Honeywell T8501 Скачать руководство пользователя страница 6

T8501 AND T8511 DELUXE ELECTRONIC THERMOSTATS

68-0162—1

6

SETTINGS

System and Fan Settings

System settings control the thermostat operation as follows:

Em. Heat (T8511 only): Emergency heat relay is

automatically controlled by the thermostat. The cooling
system is off. The compressor is de-energized.

Heat: The thermostat controls the heating.
Off: Both the heating and cooling are off.
Cool: The thermostat controls the cooling.
Auto: The thermostat automatically changes between

heating and cooling operation, depending on the indoor
temperature.

Fan settings control the system fan as follows:

On: Fan operates continuously.
Auto: Fan operates with equipment.

The system default setting is Heat and the fan default setting
is Auto. Use the keyboard to change to the desired settings.
See Fig. 7 and 8.

M10147

i

Press to select
heating or cooling
equipment.

  

Em. Ht.-Emergency heating
Heat— Heating equipment
Off — No equipment
Cool—Cooling equipment
Auto—Thermostat

automatically selects
heating and cooling
equipment.

Press to select
heating or cooling
equipment.

  

On

Fan runs continuously

Auto—Fan runs when

heating or cooling
equipment operates

System

System

System

Fan

Fan

Fan

1

1

CHECK LIGHT ON SELECT MODELS

Fig. 7. Thermostat System and fan key location.

NOTE:

Always press the keys with your fingertip or similar
blunt tool. Sharp instruments like a pen or pencil
point can damage the keyboard.

Temperature Settings

The default setpoint for heat is 70

°

F (21

°

C) and for cool is

78

°

F (25.5

°

C). Press the increase 

 or decrease 

 key to

change the present setting. To change between heat and
cool, press the Information

   i   

key until the setting to be

changed appears. Press the increase 

 or decrease 

 key

to adjust the setting.

INSTALLER SETUP

NOTE:

For most applications, the thermostat factory
settings will not need to be changed. Review the
factory settings in Table 4 and if no changes are
necessary, go to the Installer System Test section.

The Installer Setup is used to customize the thermostat to
specific systems. Installer Setup numbers are listed in
Table 4. The table includes all the configuration options
available.

A combination of key presses are required to use the Installer
Setup feature.

To enter the Installer Setup, press and hold the
Information

   i   

key with the increase 

 and decrease 

keys until the first number is displayed. All display
segments appear for approximately three seconds before
the number is displayed. See Fig. 8 and 9.

To advance to the next Installer Setup, press the
Information

   i   

key.

To change a setting, use the increase 

 and decrease 

keys.

To exit the Installer Setup, press and hold the Information

 i   

key until the display returns to normal (approximately

three seconds). The display will scroll the numbers
backwards to get to the normal display. The Installer
Setup is automatically exited if no key presses are made
for five minutes.

Em HeatOffCool Auto Only

Heat Cool

OnAuto

System

Fan

Room

Outdoor

Em Ht Temporary Setting

Wait

%Humid

Aux Ht

Remote

Repl

Batt

M4844

Fig. 8. All the segments of LCD displayed.

Fig. 9. Installer Setup and setting displayed.

CAUTION

Heat pump and electric heat systems must be
configured to 01 in Installer Setup 02 to prevent
equipment damage caused by the system running
without the fan (T8501 only).

IMPORTANT

Only configurable numbers are shown on the device.
Example: If thermostat does not have a system key,
Installer Setup number 12 will not be displayed.
Review Table 4 factory settings and mark any desired
changed in the Actual Setting column. When the
Installer Setup is complete, review the settings to
confirm that they match the system.

M10406

INSTALLER SETUP
NUMBER DISPLAY 
(COLUMN 2 OF TABLE 4)

FACTORY SETTING OR
OTHER CHOICE DISPLAY
(COLUMN 3 OR 5 OF TABLE 4)

Содержание T8501

Страница 1: ...ccurate than a thermometer Configurable features allows one model to be used to replace many different models less inventory no need to carry separate models to get these features F or C temperature display Automatic or manual changeover Electric or conventional heat fan operation Adjustable heating cycle rate Minimum off time for cooling compressors and heat pumps protects and extends the life of...

Страница 2: ...ications Also This product is tested and calibrated under closely controlled conditions and some minor differences in performance can be expected if those conditions are changed Models See Table 1 Electrical Rating Input Power 18 to 30 Vac 50 60 Hz Load Rating See Table 2 Temperature Setpoint Range 40 F to 99 F 4 C to 37 C depending on model and if in heating or cooling Display Range Controlled 30...

Страница 3: ...the product or cause a hazardous condition 2 Check the ratings given in the instructions and on the product to make sure the product is suitable for your application 3 Installer must be a trained experienced service technician 4 After completing installation use these instructions to checkout the product operation CAUTION Disconnect power supply to prevent electrical shock or equipment damage Loca...

Страница 4: ...T Outdoor temperature sensor input for C7089B Input R V 24V system transformer Input RC 24V cooling transformer Input RH V 24V heating transformer Input W Heating relay Output 24V powered contact W1 H1 R3 Heating relay Output 24V powered contact W2 H2 R4 W3 Y Stage 2 heating relay or auxiliary heat relay Output 24V powered contact X1 A1 A C L X Z User defined Light Emitting Diodes LEDs Annunciatio...

Страница 5: ...rmostat Fig 4 Proper wiring technique Mounting Thermostat 1 Engage tabs at the top of thermostat and wallplate See Fig 5 2 Press lower edge of case to latch NOTE To remove the thermostat from the wall first pull out at the bottom of the thermostat remove top last M6798A B PRESS LOWER EDGE OF CASE TO LATCH A ENGAGE TABS AT TOP OF THERMOSTAT AND WALLPLATE Fig 5 Mounting thermostat on wallplate Using...

Страница 6: ...ostat factory settings will not need to be changed Review the factory settings in Table 4 and if no changes are necessary go to the Installer System Test section The Installer Setup is used to customize the thermostat to specific systems Installer Setup numbers are listed in Table 4 The table includes all the configuration options available A combination of key presses are required to use the Inst...

Страница 7: ...ed fan operation in heatinga b 19 00 No extended fan operation after the call for heat ends 01 Fan operation is extended 90 seconds after the call for heat ends Extended fan operation in coolingb 20 00 No extended fan operation after the call for cool ends 01 Fan operation is extended 90 seconds after the call for cool ends Not used 21 thru 23 Outdoor temperature displayb 24 00 No outdoor tempera ...

Страница 8: ...system test The system test will time out after five minutes without any key presses Press and hold the increase and decrease keys at the same time until two zeros appear All segments of the display will be displayed before the two zeros appear See Fig 10 and 11 M6792A TEST NUMBER Installer Setup Number Press i key Factory Setting Other Choices Press or key to change Actual Select to change Displa...

Страница 9: ...pment system test 41 Fan comes on 40 Fan turns off Key or Switch Operation System Test IMPORTANT Test numbers will only be displayed when the system is configured for the selected function EXAMPLE Numbers 60 61 and 62 are the only numbers that will be displayed when a system is configured for heat only SYSTEM KEY SYSTEM TEST i 60 Change from cooling or fan to key operation system test System 61 He...

Страница 10: ...ature is displayed to exit the system test The system test times out after five minutes without any key presses CHECKOUT Outdoor Temperature Sensor where applicable Allow the outdoor temperature sensor to soak in the outdoor air for a minimum of five minutes before taking a reading With an accurate thermometer 1 F 0 5 C measure the temperature at the sensor location allowing time for the thermomet...

Страница 11: ...energy savings Occupants do not need to continually adjust thermostat settings to maintain desired temperature even during severe weather Operation Sequence The thermostat energizes specific terminals depending what the Fan and System are set to The LCD will display symbols and words to report the condition of system See Tables 7 and 8 for specific information Table 7 T8501 Sequence of Operation F...

Страница 12: ...set for electric heat systems the fan comes on at the same time as the heat and is energized by the thermostat The fan is energized by the plenum switch when set for conventional heating system Outdoor Temperature Sensor select models The outdoor temperature sensor is used to display the outdoor temperature Pressing the Information i key once will show the outdoor temperature if Installer Setup nu...

Страница 13: ...wiring between thermostat and HVAC equipment replace any broken wires and tighten any loose connections If 24 Vac is present proceed with troubleshooting Temperature display is incorrect Room temperature display has been reconfigured Enter Installer Setup number 37 and reconfigure the display Thermostat is configured for F or C display select models Enter Installer Setup number 14 and reconfigure ...

Страница 14: ...e circuit breaker is tripped reset the circuit breaker check if the system fuse is blown replace the fuse check if the system switch at the equipment is in the Off position set to the On position check wiring between thermostat and HVAC equipment replace any broken wires and tighten any loose connections If 24 Vac is present proceed with troubleshooting Thermostat minimum off time is activated Wai...

Страница 15: ...T8501 AND T8511 DELUXE ELECTRONIC THERMOSTATS 68 0162 1 15 ...

Страница 16: ...rol Honeywell Limited Honeywell Limitée 155 Gordon Baker Road North York Ontario M2H 3N7 Honeywell Latin American Region 480 Sawgrass Corporate Parkway Suite 200 Sunrise FL 33325 Helping You Control Your World 68 0162 1 J H Rev 10 97 Printed in U S A Home and Building Control Honeywell Inc Honeywell Plaza P O Box 524 Minneapolis MN 55408 0524 Printed on recycled paper containing at least 10 post c...

Отзывы: