Honeywell T8034C Скачать руководство пользователя страница 5

69-1598

5

T8034C HEATING/COOLING THERMOSTATS

Fig. 9. Heat Pump Wiring for T8034C.

SETTING AND ADJUSTMENT

System and Fan Switching

The T8034C features SYSTEM and FAN switches for
control of the heating-cooling and fan systems.

The SYSTEM switch controls system operation as follows:

HEAT: Only heating system operates.
OFF: Both heating and cooling systems are off.
COOL: Only cooling system operates.

The FAN switch controls fan operation as follows:

AUTO: In standard systems, fan operates in response

to the thermostat in cooling;  fan operates in
response to the plenum fan control in heating. In
heat pump or electric heat systems, the fan operates
in response to the thermostat in heating and cooling.

ON: The fan runs continuously.

To switch positions, slide the lever to the desired position.
Place the switch lever directly over the desired indicator
mark for proper circuit operation.

Heat Anticipator Setting

IMPORTANT

The T8034C Thermostat has an adjustable heat
anticipator and operates properly ONLY IF THE
ANTICIPATOR IS ADJUSTED TO MATCH THE
CURRENT DRAW OF THE PRIMARY CON-
TROL. Use this thermostat only on systems with
current draws that fall within the range of the heat
anticipator. Do not use this device on Powerpile
(millivolt) systems.

A current rating is usually stamped in the nameplate of the
primary control. Set the adjustable heat anticipator
indicator to match the value given on the nameplate.

H1

TEMP. FALL

C1

1

POWER SUPPLY. PROVIDE DISCONNECT 
MEANS AND OVERLOAD PROTECTION 
AS REQUIRED.

HEAT RELAY

FAN RELAY

FAN SWITCH

ON

AUTO

COOL

OFF

HEAT

COOL

OFF

HEAT

SYSTEM
SWITCH

C1
ANTICIPATOR

H1 
ANTICIPATOR

M13313

B

O

W

Y

G

R

L1 
(HOT)

L2

1

CHANGEOVER
RELAY (HEAT)

CHANGEOVER
RELAY (COOL)

COMPRESSOR
RELAY

5

4

If the current rating is not available:

1.

Turn off the power.

2.

Wire the thermostat, but do not mount it on the wall.

3.

Connect an ammeter between the W wire and W
terminal on the thermostat (in series with the primary
control).

4.

Prepare the system for operation.

5.

Turn on the power.

6.

Turn the system switch to heat.

7.

Increase the thermostat setpoint as necessary to get
the system operating.

8.

With the system operating through the ammeter,
wait one minute, then read the ammeter.

9.

Turn the system switch to OFF, and turn off the
power.

10.

Adjust the heat anticipator to match the reading on
the ammeter.

11.

Disconnect the ammeter, reconnect the W wire, and
mount the thermostat. Continue with system
checkout.

The heat anticipator could require further adjustment for
best performance. To lengthen the burner-on time, move
the indicator in the direction of the 

longer

 arrows—not

more than one-half scale marking at a time. To shorten the
burner-on time, move the indicator in the opposite
direction.

Most one-stage heating equipment is designed to operate
at five to six cycles per hour, at 50 percent load conditions.
When using a T8034 Thermostat in heat pump systems,
set the heat anticipator at 140 percent of the actual
primary control current draw to reduce the cycling rate.
Most heat pump systems should cycle 2-1/2 to 3 times per
hour.

Содержание T8034C

Страница 1: ...eck the ratings given in the Instructions and on the product to make sure the product is suitable for your application 3 Installer must be a trained experienced service technician 4 After installation is complete check out product operation as provided in these Instructions CAUTION Can cause electrical shock or equipment damage Disconnect power supply before beginning installation Location Locate ...

Страница 2: ... and discard the foam plastic shipping insert that protects the switch and bimetal assembly during shipping 5 Set the adjustable heat anticipator indicator to match the current draw of the primary heating control see Heat Anticipator Setting 6 Push excess wire back through the hole and plug any opening with insulation to prevent drafts that may affect thermostat performance 7 Loosely fasten the th...

Страница 3: ...N AUTO COOL OFF HEAT COOL OFF HEAT SYSTEM SWITCH C1 ANTICIPATOR H1 ANTICIPATOR M1034F W 2 1 Y G R Fig 5 Internal schematic and typical hookup for T8034C in gas or oil fired or central electric heat systems M2297 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED DEFROST RELAY SYSTEM SWITCH HEAT OFF COOL FAN SWITCH AUTO ON H1 TEMP FALL C1 ANTICIPATOR FAN RELAY HEAT OFF COOL C...

Страница 4: ...ONNECTED THERMOSTAT WITH NOT ENERGIZE FAN IN AUTO POSITION JUMPER W Y FOR SINGLE STAGE HEAT PUMP APPLICATIONS HEAT RELAY FAN RELAY FAN SWITCH ON AUTO COOL OFF HEAT COOL OFF HEAT SYSTEM SWITCH C1 ANTICIPATOR H1 ANTICIPATOR M2323C W Y B O 2 G 1 R CHANGEOVER RELAY HEAT CHANGEOVER RELAY COOL COMPRESSOR RELAY Fig 8 Internal schematic and typical hookup for T8034C in single transformer heating cooling s...

Страница 5: ... C1 1 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED HEAT RELAY FAN RELAY FAN SWITCH ON AUTO COOL OFF HEAT COOL OFF HEAT SYSTEM SWITCH C1 ANTICIPATOR H1 ANTICIPATOR M13313 B O W Y G R L1 HOT L2 1 CHANGEOVER RELAY HEAT CHANGEOVER RELAY COOL COMPRESSOR RELAY 5 4 If the current rating is not available 1 Turn off the power 2 Wire the thermostat but do not mount it on the wal...

Страница 6: ... With the system switch set at OFF and the fan switch at ON the fan should run continuously Move the fan switch to AUTO In standard systems fan operation is controlled by the plenum fan control in heating and by the thermostat in cooling In heat pump or electric heat systems fan operation is controlled by the thermostat in heating and cooling Recalibration These thermostats are calibrated at the f...

Отзывы: