T7560A,B,C Digital Wall Module

INSTALLATION INSTRUCTIONS

CAUTION

: This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in

accordance with the Installation Instructions, may cause interference with radio communication. It has been tested and
found to comply with the limits for a Class A computing device pursuant to Subpart J of Part 15 of FCC Rules, which are
designed to provide reasonable protection against such interference when operated in a commercial environment.
Operation of this equipment in a residential area is likely to cause interference, in which case, users at their own expense
will be required to take whatever measures may be required to correct the interference. Any unauthorized modification of
this equipment may result in the revocation of the owner’s authority to continue its operation.

BEFORE INSTALLATION

All wiring must comply with local electrical codes and
ordinances or as specified on installation wiring diagrams.
Digital Wall Module (DWM) wiring can be sized from 16 to 22
AWG (1.5 to 0.34 mm

2

), depending on the application. The

maximum length of wire from a device to a wall module is
164 ft (50 m). Twisted pair wire is recommended for wire runs
longer than 100 ft (30.5 m).

 CAUTION

EMI Noise Introduction.
Risk of erratic system operation.

Keep wiring at least one ft (305 mm) away from large
inductive loads such as motors, line starters, lighting
ballasts and large power distribution panels. During
installations, try to avoid areas of high EMI noise.
Run wall module wiring separately from 50 Vac or
greater power wiring.

Table 1. Types of DWM.

Sensor

1

Setpoint

Bypass

Fan

Override

T7560A

Tmp

wheel

button

button

T7560B

Tmp/Hum

wheel

button

button

T7560C

Tmp/Hum

-

-

-

Tmp = Temperature sensor; Hum = Humidity sensor

Table 2. Controller SW requirements for powering via

terminal 5 and new LCD signaling.

Fan Coil Unit

W7752

Hydronic

W7762

Chilled Ceiling

W7763

1.00.04

1.00.03

1.00.03

NOTE:

A software module (ModAL module GNRSC02A) is
available to adapt the wall module to the respective
Excel 20, 50, 80, 100, 500, 600 controller, making
any further configuring obsolete. Contact your local
Honeywell distributor for further details.

DWM DISASSEMBLY

The T7560A,B,C comes packed with a subbase that mounts
separately for ease of installation. The cover is fixed by a
latch on the underside of the unit. Remove the cover as
shown in Fig. 1 (T7560A,B) or Fig. 2 (T7560C):

1.  

Insert the tip of an awl or a similar narrow, pointed
object into the small hole in the latch (T7560A,B) or
simply depress the latch by hand (T7560C).

2.  

Pry off the cover.

Fig. 1. DWM disassembly (T7560A,B)

Fig. 2. DWM disassembly (T7560C)

Содержание T7560A

Страница 1: ...t 50 m Twisted pair wire is recommended for wire runs longer than 100 ft 30 5 m CAUTION EMI Noise Introduction Risk of erratic system operation Keep wiring at least one ft 305 mm away from large inductive loads such as motors line starters lighting ballasts and large power distribution panels During installations try to avoid areas of high EMI noise Run wall module wiring separately from 50 Vac or...

Страница 2: ...ers listed in Table 2 and if a SW version listed in Table 2 or higher is installed If the DWM is powered via terminal 5 the Excel 10 controller must be configured for LCD_DISPLAY LED output continuously ON NOTE The 24 Vac power supply is needed only with the T7560B DWM for the humidity sensor Alternatively a DC voltage source with 5 12 V can be connected to terminal 5 see IMPORTANT note above Alte...

Страница 3: ...ring of DWM NOTE If connected to W7753 UV Controller both terminals 4 and 6 must be connected W7761 Remote I O Controller supports only terminals 2 temperature 7 humidity and 1 common as well as terminal 8 as voltage supply Wiring with terminal 8 is not necessary if An FCU or CHC controller with software is connected see table 2 An Excel 500 with 6V 8V 10V signaling from the controller is used The...

Страница 4: ...ameter value 6 Confirm selection by pressing UNIT ENABLE 7 Repeat steps 4 to 6 to configure next parameter or press BYPASS to leave the configuration mode NOTE After approx 10 seconds without further action the DWM automatically falls back to normal mode P1 Setpoint Type Setting Scale Type Setting Fahrenheit relative Fahrenheit absolute Centigrade relative Centigrade absolute P2 Room Temperature S...

Страница 5: ...cupied 01 enable FAN Key enable Setpoint Key 02 enable FAN Key disable Setpoint Key 03 disable FAN Key enable Setpoint Key 04 disable FAN Key disable Setpoint Key To disable means to switch back to FAN auto Setpoint offset zero and disable operation To enable means to make normal operation possible no action if unoccupied Unoccupied means Effective Unoccupied moon on continuously or Override Unocc...

Страница 6: ... connected to the 2 LON terminals Via the 3 5 mm jack plug a PC connection can be established Order quantity set with 5 pieces Fig 9 T7460LONJACK Mounting Remove the setpoint wheel and put in the LonJack as shown in the following Fig 10 Mounting T7460 LONJACK T7560 Blinds Same material and color as housing for covering non operational buttons Order quantity set of 50 pieces ...

Страница 7: ...T7560A B C DIGITAL WALL MODULES 95 7620 4 EN1B 0146GE51 R0303 7 ...

Страница 8: ...d Control Solutions Honeywell AG Böblinger Straße 17 D 71101 Schönaich Phone 49 7031 63701 Fax 49 7031 637493 http europe hbc honeywell com Subject to change without notice Printed in Germany Manufacturing location certified to EN1B 0146GE51 R0303 95 7620 4 ...

Отзывы: