Honeywell T834J Скачать руководство пользователя страница 8

T834B; T834C; T834J HEATING-COOLING THERMOSTATS

RECALIBRATION

These thermostats are calibrated at the factory and should 

not need recalibration. If the thermostat seems out of 

adjustment, first check for accurate leveling. To check 

calibration, proceed as follows:

1.

  Move the temperature setting lever to the left 

(low) end of the temperature scale. Place system 

switch at OFF. Wait at least five minutes.

2.

  Remove the thermostat cover. Move the setting 

lever until the switch just makes contact. The 

mercury in the switch will roll to the left end of 

the tube.

3.

  Replace cover and wait five minutes for the cover 

and the thermostat to lose the heat it has gained 

from your hands. If the thermometer pointer and 

the setting lever indicator read approximately the 

same, no recalibration is needed.

3.

  Move the setting lever to a low setting. Wait at 

least five minutes for temperature to stabilize.

4.

  Slowly move the setting lever until it reads the 

same as the thermometer.

5.

  Remove cover. Holding the setting lever so it 

does not move, reinsert wrench and carefully turn 

counterclockwise 

\  until the mercury rolls to 

the left end of the tube but no farther.

6. 

Recheck calibration. Set thermostat system 

switch for desired operation and replace cover.

COIL SHOW N W ITHO UT 
HEAT ANTICIPATOR

If recalibration appears necessary, proceed as follows:

1.

  Place the temperature setting lever at the same 

setting as the thermometer. Remove cover.

2.

  Insert Honeywell part no. 104994A Calibration 

Wrench (order separately) onto the hex nut under 

the coil. See Fig. 13. Holding the setting lever so 

it does not move, turn the wrench clockwise

until the mercury rolls to the right end of the tube. 

Remove wrench and replace cover.

To ensure accurate temperature control, do not 

touch or breathe on bimetal or thermometer.

Æ

2

CALIBRATIO N
W RENCH

M2044A

Fig.  13.  Recalibration  procedure.

Honeywell

Automation and Control Solutions

Honeywell International Inc.  Honeywell Limited—Honeywell Limitée

1985 Douglas Drive North 

35 Dynamic Drive

Golden Valley, MN 55422 

Scarborough, Ontario  M1V 4Z9

69-0444— 10  G.H.  Rev.  5-99

®

  Printed  in  U.S.A.  on  recycled 

paper containing  at  least  10% 

post-consumer paper fibers.

www.honeywell.com/yourhome

Содержание T834J

Страница 1: ...trash at the end of its useful life If this control is replacing a control that contains mercury in a sealed tube do not place your old control in the trash Contact your local waste management authority for instructions regarding recycling and the proper disposal of this control or of an old control containing mercury in a sealed tube INSTALLATION When Installing this Product 1 Read these instruct...

Страница 2: ...t cover bypullingoutwardon bottomedgeofthecover until itsnapsfreeof the thermostat base See Fig 2 Carefullyrem ove anddiscardthefoamplasticshippinginsert that protectstheswitchandbim etal assemblyduring shipping 5 Set theadjustableheat anticipator indicatorto m atchthecurrent drawof theprimaryheating control seeHeatAnticipatorSettingsection 6 Pushexcesswire backthroughtheholeandplug anyopeningwith...

Страница 3: ...G M2035A Fig 4 Internal schematic and typical hookup for T834C dual fuel model in a gas or oil fired or central electric heat system JUMPER W Y FOR SINGLE STAGE HEAT PUMP Fig 6 Internal schem atic and typical hookup for T834C gas or oil fired system s and single stage heat pump or central electric heat 3 69 0444 10 ...

Страница 4: ...T834B T834C T834J HEATING COOLING THERMOSTATS H1 Fig 8 Internal schem atic and typical hookup for T834C with terminal for defrost relay in heat pump system FAN 69 0444 10 4 ...

Страница 5: ...nd typical hookup for T834B in standard heating cooling system with no fan switching H1 A Fig 11 Internal schem atic and typical hookup for T834B in heating cooling system with zone valve Fig 12 Internal schem atic and typical hookup for T834J cooling only system 5 69 0444 10 ...

Страница 6: ...scale Thesam elevercontrols bothheatingandcooling O nmodelswithtem perature rangestops temperaturesettinglevercanbemovedonly betweenthetwotemperaturerangestops HEAT ANTICIPATOR SETTING IMPORTANT The T834 Thermostat has an adjustable heat anticipator and will operate properly ONLY IF THEANTICIPATOR IS ADJUSTED TO MATCH THE CURRENT DRAW OF THE PRIMARY CONTROL Use this thermostat only on systems with...

Страница 7: ...on inresponsetoacall for heatingorcooling Cooling A CAUTION Damage to Compressor Possible Operating at too low of an outdoor temperature may cause compressor damage D onot operatecoolingifoutdoortem perature is below50 F 10 C Refertomanufacturer recom m endations NOTE Toprevent compressorshortcycling am inim um off tim er maybeincludedtoprovideafive minute tim edelaybeforeactivatingthecompressoraf...

Страница 8: ...ersoit doesnot m ove reinsertwrenchandcarefullyturn counterclockwise until themercuryrollsto theleftendof thetubebut nofarther 6 Recheckcalibration Set thermostat system switchfordesiredoperationandreplacecover COIL SHOWN WITHOUT HEAT ANTICIPATOR If recalibrationappearsnecessary proceedasfollows 1 Placethetem peraturesettingleverat thesam e settingasthethermometer Removecover 2 Insert Honeywell pa...