T8524 DELUXE ELECTRONIC THERMOSTAT
68-0202
7
Table 4. Thermostat Installer Setup Options.
(continued)
Installer Setup
Number (Press
Time
▲
key to
Factory-Setting
Other Choices
(Press
▲
or
▼
key to change)
Actual
Select
change)
Display
Description
Display
Description
Setting
Not used
1
—
—
—
—
—
Fan operation
2
0
Conventional
applications where
equipment controls
fan operation in heat
mode
1
Electric heat applications
where thermostat controls fan
in heat mode
Not used
3
—
—
—
—
—
Heating cycle rate
a
4
6
Stage 1
3 or 9
3—3 cph
used for steam systems
5
Stage 2
6—6 cph factory setting for all
stages of system
9— 9 cph used for electric
heat
Not used
6 thru 11
—
—
—
—
—
System setting
adjustment
12
1
Manual changeover
0 or 2
0—Auto changeover
2—Fixed auto changeover
Not used
13
—
—
—
—
—
Degree tempera-
ture display
14
0
Temperature is
displayed in °F
1
Temperature is displayed
in °C
Not used
15 thru 18
—
—
—
—
—
Extended fan
operation in heating
19
0
No extended fan
operation after the call
for heat ends
1
Fan operation is extended
90 seconds after the call for
heat ends.
Extended fan
operation in cooling
20
0
No extended fan
operation after the call
for cool ends
1
Fan operation is extended
90 seconds after the call for
cool ends.
Not used
21 thru 23
—
—
—
—
—
Outdoor
temperature display
(models with OT
terminals)
24
0
No outdoor
temperature is
displayed
1
Outdoor temperature is
displayed. Needs a
C7089B1000 Outdoor Sensor
to operate.
Not used
25 thru 29
—
—
—
—
—
Deadband
30
3
Heating and cooling
setpoints can be set
no closer than 3°F
(1.5°C)
4 thru 10 Heating and cooling setpoints
can be set no closer than the
chosen value:
4—4°F (2°C)
5—5°F (2.5°C)
6—6°F (3°C)
7—7°F (3.5°C)
8—8°F (4°C)
9—9°F (4.5°C)
10—10°F (5°C)
Not used
31 and 32
—
—
—
—
—
Minimum off time
for the compressor
33
5
5 minute minimum off
time for the
compressor
0 thru 4
Minimum number of minutes
(0 thru 5) the compressor will
be off between calls for the
compressor
Temperature range
stops in heating
34
90
Highest setpoint
heating can be set to
40 to 89
Temperature range (1°F
increments) heating setpoint
can be set to
a
The cycle rate for the last stage of heat is adjustable with 6 cph being the factory setting.