T7460A,B,C,D,E,F WALL MODULES – INSTALLATION INSTRUCTIONS 

EN1B-0291GE51 R0718B 

1-3/16

(30)

1-1/16

(27)

SEN

SO

R

SET

 PT

BYP

/F

AN

LED

BYP

/R

TN

LED

/R

T

N

CO

M

1:W7750

  W7751

  W7752

  W7762

  W7763

2:W7753

3:XL500

JUMPER

A  B

2-3/8

(60)

3-7/16

(86)

4-1/8
(104)

4

(100)

2-11/16 (68)

3-7/8 (98)

3-15/16 (99)

Auto

0

1 2 3

 

Fig. 3. T7460A,B,C,D,E,F dimensions in in. (mm) 

 

Mounting Procedure 

1.

  Disassemble the cover as is shown in Fig. 1. 

2.

  (T7460B,C,D,E,F, only) Remove the setpoint dial by 

pulling it off. 

3.  a)

 Mount the wall module onto the wall outlet box, or 

b) 

bore wall holes as is specified in Fig. 2 and mount the 

wall module with appropriate screws. 

4.

  Connect the wires to the terminal block according to the 

specifications in section “Wiring”. 

5.

  (T7460B,C,D,E,F only) With the double-D hole of the 

potentiometer in the "12 o'clock" orientation (see Fig. 4), 
hold the setpoint dial such that the "21" (Celsius absolute 
scale) or "0" (Celsius relative scale) is at the "3 o'clock" 
position and then insert the dial into the hole. 

  W7762

2:W7753

3:XL500

  W7762

2:W7753

3:XL500

12

12 1

2

15

18

21

24

27

30

+

5

-4 -3

-2

-1

0

+3

-5

+

4

+2

+1

3 O‘CLOCK 

POSITION

12 O‘CLOCK 

ORIENTATION

12 O‘CLOCK 

ORIENTATION

3 O‘CLOCK 

POSITION

 

Fig. 4. Mounting position of setpoint dial 

6.

  Remount the cover as depicted in Fig. 5 and make sure 

that the tab on the underside engages. 

 

 

Fig. 5. Mounting cover of T7460 wall modules 

 

Wiring 

Attach the wires from the device sensor terminals to the 
appropriate wall module terminals and set the jumpers 
according to the connected controller. See Fig. 7 through Fig. 
6. 

IMPORTANT 

Screw type terminal blocks are designed to accept 
no more than one 16 AWG (1.5 mm

2

) conductor. 

Wire the terminal blocks as follows: 

1. 

Strip 3/16 in. (5 mm) of insulation from the conductor. 

2.

  Insert the wire in the required terminal location and tighten 

the screw to complete the termination. 

3.

  Verify jumper setting with Fig. 6 and wall module wiring 

with Fig. 7 and Fig. 8. 

 

Содержание T7460B

Страница 1: ...exposure to the average zone temperature NOTE Maintain a mounting clearance of approx 4 in 10 cm to the left hand side of the module in order to allow a free airflow for the temperature sensor and accessibility of the setpoint dial Do not mount the wall modules on an outside wall on a wall containing water pipes or near air ducts Avoid locations that are exposed to discharge air from registers or ...

Страница 2: ...he 21 Celsius absolute scale or 0 Celsius relative scale is at the 3 o clock position and then insert the dial into the hole W7762 2 W7753 3 XL500 W7762 2 W7753 3 XL500 12 12 1 2 1 5 18 21 24 2 7 3 0 5 4 3 2 1 0 3 5 4 2 1 3 O CLOCK POSITION 12 O CLOCK ORIENTATION 12 O CLOCK ORIENTATION 3 O CLOCK POSITION Fig 4 Mounting position of setpoint dial 6 Remount the cover as depicted in Fig 5 and make sur...

Страница 3: ... AI GND 24 AI GND altern to SETPT LED 10 Vdc 3mA permanent 5 XF822 1 AO XF522 1 AO XFL522 1 AO 37 AO 15 AO 12 AO 19 AO LED RTN 0Vdc LED OFF 10Vdc LED ON 7 XF822 2 AO XF522 3 AO XFL522 2 AO 38 AO 17 AO 13 AO 17 AO NOTE In the case of Excel 10 12 wiring please refer to the respective Excel 10 12 Installation Instructions NOTE In the case of the T7460A B C bypass signaling is via digital input In the...

Страница 4: ...0C E F WALL MODULE IN CONJUNCTION WITH THE EXCEL 10 UV CONTROLLER W7753 CONNECT TERMINAL 6 BYP RTN WITH THE CONTROLLER S BYPASS INPUT IMPORTANT THE GRAY SHADED TERMINALS ARE INTERNALLY CONNECTED THE WHITE UNSHADED TERMINALS ARE NOT INTERNALLY CONNECTED Wiring of Modules SENSOR SET PT COM T7460D T7460E 5 6 7 1 2 3 4 5 6 7 1 2 3 4 5 6 7 1 2 3 4 5 6 7 1 2 3 4 T7460F T7460C BYP FAN LED BYP RTN LED RTN...

Страница 5: ... IN POS 2 Fig 10 Circuitry of T7460C D E F Wall Modules ACCESSORIES T7460 LONJACK The T7460 LONJACK is a small board allowing easy access to LONWORKS or BACnet via the correspondingly wired wall module apply appropriate wiring guidelines for LONWORKS or BACnet networks as the case may be The T7460 LONJACK provides an additional 3 5 mm jack socket for a 3 5 mm jack plug Order quantity set with 5 pi...

Страница 6: ... Energy Solutions Division of Honeywell Technologies Sàrl Rolle Z A La Pièce 16 Switzerland by its Authorized Representative Home and Building Technologies Honeywell GmbH Böblinger Strasse 17 71101 Schönaich Germany Phone 49 0 7031 637 01 Fax 49 0 7031 637 740 http ecc emea honeywell com EN1B 0291GE51 R0718B ...

Отзывы: