T8665A CHRONOTHERM® IV DELUXE PROGRAMMABLE WIRELESS THERMOSTAT
69-1535-3
6
Table 3. Thermostat Installer Setup Options.
Select
Installer Setup
Number
(Press Time
V
key to
change)
Factory Setting
Other Choices
(Press
V
or
W
key to change)
Actual
Setting
Display
Description
Display
Description
Not used
1
—
—
—
—
—
Fan operation
a
2
0
Conventional
applications where
equipment controls
fan operation in heat
mode
1
Heat pump or electric heat
applications where
thermostat controls fan
operation in heat mode
Not used
3
—
—
—
—
—
Heating cycle
rate
4
6
6—6 cph used for
conventional heat
1, 3 or 9
1—1 cph used for radiant
floor heat, gravity system
3—3 cph used for hot
water systems or high
efficiency furnaces
9—9 cph used for electric
heat systems
Not used
5 thru 11
—
—
—
—
—
System setting
adjustment
12
1
Manual changeover 0 or 2
0—Auto changeover
2—Auto only
Adaptive
Intelligent
Recovery™
control
13
0
Adaptive Intelligent
Recovery™ control
is activated (system
starts early so
setpoint is reached
by start of program
period)
1
Conventional recovery
(system starts recovery at
programmed time)
—
Degree
temperature
display
14
0
Temperature is
displayed in °F
1
Temperature is displayed
in °C
Not used
15
—
—
—
—
—
Clock format
16
0
12-hour clock format 1
24-hour clock format
Not used
17 and 18
—
—
—
—
—
Extended fan
operation in
heating
a
19
0
No extended fan
operation after the
call for heat ends
1
Fan operation is extended
90 seconds after the call
for
heat ends.
Extended fan
operation in
cooling
a
20
0
No extended fan
operation after the
call for cool ends
1
Fan operation is extended
90 seconds after the call
for
cool ends.
Not used
21 thru 29
—
—
—
—
—
Deadband
30
3
Heating and cooling
setpoints can be set
no closer than 3°F
(1.5°C)
4 thru 10 Heating and cooling
setpoints can be set no
closer than the chosen
value:
4—4°F (2°C)
5—5°F (2.5°C)
6—6°F (3°C)
7—7°F (3.5°C)
8—8°F (4°C)
9—9°F (4.5°C)
10—10°F (5°C)
Not used
31 and 32
—
—
—
—
—
Minimum off
time for the
compressor
33
5
five-minute
minimum off time for
the compressor
0 thru 4
Minimum number of
minutes (0 thru 5) the
compressor will be off
between calls for the
compressor