T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
25
62-0254—13
Fig. 58. Setup - Outputs - Options - Schedule.
2.3.3.1. USE SCHED
1.
Press the
button to display the schedule
selections.
2.
Use the
and
buttons to highlight YES or NO.
Default: NO
3.
Press the
button to accept the value and display
the MIN OFF option.
Selecting NO disables scheduling for
all
outputs.
Selecting YES enables scheduling for
all
outputs. When
YES is selected, all individual outputs default to follow the
schedule. However, each individual output can be
removed from scheduling as desired.
With Scheduling enabled, when you return to Program
mode, the new option for Scheduling displays. You can
press the home key and then the menu key to view the
Schedule options in the menu.
See “2.3.1.5. SCHEDULE” on page 23.
Fig. 59. Setup - Outputs - Options - Min Off/On Time.
2.3.3.2. MIN OFF or MIN ON
This is the minimum number of seconds of “off time” or
“on time” for
all
relays.
1.
Press the
button to display the Min Off/On value.
2.
Use the
and
buttons to increase/decrease
the desired number of seconds from 0 to 990 sec-
onds in 10 second increments.
Default: 0 (zero)
Range: 0 to 990 seconds
3.
Press the
button to accept the seconds and
display the DI OPTIONS.
NOTES:
1.
The minimum OFF or ON time applies to
all
relay outputs.
2.
When minimum OFF or ON time is active,
relays waiting to be energized display a
flashing square underneath the relay number
on the home screen.
3.
If the minimum OFF time is not equal to zero
(0), the minimum OFF time activates at
power-up. To manually override, press the
button at any time.
SETUP
OUTPUTS
OPTIONS
USE SCHED
SETUP
OUTPUTS
OPTIONS
USE SCHED
USE
SCHEDULE
FOR
OUTPUTS
YES
NO
M24521
SETUP
OUTPUTS
OPTIONS
ENTER
MINIMUM
OFF TIME
FOR RELAYS
SETUP
OUTPUTS
OPTIONS
MIN OFF
0
SEC
M24522A
OR
MIN ON
ENTER
MINIMUM
ON TIME
FOR RELAYS
SETUP
OUTPUTS
OPTIONS
MIN ON
0
SEC
MIN OFF