INSTALLATION INSTRUCTIONS

Place Bar Code Here

62-2016-05

TB7600 Series Communicating 

RTU/Heat Pump Thermostats

FOR COMMERCIAL HVAC APPLICATIONS

APPLICATION

The TB7600 Series PI thermostat family is specifically 

designed for single stage and multi-stage control of heating/

cooling equipment such as rooftop and self-contained units. 

The TB7600 Series are communicating thermostats with 

models available in BACnet

®

 MS/TP and ZigBee

®

 wireless 

mesh protocols and can be easily integrated into a WEBs-AX 

building automation system based on the NiagaraAX

®

 

platform. The product features an intuitive, menu-driven, 

back-lit LCD display, which walks users through the 

programming steps, making the process extremely simple. 

Accurate temperature control is achieved due to the product’s 

PI time proportional control algorithm, which virtually 

eliminates temperature offset associated with traditional, 

differential-based thermostats.

Depending on the model, up to three remote sensor inputs 

are available. All models contain a SPST auxiliary switch, 

which can be used to control lighting or disable the 

economizer function and a discharge air sensor input. For more advanced applications, an economizer control logic has 

been integrated onto the thermostat for use with proportional damper economizer actuators.

Thermostats equipped with an occupancy sensor cover provide advanced active occupancy logic, which will 

automatically switch occupancy levels from Occupied to Unoccupied as required by local activity being present or not. 

This advanced occupancy functionality provides advantageous energy savings during occupied hours without 

sacrificing occupant comfort. All thermostats are PIR ready and can be ordered with or without Honeywell occupancy 

sensor. The occupancy sensor cover is available to order separately if a PIR is needed at a later time.

FEATURES

• Available in BACnet MS/TP and ZigBee wireless protocols
• Backlit LCD display with dedicated function menu keys for simple operation
• Built in default profile set-up for easier start up and commissioning
• Fully integrated advanced occupancy functionality with a PIR accessory cover on some models
• Non-volatile EEPROM memory prevents loss of parameters during power outage
• Programmable smart fan operation can provide energy savings during night mode
• Password protection to minimize parameter tampering
• Three levels of keypad lockout to limit access to change user parameters such as setpoints, system mode, 

etc.

• Gas/oil or electric system compatibility for all type of applications
• SPST auxiliary output can be used for lighting and/or economizer override
• 0 to 10 Vdc economizer output for more retrofit opportunities

— Built in dry bulb economizer logic using outdoor temperature sensor

— Input for supply/mixed air temperature sensor

• Support single and two stages heat pump with one auxiliary heat stage

TB7600 Series 

Thermostat

TB7600 Series 

Thermostat with 

Occupancy Sensor

Содержание TB7600

Страница 1: ...ced active occupancy logic which will automatically switch occupancy levels from Occupied to Unoccupied as required by local activity being present or not This advanced occupancy functionality provides advantageous energy savings during occupied hours without sacrificing occupant comfort All thermostats are PIR ready and can be ordered with or without Honeywell occupancy sensor The occupancy senso...

Страница 2: ...e trip when the coil is downstream of the auxiliary heat source Use programmable models only when installing as standalone thermostats that may eventually be added to a WEBs AX network When a programmable thermostat is added to a network schedules should be applied through the WEB Station AX TB7600 Series Model Selection Product Number Description Outputs Scheduling1 Occupancy Sensor2 BACnet Model...

Страница 3: ...ll providing comfort It provides exceptional accuracy due to its unique PI time proportioning control algorithm which virtually eliminates temperature offset associated with traditional differential based on off thermostats INSTALLATION AND WIRING Mounting Locations Do not install on an outside wall Must be installed away from any heat source Should not be installed near an air discharge grill Sho...

Страница 4: ...als 3 Open the thermostat PCB to the left by pressing the PCB retaining tabs Fig 3 4 Pull cables 6 inches out of the wall 5 Thread cable through the central hole of the base 6 Align the base and mark the location of the two mounting holes on the wall Install proper side of base up 7 Install anchors in the wall 8 Insert screws through the mounting holes on each side of the base and mount base on wa...

Страница 5: ... Model Number Heat Pump TB7656B TB7605B TB7652B TB7600B TB7652A TB7600A TB7652H TB7600H Programmable Yes No Yes No Yes No Programmable Yes No Top left terminal block 1 Cool Stage 2 Y2 Y2 Y2 Y2 Blank Blank 1 Compressor Stage 2 Y2 Y2 2 Cool Stage 1 Y1 Y1 Y1 Y1 Y1 Y1 2 Compressor Stage 1 Y1 Y1 3 Fan G G G G G G 3 Fan G G 4 24 V Hot RC RC RC RC RC RC 4 24 V Hot RC RC 5 24 V Com C C C C C C 5 24 V Com ...

Страница 6: ...2 4601 104 40 5 3467 31 35 234 4009 5 15 71 2430 41 5 25 1119 77 25 10 0000 113 45 4 3881 22 30 171 3474 14 10 54 1988 50 10 19 7390 86 30 8 0694 122 50 3 6202 13 25 126 6109 23 5 41 5956 59 15 15 6286 95 35 6 5499 131 55 3 0016 Y2 Y1 G RC C RH W1 JUMPER J1 COOL STAGE 2 COOL STAGE 1 FAN HEAT STAGE 1 HEAT STAGE 2 0 10 VDC 24V COM AUXILIARY OUTPUT W2 EC AU DI1 DI2 DIGITAL INPUT 1 DIGITAL INPUT 2 RS ...

Страница 7: ...B WALLOVR 1014 CAN BE MIXED AND MATCHED TB WALL 1014 AND TB WALLOVR 1014 ARE TO BE WIRED IN PARALLELL ENSURE THE DIP SWITCH SETTING IS CORRECT IN EACH REMOTE SENSOR 1 1 Scom RS AUX C DI TB WALLOVR 1014 DIP SWITCHES S1 OFF S2 ON DIP SWITCHES S2 1 OFF S2 2 ON ON 1 2 S2 Scom RS AUX C DI TB WALLOVR 1014 Scom RS AU C D1 TB7600 SERIES THERMOSTAT D2 Scom RS AU C D1 TB7600 SERIES THERMOSTAT D2 Scom RS AU ...

Страница 8: ...abled If alarms are detected they will automatically be displayed at the end of the status display scroll During an alarm message display the back lit screen will light up at the same time as the message and shut off during the rest of the status display Two alarms maximum can appear at any given time The priority for the alarms is as follows Frost ON Indicates that the heating is energized by the...

Страница 9: ...m and to manually scroll through the displayed information The NO key is used when you do not desire a parameter change and to advance to the next menu item Can also be used to toggle between heating and cooling setpoints The MENU key is used to access the Main User Menu or exit the menu IF STATUS IS UNOCCUPIED IF STATUS IS TEMPORARY OCCUPIED TIME OVERRIDE SCHD Y N CANCEL OVRD Y N TEMPERAT SET Y N...

Страница 10: ...rmostat is in unoccupied mode The unoccupied mode is enabled either by the internal timer scheduling or by a remote NSB contact via DI1 or DI2 If DI1 or DI2 is configured to operate as a remote temporary override contact this menu will be disabled Answering Yes to this prompt will cause the thermostat to go into occupied mode for an amount of time equal to the parameter TOccTime 1 to 12 hours RESU...

Страница 11: ...only the automatic heating frost protection at 50 F 10 C is enabled FAN MODE SETTING This section of the menu is permits the setting of the fan mode operation Use to set value Yes key to confirm Fan mode On Fan is on continuously even when system mode is OFF Fan mode Auto Fan cycles on a call for heating or cooling for both occupied and unoccupied periods Fan mode Smart During occupied periods fan...

Страница 12: ...ss day scheduling No key to jump to next day Copy Y N Previous Yes next Æ No down È Copy Y N Previous Yes next Æ No down È Yes Will copy previous day schedule No Daily schedules will be accessed Yes key to copy previous day No key to set new time value for each day Occupied 00 00 AM Use To set value Occupied 00 00 AM Use To set value Occupied 00 00 AM Use To set value Sets Event 1 Occupied time Wi...

Страница 13: ...1 Occupied time Will activate occupied setpoints Use to set value Yes key to confirm Unoccup 00 00 AM Use To set value Unoccup 00 00 AM Use To set value Unoccup 00 00 AM Use To set value Sets Event 2 Unoccupied time Will activate unoccupied setpoints Use to set value Yes key to confirm Occupie2 00 00 AM Use To set value Occupie2 00 00 AM Use To set value Occupie2 00 00 AM Use To set value Sets Eve...

Страница 14: ...on of the menu permits the user to set the time and day Time setting Day setting Time format setting Time set Y N No next Æ Yes down È Day set Y N No next Æ Yes down È 12 24hrs set Y N No exit Yes down È Time 0 00 Use To set value Day Monday Use To set value 12 24hrs 12 hrs Use To set value M16943 ...

Страница 15: ... alone unit this parameter will not be used or displayed For BACnet models valid range to use is from 0 to 127 Default value of 254 disables BACnet communication for the thermostat For wireless models valid range is 0 to 254 with a maximum of 30 thermostats per WEB 2xx controller and 50 thermostats per WEB 6xx 7xx controller PAN ID Personal Area Network Identification Default value 0 Range is 0 to...

Страница 16: ...d setpoints This option provides low cost setback operation via an occupancy sensor or from a dry contact RemOVR Temporary override remote contact Disables all override menu function of the thermostat The override function is now controlled by a manual remote momentarily closed contact When configured in this mode the input operates in a toggle mode With this function enabled it is now possible to...

Страница 17: ... PI control loop CAUTION Note that the default value of 2 0 F 1 1 C gives satisfactory operation in most normal installation cases The use of a superior proportional band different than the factory one is normally warranted in applications where the thermostat location is problematic and leads to unwanted cycling of the unit A typical example is a wall mounted unit where the thermostat is installe...

Страница 18: ... modified 2 3 or 4 F 1 0 to 2 0 C Fan cont Fan control Default value On For multi stage models fan control applies to W1 and W2 For heat pump models fan control applies to W1 only Emergency heat Fan control in heating mode When selecting On the thermostat in all cases will always control the fan terminal G Valid for On or Auto fan mode When selecting Off the fan terminal G when heating stages term...

Страница 19: ...the WEBs AX Workbench 2 events will set up programming for the following Event 1 is for Occupied setpoints Event 2 is for Unoccupied setpoints 4 events will set up programming for the following Event 1 is for Occupied setpoints Event 2 is for Unoccupied setpoints Event 3 is for Occupied setpoints Event 4 is for Unoccupied setpoints Aux cont Auxiliary contact configuration Default value N O normall...

Страница 20: ...eating setpoint Economy mode In Heating mode If the heat pump is not able to satisfy the heating setpoint the auxiliary heat will be energized to satisfy only when the temperature has dropped 2 0 F 1 1 C below the heating setpoint Selecting economy mode will add a deadband between the heat pump and auxiliary heat in heating mode The actual temperature maintained will be lower than the true heating...

Страница 21: ...of the mechanical cooling if the free cooling economizer cannot maintain the cooling setpoint Off Typically applies when the MS mixed air temperature sensor is installed after the mechanical cooling refrigeration coils In this case mechanical cooling will never operate at the same time as free cooling On Typically applies when the MS mixed air temperature sensor is installed before the mechanical ...

Страница 22: ...ll end and the equipment will start Heating setpoint is satisfied Raise the Heating setpoint Heating lockout attained Mode is locked out based on outside air temperature Change configuration parameter H Lock to value 120 F 49 C to by pass lockout Wiring error Start the Fan by forcing the Fan ON mode Put a jumper across terminals RH and W1 The heating should come ON If it does not verify wiring and...

Страница 23: ... verify wiring and check if a jumper is required between RC and RH Heat pump does not operate in heating mode Wrong mode selected Select heating mode Thermostat in Unoccupied mode Select Occupied Hold in Schedule hold or Override to force the thermostat Occupied heating setpoint Anti cycle delay active Wait the anti cycling period will end and the equipment will start Heating setpoint is satisfied...

Страница 24: ...curacy 0 9 F 0 5 C 70 F 21 C typical calibrated Occupied and unoccupied setpoint range cooling 54 F to 100 F 12 0 to 37 5 C Occupied and unoccupied setpoint range heating 40 F to 90 F 4 5 C to 32 C Room and outdoor air temperature range 40 F to 122 F 40 C to 50 C Proportional band for room temperature control Factory set heating and cooling at 2 0 F 1 1 C Digital inputs Relay dry contact only acro...

Страница 25: ...ice must accept any interference received including interference that may cause undesired operation Agency Approvals on BACnet models BTL IMPORTANT All TB7600 series controls are for use as operating controls only and are not safety devices These instru ments have undergone rigorous tests and verifications prior to shipment to ensure proper and reliable opera tion in the field Whenever a control f...

Страница 26: ...TB7600 SERIES COMMUNICATING RTU HEAT PUMP THERMOSTATS 62 2016 05 26 ...

Страница 27: ...TB7600 SERIES COMMUNICATING RTU HEAT PUMP THERMOSTATS 27 62 2016 05 ...

Страница 28: ...MOSTATS Automation and Control Solutions Honeywell International Inc 1985 Douglas Drive North Golden Valley MN 55422 customer honeywell com U S Registered Trademark 2011 Honeywell International Inc 62 2016 05 M S Rev 09 11 Printed in United States ...

Отзывы: