T8501A,B,C,D MICROELECTRONIC THERMOSTATS

Table 2. Thermostat Installer Setup Options (continued).

a

Available on select models.

Mode 02 must be set to 01 to extend fan operation.

c

 T8501D is 48

°

F.

Mode Display

(Press 

  i   

key

Factory-Setting

Other Choices  

(Press 

 or  

 key to change)

Select

to change)

Display

Description

Display

Description

Not used

13  

Degree tempera-
ture display

14

00

Temperature is
displayed in °F

01

Temperature is displayed in °C

Not used

15 thru 18  

Extended fan
operation in
heating

a,b

19  

00

No extended fan
operation after the call
for heat ends

01

Fan operation is extended  
90 seconds after the call for  
heat ends

Extended fan
operation in
cooling

a

20  

00

No extended fan
operation after the call
for cool ends

01

Fan operation is extended  
90 seconds after the call for  
cool ends

Not used

21 thru 23  

Outdoor
temperature
display

a

24

00

No outdoor temperature
is displayed

01

Outdoor temperature is displayed.
Needs a C7089B1000 Outdoor
Sensor to operate.

Not used

25 thru 32

Minimum off time
for the
compressor

33

05

5 minute minimum off
time for the compressor

00, 01,
02, 03 or
04

Minimum number of minutes  
(0 thru 5) the compressor will be
off between calls for the
compressor

Heating setpoint
range stop

a

34

90

Heating setpoint can be
set no higher than 90°F

40 thru
90

Number can be set anywhere
between 40 and 90 in 1°F
increments

Cooling setpoint
range stop

a

35

45

c

Cooling setpoint can be
set no lower than 45°F

c

45

c

 thru

99

Number can be set anywhere
between 45

c

 and 99 in 1°F

increments

System On
display

a

36

00

LCD On symbol is
displayed when system
is energized

01

Display is disabled, usually set for
01 for a zoned system

Temperature
display
adjustment

37

00

No difference in
displayed temperature
and actual room
temperature

01 thru
06

01—Display adjusts to 1°F higher

than actual room temperature

02—Display adjusts to 2°F higher

than actual room temperature

03—Display adjusts to 3°F higher

than actual room temperature

04—Display adjusts to 1°F lower

than actual room temperature

05—Display adjusts to 2°F lower

than actual room temperature

06—Display adjusts to 3°F lower

than actual room temperature

Содержание t8501A

Страница 1: ...g installation use these instructions to check out the product operation T8501 System Changeover System Selection Fan Selection Comments A Heat only None None None B Heat only None Heat Off On Auto Select models have only a system switch or fan switch and some models have both C Heat Cool Manual Heat Off Cool On Auto System and fan selections are done by switches D Heat Cool Automatic Heat Off Coo...

Страница 2: ...he holes 쐂 Tighten mounting screws WIRING All wiring must comply with local electrical codes and ordinances Refer to Fig 3 through 5 for typical hookups A letter code is located near each terminal for identifica tion CAUTION Disconnect power before wiring to prevent electrical shock or equipment damage 쐃 Loosen the terminal screws on the wallplate and connect the system wires See Fig 6 IMPORTANT U...

Страница 3: ...O G Y W OUTDOOR TEMPERATURE SENSOR COOL CHANGEOVER VALVE OR DAMPER HEAT CHANGEOVER VALVE OR DAMPER THERMOSTAT 1 2 2 M4826 FOR WRAPAROUND INSERTION STRIP 7 16 IN 11 MM FOR STRAIGHT INSERTION STRIP 5 16 IN 8 MM L1 HOT L2 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED AVAILABLE ON SELECT MODELS JUMPER Rh TO Rc IN A SINGLE TRANSFORMER SYSTEM 1 HEATING RELAY OR VALVE COIL M48...

Страница 4: ...with your fingertip or similar blunt tool Sharp instruments like a pen or pencil point can damage the keyboard Temperature Settings The default setpoint for heat is 70 F 21 C and for cool is 78 F 25 5 C Press the increase or decrease key to change the present setting To change between heat and cool press the Information i key until the setting to be changed appears INSTALLER SETUP NOTE For most ap...

Страница 5: ...on of key presses are required to use the Installer Setup feature To enter the Installer Setup mode press and hold the Information i key with the increase and decrease keys until the first mode number is displayed All display segments appear for approximately three seconds before the mode number is displayed See Figs 11 and 12 To advance to the next Installer Setup mode press the Information i key...

Страница 6: ...perate Not used 25 thru 32 Minimum off time for the compressor 33 05 5 minute minimum off time for the compressor 00 01 02 03 or 04 Minimum number of minutes 0 thru 5 the compressor will be off between calls for the compressor Heating setpoint range stopa 34 90 Heating setpoint can be set no higher than 90 F 40 thru 90 Number can be set anywhere between 40 and 90 in 1 F increments Cooling setpoint...

Страница 7: ...two zeros appear Continued Em HeatOffCool Auto Only Heat Cool OnAuto System Fan Room Outdoor Em Ht Temporary Setting Wait Humid Aux Ht Remote Repl Batt M4844 M6792 TEST MODE NUMBER Test Number Self Test Description 10 19 Heating equipment can be turned on and off 30 39 Cooling equipment can be turned on and off 40 49 Fan equipment T8501D only can be turned on and off 60 69 System key or system swi...

Страница 8: ...ss Test Mode Number Description Key or Switch Operation Self Test a IMPORTANT Test Mode Numbers will only be displayed when the system is configured for the selected function EXAMPLE Numbers 60 61 and 62 are the only numbers that will be displayed when a system is configured for heat only SYSTEM KEY OR SWITCH SELF TEST When system switch is used move switch to see Test Mode Numbers i 60 Change fro...

Страница 9: ...d tighten any loose connections If 24 Vac is present proceed with troubleshooting Thermostat microprocessor is locked up Remove the thermostat from the wallplate for 2 minutes After 2 minutes replace the thermostat on the wallplate Temperature display is incorrect Room temperature display has been reconfigured Enter Installer Setup mode number 37 and reconfigure the display Thermostat is configure...

Страница 10: ...ostat minimum off time is activated Wait up to five minutes for the system to respond Enter Installer Setup mode number 33 Reconfigure minimum off time if required System selection is not set to Cool Set system selection to Cool System On indicator is lit but no heat is being delivered Fan operation set for 00 conventional heat when it should be set for 01 electric heat Enter Installer Setup mode ...

Страница 11: ...69 0959 11 T8501A B C D MICROELECTRONIC THERMOSTATS ...

Страница 12: ...uilding Control Honeywell Limited Honeywell Limitée 155 Gordon Baker Road North York Ontario M2H 2C9 69 0959 J H 10 96 Printed in Taiwan R O C Home and Building Control Honeywell Inc Honeywell Plaza P O Box 524 Minneapolis MN 55408 0524 www honeywell com yourhome ...

Отзывы: