T8601D CHRONOTHERM® IV DELUXE PROGRAMMABLE THERMOSTATS
5
69-1626
— To advance to the next Installer Setup, press the Time
▲
key.
— To change a setting, use the increase
▲
or decrease
▼
key.
— To scroll the Installer Setup numbers backwards,
press the Time
▼
key.
— To exit the Installer Setup, press Run Program.
Fig. 10. Display of all LCD settings.
Fig. 11. Display of Installer Setup
number and setting.
CAUTION
Equipment Damage Hazard.
System running without fan can damage
equipment.
Be sure to configure heat pump and electric heat
systems to 1 in Installer Setup number 2.
IMPORTANT
Only configurable numbers are shown on the
device. Example: If thermostat does not have a
System key, Installer Setup Number 12 is not
displayed. Review Table 3 factory-settings and
mark any desired changes in the Actual Set-
tings column. When Installer Setup is complete,
review settings to confirm they match system.
M14559
Aux Ht
Set Day/Time
Set Program
Mon
Wake Leave Return
Sleep
Outdoor
Room
Filter
Wait
System
Fan
Em Heat
On
Auto
Off
Cool
Auto
AM
PM
Hold for
Heat
Cool
Repl Batt
Recovery
DST
Tue Wed Thu Fri Sat Sun
Days
Temporary Setting
Em Ht
M14618
INSTALLER SETUP
NUMBER DISPLAY
(COLUMN 2 OF TABLE 3)
FACTORY SETTING OR OTHER
CHOICE DISPLAY (COLUMN 3
OR 5 OF TABLE 3)
Table 3. Thermostat Installer Setup Options.
Select
Installer Setup
Number
(Press Time
▲
key to change)
Factory-Setting
Other Choices
(Press
▲
or
▼
key to change)
Actual
Setting
Display
Description
Display
Description
Not used
1
—
—
—
—
—
Fan operation
a
2
0
Conventional application
where equipment control
fan operation in heat mode
1
Heat pump or electric
heat applications where
thermostat controls fan
operation in heat mode
Not used
3
—
—
—
—
—
Heating cycle
rate
4
6
6—6 cph used for conven-
tional heat
1, 3 or 9 1—1 cph used for radiant
floor heat, gravity
system
3—3 cph used for hot
water systems or high
efficiency furnaces
9—9 cph used for electric
heat systems
Not used
5 thru 11
—
—
—
—
—
System setting
adjustment
12
1
Manual changeover
0 or 2
0—Auto changeover
2—Auto only
Adaptive
Intelligent
Recovery™
control
13
0
Adaptive Intelligent
Recovery™ control is
activated (system starts
early so setpoint is reached
by start of program period)
1
Conventional recovery
(system starts recovery at
programmed time)
Degree
temperature
display
14
0
Temperature is displayed in
°F
1
Temperature is displayed
in °C
Not used
15
—
—
—
—
—
Clock format
16
0
12-hour clock format
1
24-hour clock format