 16 sec. LED blink 8 sec

Fault Current: 

8.8mA (Yellow LED illuminated)

Coil Activation/Deactivation Current:  76mA Maximum for 12mS

Relay Contact Rating: 

5A, at 30VDC, 5A at 250VAC

Maximum rated continuous current with the 

isolator 

 closed (I

c

 max):  1A

Maximum rated isolator  current (under short circuit) (I

max):  1A

Maximum leakage current (I

max) with the isolator  open (isolated state):  15mA

Maximum series impedance with the isolator  closed (Z

c

 max): 170 m ohm at 15Vdc

Operating Temperature: 

-20°C to 60°C

Humidity: 

5% to 95% Relative Humidity

Dimensions TC810E1040 and TC810E1040-KO:  134mm(H) x 139mm(W) x 40mm(D)

Dimensions TC810E1057: 

127mm(H) x 76mm(W) x 48mm(D) (Including terminals)

Weight TC810E1040 and TC810E1040-KO:  195g

Weight TC810E1057: 

140g

Maximum Wire Gauge 

1.5mm² - TC810E1040 (-KO), 2.5mm² - (-DIN)

INSTALLATION

Note: These modules must only be connected to control panels using 

compatible proprietary analogue addressable communication 

protocols for monitoring and control.

CAUTION

Disconnect loop power before installing modules or sensors. 

High voltages may be present on terminals 7 to 12.

TC810E1040 and TC810E1040-KO

1.  The TC810E1040(-KO)  includes a custom low profile surface-mounting 

box with several options for fixing centres.  To access all fixing points, 

and the rear cable entry knock out, the circuit board must be removed.  

It is held in place by two screws through the circuit board.  Ensure that 

these screws are replaced when refitting the circuit board.

2.  If rear cable entry is not required, the box has several cover drill points 

permitting the entry of cables using suitable glands.

3.  Wiring to the TC810E1040(-KO) is made via two 6 way terminal strips 

on the module circuit board, capable of supporting conductors up to 

1.5mm².  See figure 2 for connections.

4.  An earthing terminal is provided in the surface mount box for connection 

of the loop cable screen, if used, to ensure continuity.  See figure 1a.

TC810E1057

1.  TC810E1057 mounts onto standard 35mm x 7.5mm "Top Hat" DIN rail.  

It must be mounted in a suitable cabinet meeting the applicable safety 

standards.

2.  Wiring to the TC810E1057 is via plug in type terminals capable of 

supporting conductors up to 2.5mm².  See figure 2 for connections.

WARNING

Ensure that the correct terminals are used for the loop and 

switched voltage as damage may result from incorrect usage.

For both modules, the address is selected by means of rotary decade 

address  switches  (see  figure  2),  accessed  at  the  front  of  the  module.    A 

screwdriver should be used to rotate the wheels to select the desired 

address. (Note: The number of addresses available will be dependent on 

panel capability, check the panel documentation for information on this.)  

Short Circuit Isolators 

All TC810E series modules are provided with short circuit monitoring and 

isolators on the intelligent loop.  If required the isolators may be wired out of 

the loop to facilitate the use of the modules on high current loaded loops, for 

example if sounders are used.  To achieve this, the loop out positive should 

be wired to terminal 5 rather than terminal 2.

 

Figure 1a:  TC810E1040(-KO) Surface Mount 

Output Module with 240V Relay Contacts

Figure 1b:  TC810E1057 Din Rail Mounted 

Output Module with 240V Relay Contacts.

TO MOUNT, LOCATE LUG OVER TOP 

OF RAIL AND ROTATE THE MODULE 

DOWN TO CLIP INTO PLACE.  

TO REMOVE, PUSH UPWARDS, AND 

ROTATE TOP OF MODULE AWAY 

FROM RAIL.

Figure 2:  Module Wiring

NOTE:

  

Wiring is the same for TC810E1040(-KO) and TC810E1057

Loop -, Out

Loop +, Out - See Note 1

Loop -, In

Loop +, In

Loop +, Out - See Note 1

T6 - Not Connected

Relay 1, N/O

Relay 2, N/C

Ground

Ground

Relay 2, N/C

Relay 1, N/O

TENS UNITS

LOOP CABLE SCREEN TERMINAL

TC810E1040, TC810E1040-KO 

AND

 TC810E1057

INSTALLATION INSTRUCTIONS FOR MAINS SWITCHING OUTPUT MODULES

ROTARY DECADE ADDRESS SWITCHES

Notes:

1. If short circuit isolation is not required, then the loop output should 

be wired to terminal 5 rather than terminal 2.  Terminal 5 is internally 

connected directly to terminal 4.

2. In order to meet the requirements of European Safety Standards, 

ensure that all cables carrying voltages in excess of 48V  are suitably 

fused.

Содержание TC810E1040

Страница 1: ...able entry is not required the box has several cover drill points permittingtheentryofcablesusingsuitableglands 3 Wiring to the TC810E1040 KO is made via two 6 way terminal strips on the module circuit board capable of supporting conductors up to 1 5mm Seefigure2forconnections 4 Anearthingterminalisprovidedinthesurfacemountboxforconnection oftheloopcablescreen ifused toensurecontinuity Seefigure1a...

Страница 2: ...nte appositi premistoppa 3 Il cablaggio del modello TC810E1040 KO viene effettuato per mezzo di 2 morsetti a 6 vie presenti sul circuito stamapo del modulo Sono supportati conduttori fino a 1 5 mm Per informazioni su come effettuare le connessioni ved figura 2 4 La scatola per montaggio su superficie contiene anche un terminale di messa a terra per la connessione dello schermo del cavo del circuit...

Страница 3: ...le la caja presenta en la tapa varios troqueles por donde se pueden introducir cables utilizando casquillos adecuados 3 Las conexiones con el TC810E1040 KO se realizan mediante dos bloques de terminales de 6 vías en la placa de circuito del módulo con capacidad para cables con sección máxima de 1 5 mm Consulte las conexiones en la figura 2 4 La caja para montaje en superficie incluye un terminal d...

Страница 4: ...seite nicht erforderlich ist können die vorgesehen Bohrlöcher der Abdeckung in Verbindung mit geeigneten Kabelmanschetten genutzt werden 3 Die Verdrahtung des TC810E1040 KO erfolgt über die 6 poligen Anschlussleisten auf der Platine mit einem zulässigen Kabelquerschnitt von max 1 5mm Anschluss siehe Abbildung 2 4 Die Kabelabschirmung wird an die entsprechende Klemme der Montagebox angeschlossen Be...

Отзывы: