TB7600 SERIES COMMUNICATING RTU/HEAT PUMP THERMOSTATS
62-2016—05
16
Get From
Get From another thermostat
configuration utility
Default value =
255
Range is: 0-254
Conditional parameter to wireless models (TB76xxX5x14W)
This parameter is only available for wireless thermostats. This
parameter lets you to copy the configuration parameter settings
from a like Honeywell TB7200 thermostat. To use this command,
the thermostat you want to copy parameters from must be on the
wireless network with a network address (
Com addr
) and must be
the same model number as the thermostat you want to copy to.
On the thermostat you want to copy parameters to, enter the
network address (
Com addr
) of the thermostat you want to copy
parameters from. This process can be completed locally at the
thermostat or using the WEBStation-AX.
If the parameters copy successfully, the
Get From
address returns
to
255
. If the parameters do not copy successfully,
254
is displayed.
If the copy was not successful, verify the following:
•
The thermostat to be copied is the same model as the one being
copied to.
•
The thermostat to be copied is on the network.
•
The correct network address (
Com addr
) value for the
thermostat to be copied was entered.
Leaving the
Get From
parameter value at
255
means that
configuration parameters will be set manually.
DI 1
Digital input no.1 configuration
Open contact input = function not
energized
Closed contact input = function
energized
Default value =
None
None, No function will be associated with the input
Rem NSB, remote NSB timer clock input. Will disable the internal
scheduling of the thermostat. The scheduling will now be set as per
the digital input. The time is still displayed as information, but the
menu part related to scheduling is disabled and no longer
accessible.
•
Open contact = occupied setpoints
•
Closed contacts = unoccupied setpoints
This option provides low cost setback operation via an
occupancy sensor or from a dry contact
RemOVR Temporary override remote contact. Disables all override
menu function of the thermostat. The override function is now
controlled by a manual remote momentarily closed contact. When
configured in this mode, the input operates in a toggle mode. With
this function enabled it is now possible to toggle between
unoccupied and occupied setpoints for the amount of time set by
parameter (
TOccTime
) temporary occupancy time. When Override
is enabled, an Override status message will be displayed.
Filter
, a back-lit flashing Filter alarm will be displayed on the
thermostat LCD screen when the input is energized.
Service
, a back-lit flashing Service alarm will be displayed on the
thermostat LCD screen when the input is energized. Input can be
tied in to the AC unit control card, which provides an alarm in case
of malfunction.
Fan lock, a back-lit flashing Fan lock alarm will be displayed on the
thermostat LCD screen when the input is not energized. Used in
conjunction with a local airflow sensor connected to the input.
Locks out the thermostat heating and cooling action if no airflow is
detected 10 seconds after the fan (G terminal) is energized.
•
Open contact = no airflow
•
Closed contacts = airflow present
DI 2
Digital input no. 2 configuration
Default value = None
Same as above. It is possible to configure both inputs to have the
same function.
MenuScro
Menu scroll
Default value = On = Scroll active
Removes the scrolling display and only presents the room
temperature to the user. With this option enabled, no status is given
of mode, schedule and outdoor temperature. Outdoor temperature
only displays if a network variable is received.
On = Scroll active
Off = Scroll not active
Lockout
Keypad lockout levels
Default value = 0 No lock
0= No lock
1= Low level
2= High level
See Table 15 for
Lockout
level details
Table 14. Configuration Parameters for all models (Continued)
Configuration
parameters
Significance Default value
Adjustments