ControlNet Fiber Media
Specifications
26
Experion PKS ControlNet Fiber Optic Implemenation Guide
R210
Honeywell
10/04
Specifications
ControlNet Repeater Adapter TC-RPA002
Parameter
Description
General
Fiber Module Capacity
4 modules
Input Voltage Rating
24Vdc nominal (NEC/CEC Class 2)
Input Voltage Range
18 to 36Vdc
Power Consumption
700 mA maximum (Based on worst case module
loading.)
Isolation Voltage
100% tested as 850Vdc for 1s between user power
and Repeater backplane connections.
Repeater Backplane Output
Current
1.6A maximum @ 5Vdc
Communication Rate
5M bits/s
Operating Conditions
Ambient Temperature
0 C to 60 C (32 F to 140 F)
Storage Temperature
–40 C to 85 C (–40 F to 185 F)
Maximum Relative Humidity
5 to 95%, non-condensing
Shock Test
Operating: 30g peak acceleration, 11 (+/-1) ms pulse
width
Non-Operating: 50g peak acceleration, 11 (+/-1) ms
pulse width
Vibration Test
5 g @ 10 to 500Hz, according to IEC 68-2-6
Physical
Power Conductor Wire Size
Minimum: 24 AWG
Maximum: 14 AWG