background image

T7984 A,B,C ELECTRONIC MODULATING CONTROL THERMOSTATS 

Output 2 On/Off (T7984B only) 

A 24 Vac on/off output which is normally used to control terminal 

reheat in a zoned system. Example: electric base board relay, 

electric duct heater relay, perimeter on/off 24 Vac valve, etc. 

This output can also be used for cooling applications with the 

mode jumper installed (See the control curves for T7984B) 

There is a status LED mounted internally that indicates the 

action of the output. The red LED indicates that the output 

electronic contact (triac) is energized. 

This electronic contact (triac) is rated at 1.1A max. in rush and 

0.5A running. This electronic contact (triac) is protected with a 

PTC self-resetting fuse. In the event of an overload or a short 

circuit, the PTC self-resetting fuse will reduce the load to a 

very low level. If the power is removed or the overload or the 

short disappears, the PTC fuse will return to its normal state 

and allow normal operation. 

CPH (Cycles per Hour) 

It is possible to fix the number of time per hour the reheat end 

device will be energized. Those settings are adjusted with DIP 

switch (S1). 

Two different settings are possible: 

4 cycles per hour or 8 cycles per hour 

Use the following setting for the following reheat device applications: 

Table 5. Cycle settings for reheat device applications 

4 cycles per hour 

8 cycles per hour 

Anything using a gas fired or 

oil fired terminal reheat device 

N.C. 24 Vac thermal valve 

(Hot wax thermal body valve) 

Any gear driven end device 

valve or damper actuator 
Properly sized electric base 

board strip 

Oversized capacity electric 

base board strip 

Properly sized electric duct 

heater 

Oversized capacity electric 

duct heater 

Output 2, Modulating Analog Output 2 to 

10Vdc (T7984C only) 

A modulating signal that uses a variable Vdc signal for the 

control of analog valve actuator or SCR power controller 

which is normally used to control terminal reheat in a zone 

system. 

This type of output on the T7984C uses a half wave rectifier 

bridge. If the same transformer is to be used for the 

thermostat and the end device, be sure to select end devices 

which also use a half wave rectifier bridge. 

There is a status LED mounted internally that indicates the 

action of the output. The red LED intensity is proportional to 

CHECKOUT 

Service LED 

All thermostats have internal service LED & a system status 

Led on the cover. The internal service LED are colored lights 

that can be viewed from the side of the thermostat they are 

energized and the system status LED is the one mounted on 

the cover. (See the checkout & start up procedures section.) 

Table 6. System Status LEDs 

Thermostat operation can be confirmed with the System 

status LED on the thermostat cover. 

Model 

Color 

Explanation 

T7984A 

green  High intensity = Demand for cooling or 

heat. 

Low = no demand. 

T7984B,C  red 

Flashing = Night setback/set-up 

activated. 

Table 7. Internal Service LEDs 

C  Color 

Indication when 

• 

• 

• 

green  Intensity is proportional to output 1 

• 

red 

On/off output 2 is closed (load 

energized) 

• 

red 

Intensity is proportional to reheat 

output 

Test Condition: 

1.

  

No contact changeover input and changeover sensor 

disconnected. No wire on mode input. 

2.

  

T7984B & C: set DIP switch S3 and S4 to —ON“ position 

to remove 75°F (24°C) limitation. 

3.

  

Room termperatures must be between 60-80°F. 

Table 8. Knob position 

Rotate Knob to:  Green 

Red (reheat models only)

T7984B & C 

Minimum Position  ON 

OFF 

Maximum Position  OFF 

ON 

The night setback feature can be temporarily overridden for 2-

1/2 hours by depressing the override button on the thermostat 

cover. 

the action of the output. 

Automation and Control Solutions 

Honeywell International Inc. 
1985 Douglas Drive North 
Golden Valley, MN  55422 
customer.honeywell.com 

Honeywell Limited-Honeywell Limitée 
35 Dynamic Drive 
Scarborough, Ontario  M1V 4Z9 

® U.S. Registered Trademark 
© 2005 Honeywell International Inc. 
95C-10815–2    M.S.  Rev. 09-05 

Содержание T7984 A

Страница 1: ...lve actuators such as ML7285 ML7421 VC7930 or M7410 All models feature user friendly set point knob All models feature output status LEDs for installer check out Locking cover and range stops are standard Night setback models feature selection of two different offset temperatures and use central time switch control Night setback models feature 2 1 2 hour local timed override Heat cool models featu...

Страница 2: ...lization SETPOINT RANGE 55 90 F 13 32 C T7984A Heating 55 75 F 13 24 C T7984B C Cooling 75 90 F 24 32 C T7984B C ORDERING INFORMATION The maximum heating setpoint and minimum cooling setpoint is electronically limited to 75 F 24 C REMOTE SENSOR 47 kΩ NTC thermistor part nos 272845 and 272847 ANALOG OUTPUT 2 to 10 Vdc 2 mA max SWITCHED OUTPUT RATING 0 5A running 1 1A inrush 24Vac protected with sel...

Страница 3: ...hermostats must be configured for proper operation by setting DIP switches T7984B Reheat output control action 7 5 or 15 minutes T7984B C Zero energy band ZEB 3 F 2 C or 5 F 3 C Setpoint adjustment cooling centred heating centred with limit override for commissioning Night setback amount see Table 2 for complete listing of option settings T7984A B C Main sensor internal or remote Table 3 T7984 DIP...

Страница 4: ...act or the changeover sensor across Fig 2 T7984A Wiring Input 2 10 Vdc 24 Vac Common 2 10 Vdc valve or VAV analog actuator Duct or Room Not used Remote sensor input 0 Vac Output 1 2 10 Vdc Changeover input for Out 1 Changeover contact OR Changeover sensor 24 Vac Power supply 0 Vac 24 Vac Transformer SEQUENCE SETPOINT DIAL CENTERED End Heating mode End Opened Cooling mode Device Device changeover 1...

Страница 5: ... Device closed off 2 Vdc 0 OUTPUT 2 ON OFF OUTPUT 1 ANALOG ZERO ENERGY BAND Temperature increase Fig 6 T7984B Sequence Mode A DIP SWITCH SETTINGS DEFINITION S3 S4 75 F OVERRIDE 1 1 HEATING DIAL 0 1 COOLING DIAL 1 0 CENTERED HC 0 0 SETPOINT DIAL DEFINITION ZEB S2 5 F 3 C 3 F 1 5 C 1 0 ZERO ENERGY BAND CYCLES HOUR S1 FAST 8 CPH 1 SLOW 4 CPH 0 OUTPUT 2 ON OFF CPH ON 1 1 2 3 4 5 6 OFF 0 COOLING SETPOI...

Страница 6: ... valve or VAV analog actuator 24 Vac Transformer Fig 9 T7984C Wiring SEQUENCE SETPOINT DIAL DEFINITION SETPOINT DIAL DEFINITION SETPOINT SETPOINT HEATING COOLING HEATING COOLING SETPOINT CENTERED SETPOINT SETPOINT CENTERED End End Device closed 2 Vdc IN ZERO ENERGY BAND OUTPUT 2 ANALOG OUTPUT 1 ANALOG SETPOINT End IN ZERO End End Device Device 100 ENERGY BAND 100 Device Device opened 10 Vdc 50 End...

Страница 7: ...model on how to wire the sensor The remote sensor are not to be used for supply control applications Zero Energy Band T7984B C Thermostats which have cooling and heating outputs T7984B C have 2 distinct setpoints one for heating the other for cooling see the control curves section for each model When the room temperature is between these to setpoints both heating and cooling outputs are off and th...

Страница 8: ...ctuator or SCR power controller which is normally used to control terminal reheat in a zone system This type of output on the T7984C uses a half wave rectifier bridge If the same transformer is to be used for the thermostat and the end device be sure to select end devices which also use a half wave rectifier bridge There is a status LED mounted internally that indicates the action of the output Th...

Отзывы: