Honeywell T7351 Скачать руководство пользователя страница 13

T7351 COMMERCIAL PROGRAMMABLE THERMOSTAT

13

63-2666—02

T7351 Relay Logic

All T7351 model thermostats contain at least four switching 

relays. In conventional applications, the relays control first 

stage cooling, first stage heating, fan, and auxiliary. In heat 

pump applications, the relays control the heat pump 

compressor, changeover, fan, and emergency heat.

O/B Terminal for Heat or Cool 
Changeover

The O/B terminal controls heat pump changeover. The default 

operation is for the terminal to be powered when calling for 

heat (or while the most recent call was for heat). This 

corresponds to a typical B terminal.

NOTE: The O/B terminal can be configured to operate as a 

typical O terminal (powered on call for cool).

Emergency Heat 

With the system set for 

Em Heat

, auxiliary heat serves as 

stage one; compressor stages are locked off. The fan cycles 

with the auxiliary heat.

Equipment Protection

As part of the operational sequence, the T7351 

microprocessor incorporates cycle rate, and minimum on and 

off times for all heating and cooling stages. This extends 

equipment life as it prevents rapid cycling of equipment.

NOTE: Minimum on and off times are fixed.

Cycle Rates

The thermostat control algorithm maintains the temperature by 

cycling stages of heating or cooling to meet setpoint. Cycle 

rates, in cycles per hour (cph) are set in the installer setup.

NOTE: Defaults are: heat: 6cph, cool: 3cph.

P+I+D Control

The T7351 microprocessor-based control requires that the 

user understands temperature control and thermostat 

performance. A conventional electromechanical or electronic 

thermostat does not control temperature precisely at setpoint. 

Typically, there is an offset (droop) in the control point as the 

system load changes. This is a phenomenon that most people 

in the industry know and accept.

IMPORTANT

• P+I+D (Loop Tuning) parameters are optimized for 

proper operation of a vast majority of HVAC systems. 

Only when completely certain of necessary and 

proper changes should you alter these values.

• Improper changes result in poor system performance 

and equipment problems such as compressor short 

cycling. Other problems include wide swings in space 

temperature and excessive overdriving of modulating 

outputs.

All adjustments to Loop Tuning parameters should be gradual. 

After each change, allow the system to stabilize to accurately 

observe the effects of the change. Then, as needed, make 

further refinements until the system operates as desired.

If adjustment of PID parameters is required, use the following:

NOTE: In the items that follow, the term “error” refers to the 

difference between the measured space temperature 

and the current actual space temperature setpoint:

— The 

Throttling Range (TR)

, also called Proportional Gain, 

determines the impact of the error on the output signal. 

Decreasing TR amplifies the error effect; that is, for a given 

error, smaller TR causes higher output signal.

— The 

Integral Time (IT)

, also called Integral Gain, 

determines the impact of the error-over-time on the output 

signal. Error-over-time has two components making up its 

value: amount of time the error exists; and size of the error. 

The higher the IT, the slower the control response. In other 

words, a decrease in IT causes a more rapid change to the 

output signal.

— The 

Derivative Time (DT)

, also called Derivative Gain, 

determines the impact of the error rate on the output signal. 

The error rate is how fast the error value changes. It can 

also be the direction the space temperature is going, either 

toward or away from the setpoint, and its speed—rapid or 

slow. A decrease in DT causes, for a given error rate, a 

greater effect on output signal.

Recovery Ramping Logic

The T7351 incorporates a ramping feature that gradually 

changes the space setpoints. During recovery operation, the 

setpoint changes at a rate in degrees per hour depending on 

the outdoor air temperature. If there is no outdoor air 

temperature sensor available, the minimum ramp rate is used.

When recovering in heating, the control point raises gradually, 

maximizing the use of the more economical first stage heat to 

bring the sensed temperature to the desired comfort setpoint. 

This minimizes using the typically more expensive later 

stage(s) of heat.

NOTE: See Fig. 10 for a pictorial representation of the heat 

ramp rate determination.

Recovery Ramping for Conventional 
Systems

Fig. 10. Heat Setpoint Ramping for Conventional Systems.

NOTES:

HEAT RECOVERY 
RAMP RATE
(DEGREES/HOUR)

MaxHtRamp

MinHtRamp

OaTempMinHtRamp

OaTempMaxHtRamp

OUTDOOR AIR
TEMPERATURE

M10109A

Содержание T7351

Страница 1: ...lled water systems 365 day programming Two Occupied and two Not Occupied periods per day Individual heat and cool setpoints available for Occupied and Not Occupied periods P I D control minimizes temperature fluctuations Recovery ramp control automatically optimizes equipment start times based on building load Convenient overrides allow temporary setpoint changes Keypad multi level lockout availab...

Страница 2: ...ximum of two heat stages and two cool stages Mounting Means Mounts on subbase Subbase Mounts On Wall Using two 5 8 in long 6 32 screws included Outlet Box Using sheet metal screws Clock Accuracy at 77 F 25 C 1 min month 30 days Minimum Stage Operation Time fixed Minimum On Heat 1 minutes Cool 3 minutes Minimum Off Cool and Heat Pump 1 minute Electrical Ratings Power 24 Vac 50 60 Hz 20 to 30 Vac 50...

Страница 3: ...y Disconnect power supply before installation IMPORTANT All wiring must agree with applicable codes ordinances and regulations MERCURY NOTICE If this control is replacing a control that contains mercury in a sealed tube do not place your old control in the trash Dispose of properly Contact your local waste management authority for instructions regarding recycling and the proper disposal of an old ...

Страница 4: ...s thermostat mounting orientation does not matter Wall mounting using standard drywall screws is standard Mounting to a 2 in 50 8 mm by 4 in 101 6 mm wiring box can be accomplished for a horizontal box no extra hardware is required for a vertical box part 209651A is required Mount to European standard wall box 2 4 in having 61 mm between mounting screws in a horizontal line with or without adaptiv...

Страница 5: ...OLES MOUNTING SCREWS Table 3 T7351 Subbase for Three stage Heat Three stage Cool Systems Terminal Description Conventional Heat Pump RCa RCa 24 VAC Cooling transformer RHa RHa 24 VAC Heating transformer X X Common aux aux Auxiliary relay W1 O B Conventional Stage 1 heating relay Heat Pump Changeover relay for heating B or cooling O b W2 W1 Conventional Stage 2 heating relay Heat Pump 1st Stage aux...

Страница 6: ...ature Refer to Table 2 for the default temperature setpoints See Programming section for complete instructions on changing the setpoints Setting System and Fan System default setting is Auto Fan default setting is On NOTE Use System and Fan keys to change settings System Settings Auto Thermostat automatically changes between heating and cooling based on indoor temperature Cool Thermostat controls ...

Страница 7: ...T7351 firmware version number 3 To return to a Setup item cycle through the options 4 To change a setting use the up or down key 5 To exit the Installer Setup press Run Schedule 6 Display prompts SAV CFG save configuration Table 4 T7351 Intelligent Fan ON control logic Occupancy Call for Heat Cool Notes Scheduled Period Motion Sensor Signal Effective Occupancy Yes No Occupied No Sensor Wired Occup...

Страница 8: ...Heat Pump Heating Energize O B on call for heat COOLSTG 1 0 4 Number of Cooling Stages 0 0 Stages of Cooling 1 1 Stages of Cooling 2 2 Stages of Cooling 3 3 Stages of Cooling Not available if Heat Pump is selected 4 4 Stages of Cooling W3 will be used as 4th stage relay Not available if Heat Pump is selected HEATSTG 1 0 3 Number of Conventional Heating Stages Not available if Heat Pump is selected...

Страница 9: ... Deg F 1 1 Deg F 2 2 Deg F 3 3 Deg F 4 4 Deg F 5 5 Deg F TMP OCC 3 1 8 Temporary Occupied Duration 1 to 8 hours TMP CAL 0 4 3 Temporary Display Adjustment 0 3 0 to 3 DDF 4 7 4 to 1 DDF MINCOOL 45 F 7 C 45 99 F 7 37 C Min Cool Setpoint MAXHEAT 90 F 32 C 40 90 F 4 32 C Max Heat Setpoint HEATLCK NO YES or NO Heating Lockout Only displayed if Outdoor Air Sensor is selected NO None YES Enabled HTLCKSP ...

Страница 10: ...t 5 Reheat w Min On DEH MIN 5 5 15 Dehumidify Minutes On DEH TMP 2 1 5 Dehumidify Temp Reset MINHTRT 5 0 20 DDF HR Minimum Heat Recovery Ramp Rate MAXHTRT 8 0 20 DDF HR Maximum Heat Recovery Ramp Rate Only Displayed if Outdoor Sensor is Selected MINHTOA 0 F 18 C 20 120 F 29 49 C Minimum Heat Outdoor Air Temperature Only Displayed if Outdoor Sensor is Selected MAXHTOA 40 F 4 C 20 120 F 29 49 C Maxi...

Страница 11: ...es hold key down to continuously decrease value Also can make temporary change in temperature setpoint Information Obtains information where humidity high limit can be set cycles through setup options Up Arrow Raises setpoint day or time When setting times or temperatures hold key down to continuously increase value Also can make temporary change in temperature setpoint Temperature Occupied Heat S...

Страница 12: ... if the compressor is cycled too quickly Use the Test Mode to check the thermostat configurations and operation To start the system test 1 Press Schedule Day Occupied and Not Occupied simultaneously 2 The display gives the option to TEST a To enter test mode press up or down until the display indicates IN TEST b To cancel this option ensure display indicates NO TEST 3 Press Run Schedule NOTES To v...

Страница 13: ...ature and excessive overdriving of modulating outputs All adjustments to Loop Tuning parameters should be gradual After each change allow the system to stabilize to accurately observe the effects of the change Then as needed make further refinements until the system operates as desired If adjustment of PID parameters is required use the following NOTE In the items that follow the term error refers...

Страница 14: ...he heat mode in Fig 10 except the slope of the line reverses for cooling Fig 12 Setpoint Ramping Parameters with Ramp Rate Calculation Advantages Comfort setting is achieved at the programmed time and maintained regardless of weather conditions occupants are comfortable Drafts from low temperature discharge air are minimized during Occupied periods Use of the more economical first stage of heat is...

Страница 15: ...he auxiliary relay are hot water heaters lighting or baseboard heat The additional loads are connected to the auxiliary relay contacts on the subbase The contacts are rated for 1 5A at 30 Vac but can be adapted to higher current applications using an external relay See Fig 13 Fig 13 Using T7351 Models with an External Relay with loads greater than 1 5A Default Auxiliary Relay Operations Unless con...

Страница 16: ...is normal NOTES The heat stage never energizes during Reheat if more than one cool stage is on Reheat mode cannot occur during heating RESET TEMP SETPT The room temperature set point resets to a specified number of degrees below the actual set point when room relative humidity RH rises above humidity high limit The default value is 2 degrees Though this may not technically reduce RH it reduces the...

Страница 17: ... blown if so replace fuse Check if the HVAC equipment power switch is in the Off position if so set to the On position Check wiring between thermostat and HVAC equipment Replace broken wires and tighten loose connections If 24 Vac is present proceed with troubleshooting Temperature display is incorrect Thermostat is configured for F or C display Press both Run Schedule and Copy then reconfigure th...

Страница 18: ...ipped if so reset circuit breaker Check if system fuse is blown if so replace fuse Check if the HVAC equipment power switch is in the Off position if so set to the On position Check wiring between thermostat and HVAC equipment Replace broken wires and tighten loose connections If 24 Vac is present proceed with troubleshooting Thermostat minimum off time is activated Wait up to five minutes for the...

Страница 19: ...S OS AS AS M HC HP HS 1 L1 HOT L2 COMPRESSOR CONTACTOR 1 COMPRESSOR CONTACTOR 2 HEAT RELAY 1 FAN RELAY HEAT RELAY 2 COMPRESSOR CONTACTOR 3 HEAT RELAY 3 TR23 H REMOTE SENSOR 9 8 7 6 5 4 3 2 1 10 11 12 GND SENSOR SET PT LED BYPASS 5 5 4 ECONOMIZER POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED ENSURE TRANSFORMER IS SIZED TO HANDLE THE LOAD HEAT COOL SYSTEMS WITH ONE TRANSF...

Страница 20: ...D WHEN INSTALLED ON A SYSTEM WITH TWO TRANSFORMERS REMOVE THE FACTORY INSTALLED JUMPER USE ECONOMIZER INSTRUCTIONS FOR INSTALLATION DIRECTIONS WHEN USING THE TR23 H FOR HUMIDITY SENSING THERE IS NO NEED TO WIRE THE HC TERMINAL BECAUSE THE T3 TERMINAL IS INTERNALLY TIED TO HC WHICH IS ALSO TIED TO TERMINAL 1 COMMON AT THE SENSOR 1 M29323 2 2 3 4 4 RC X SUBBASE O B G Y1 W1 W2 Y2 AUX RH T5 T6 T7 T4 T...

Отзывы: