T8602D CHRONOTHERM

® 

IV DELUXE PROGRAMMABLE THERMOSTATS

11

69-1507—2

TROUBLESHOOTING GUIDE

Table 6. Troubleshooting Guide.

Symptom

Possible Cause

Action

Display does not 
come on.

Thermostat is not being 
powered.

• Check if batteries are present and installed correctly.

— If batteries are present and installed correctly, replace 

thermostat.

Temperature 
display is incorrect.

Room temperature display has 
been reconfigured.

Enter Installer Setup number 37 and reconfigure the display.

Thermostat is configured for °F 
or °C display.

Enter Installer Setup number 14 and reconfigure the display.

Bad thermostat location.

Relocate the thermostat.

Temperature 
settings do not 
change. (Example: 
Cannot set the 
heating higher or 
the cooling lower.)

The upper or lower temperature 
limits were reached. 

Check the temperature setpoints:

• Heating limits are 40 to 90°F (4.5 to 32°C)
• Cooling limits are 48 to 99°F (7 to 37°C)

The setpoint temperature range 
stops were configured.

Check Installer Setup numbers 34 and 35 and reconfigure the 
setpoint stops.

Heating does not 
come on.

No power to the thermostat.

• Check for 24 Vac between R and W terminals (check for 

750 mV on PowerPile

®

 Systems).

— If missing 24 Vac:

— check if the circuit breaker is tripped—reset the circuit 

breaker.

— check if the system fuse is blown—replace the fuse.
— check if the power switch on the HVAC equipment is in 

the Off position—set to the On position.

— check wiring between thermostat and HVAC 

equipment—replace any broken wires and tighten any 
loose connections.

— If 24 Vac is present, proceed with troubleshooting.

Thermostat minimum off time is 
activated.

Wait up to five minutes for the system to respond.

System selection is not set to 
Heat.

Set system selection to Heat.

Heating setpoint is below room 
temperature.

Check heating setpoint. Set heating setpoint to desired 
temperature.

Cooling does not 
come on.

No power to the thermostat.

• Check for 24 Vac between R or RC and Y terminals 

— If missing 24 Vac:

— check if the circuit breaker is tripped—reset the circuit 

breaker.

— check if the system fuse is blown—replace the fuse. 
— check if the power switch on the HVAC equipment is in 

the Off position—set to the On position.

— check wiring between thermostat and HVAC 

equipment—replace any broken wires and tighten any 
loose connections.

— If 24 Vac is present, proceed with troubleshooting.

Thermostat minimum off time is 
activated.

• Wait up to five minutes for the system to respond.
• Enter Installer Setup number 33. Reconfigure minimum off 

time (if required).

System selection is not set to 
Cool.

Set system selection to Cool.

Cool setpoint is above room 
temperature.

Check cooling setpoint. Set cooling setpoint to desired 
temperature.

Содержание T8602D

Страница 1: ...the product or cause a hazardous condition 2 Check the ratings given in the instructions and on the product to make sure the product is suitable for your application 3 Installer must be a trained experienced service technician 4 After completing installation use these instructions to check out the product operation Location Install the thermostat about 5 ft 1 5m above the floor in an area with goo...

Страница 2: ...RING All wiring must comply with local electrical codes and ordinances Refer to Fig 3 and 6 for typical hookup A letter code is located near each terminal for identification CAUTION Electrical Hazard Can cause electric shock or equipment damage Disconnect power before wiring 1 Loosen the terminal screws on the wallplate and connect the system wires See Fig 7 IMPORTANT Use 18 gauge color coded ther...

Страница 3: ...M THE THERMOSTAT CABLE 2 2 2 1 3 OT OT OUTDOOR TEMPERATURE SENSOR 3 RC L1 HOT L2 M10348 FAN RELAY Y G THERMOSTAT RC HEAT RELAY R W L1 HOT L2 COMPRESSOR CONTACTOR HEATING TRANSFORMER COOLING TRANSFORMER B HEAT DAMPER COOL DAMPER O 2 1 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED JUMPER RC TERMINAL TO R TERMINAL WHEN INSTALLED ON A ONE TRANSFORMER SYSTEM CAN BE USED FOR ...

Страница 4: ...n heating and cooling operation depending on the indoor temperature Fan settings control the system fan On Fan operates continuously Auto Fan operates with equipment Fig 10 Thermostat System and Fan key locations M14624 Time Set Program System Fan Run Program Hold Temp Set Current Day Time Wake Leave Return Sleep Day Heat Cool Settings Daylight Time Copy INCREASE TEMPERATURE SETTING OR SCROLL FORW...

Страница 5: ... 11 and 12 To advance to the next Installer Setup press the Time key To change a setting use the increase or decrease key To scroll the Installer Setup numbers backward press the Time key To exit the Installer Setup press Run Program Fig 11 Display of all LCD segments Fig 12 Display of Installer Setup number and setting CAUTION Heat Pump and Electric Heat System Configuration Hazard Can cause equi...

Страница 6: ...arly so setpoint is reached by start of program period 1 Conventional recovery system starts recovery at programmed time Degree temperature display 14 0 Temperature is displayed in F 1 Temperature is displayed in C Not Used 15 Clock format 16 0 12 hour clock format 1 24 hour clock format Not Used 17 and 18 Extended fan operation in heating a 19 0 No extended fan operation after the call for heat e...

Страница 7: ...t Used 36 Temperature display adjustment 37 0 No difference in displayed temperature and actual room temperature 3 thru 3 1 Display adjusts to 1 F higher than actual room temperature 2 Display adjusts to 2 F higher than actual room temperature 3 Display adjusts to 3 F higher than actual room temperature 1 Display adjusts to 1 F lower than actual room temperature 2 Display adjusts to 2 F lower than...

Страница 8: ... days remaining at any time by pressing the i key three or four times If more than one timer is active all active timers show sequentially when pressing the i key several times M14619 Time Set Program System Fan Run Program Hold Temp Set Current Day Time Set Current Day Time Wake Leave Return Sleep Day Heat Cool Settings Daylight Time Copy Set Day Time Mon PM M14620 Time Set Program System Fan Run...

Страница 9: ... test and Time to go to the next test The Run Program key will not exit this test Press Time or Time and then the Run Program key to exit Test Number System Test Description 10 19 Heating equipment can be turned on and off 30 39 Cooling equipment can be turned on and off 40 49 Fan equipment can be turned on and off 60 0 to 60 19 Keyboard keys test M14559 Aux Ht Set Day Time Set Program Mon Wake Le...

Страница 10: ...ware identification code Example 02 software ID code 2 4 Press the increase key again to display the soft ware revision number Example 001 Revision number 1 5 Press the increase key again to display the EEPROM identification code Example 314 EEPROM ID 314 6 Press the Run Program key to exit the System Test The System Test times out after four minutes without any key presses CHECKOUT Outdoor Temper...

Страница 11: ...ircuit breaker check if the system fuse is blown replace the fuse check if the power switch on the HVAC equipment is in the Off position set to the On position check wiring between thermostat and HVAC equipment replace any broken wires and tighten any loose connections If 24 Vac is present proceed with troubleshooting Thermostat minimum off time is activated Wait up to five minutes for the system ...

Страница 12: ...the furnace has warmed up to a setpoint Wait a minute after seeing the on indicator and then check the registers Heating or cooling equipment is not operating Verify operation of heating or cooling equipment in self test Outdoor tempera ture not displayeda Option not activated Enter Installer Setup number 24 and set to 1 Thermostat must have OT terminals and a C7089B1000 installed Outdoor temperat...

Отзывы: