62-0124—3

7

T7300E SERIES 2000 COMMERCIAL MICROELECTRONIC HEAT PUMP THERMOSTAT

Thermostat Information

1. Press the Heat/Cool Settings key to access the

thermostat information.

M4934

2. Press the increase

 ▲

 

key to display the production

date code. The first two large digits are the month
and the third digit is the last digit of the year.
(Example: 036 = March 1996)

M4931

3. Press the increase

 ▲

 

key again to display the

software identification code.  (Example: 02 =
software ID code 2)

M4932A

4. Press the increase

 ▲

 

key again to display the

software revision number.  (Example: 001 = revision
number 1)

M10229

5. Press the increase

 ▲

 

key again to display the

EEPROM identification code.  (Example: 314 =
EEPROM ID 314)

M4933A

6. Press the increase

 ▲

 

key again to display the

subbase identification code.  (Example: HP = heat
pump subbase)

M10290

Key to  

Press

Test

Number

Description

Key Operation System Test

Heat/Cool Settings

60   2

Change from fan to key operation system test.

Unoccupied Temp

60   0

Unoccupied Temp test number is displayed.

Occupied Temp

60   1

Occupied Temp test number is displayed.

▲   

60   3

Increase test number is displayed.

▼   

60   5

Decrease test number is displayed.

Clear Start Time

60   7

Clear Start Time test number is displayed.

Day

60   8

Day test number is displayed.

Copy

60   9

Copy test number is displayed.

Unoccupied  

Start TIme

60   10

Unoccupied Start Time test number is displayed.

System

60   11

System test number is displayed.

Fan

60   12

Fan test number is displayed.

Set Current

Day/Time

60   14

Set Current Day/Time test number is displayed.

Run Program

60   15

Run Program test number is displayed.

Temporary

Occupied

60   16

Temporary Occupied test number is displayed.

Occupied  

Start Time

60   17

Occupied Start Time test number is displayed.

Continuous

Unoccupied

60   19

Continuous Unoccupied test number is displayed.

Table 4. Installer System Test Options (Continued).

Содержание T7300E Series

Страница 1: ...duct 1 Read these instructions carefully Failure to follow the instructions can damage the product or cause a hazardous condition 2 Check the ratings given in the instructions and on the product to make sure the product is suitable for your application 3 Installer must be a trained experienced service technician 4 After completing installation use these instructions to check out the product operat...

Страница 2: ...ic systems Installer Setup numbers are listed in Table 2 The table includes all the configuration options available A combination of key presses are required to use the Installer Setup feature To enter the Installer Setup mode press and hold the Heat Cool Settings key with both the increase and decrease keys until the first number is displayed All display segments appear for approximately three se...

Страница 3: ...e settings to confirm that they match the system Fig 4 Display of Installer Setup number and setting M10238B INSTALLER SETUP NUMBER DISPLAY COLUMN 2 OF TABLE 2 FACTORY SETTING OR OTHER CHOICE DISPLAY COLUMN 3 OR 5 OF TABLE 2 Table 2 Thermostat Installer Setup Options continued Installer Setup Number Press Unoccupied Temp key Factory Setting Other Choices Press or key to change Actual Select to cha...

Страница 4: ...sing activated Keypad lockout level keypad lockout is enabled and disabled by DIP switch 1 on back of thermostat 25 0 No lockout 1 2 3 1 Lockout all keys on thermostat except system and fan settings temporary setpoint clock and day adjustments 2 Lockout all keys except set current Day Time increase and decrease keys 3 Lockout all keys except temporary occupied set day and clock keys Duration of te...

Страница 5: ...y M4952B Set Program Set Temperature Change Time Temp Occupied Temp Unoccupied Start Time Day System Fan Copy Occupied Start Time Run Program Temporary Occupied Continous Unoccupied Set Current Day Time Clear Start Time Unoccupied Temp Heat Cool Settings Day PM Tue Set Day Time 3 Press increase or decrease until the current time is displayed NOTE Tapping the Set Current Day Time will change the ti...

Страница 6: ...ram to exit the system test The system test times out after four minutes without any key presses continued Key to Press Test Number Description Heating Equipment System Test Heat Cool Settings 10 Enter heating equipment system test 11 Stage one heat comes on The system fan is also energized 12 Stage two heat comes on Stage one heat and system fan remain on 13 Stage three heat comes on Stage one an...

Страница 7: ...s Test Number Description Key Operation System Test Heat Cool Settings 60 2 Change from fan to key operation system test Unoccupied Temp 60 0 Unoccupied Temp test number is displayed Occupied Temp 60 1 Occupied Temp test number is displayed 60 3 Increase test number is displayed 60 5 Decrease test number is displayed Clear Start Time 60 7 Clear Start Time test number is displayed Day 60 8 Day test...

Страница 8: ... Vac check if the circuit breaker is tripped reset the circuit breaker check if the system fuse is blown replace the fuse check if the power switch on the HVAC equipment is in the Off position set to the On position check wiring between thermostat and HVAC equipment replace any broken wires and tighten any loose connections If 24 Vac is present proceed with troubleshooting Temperature display is i...

Страница 9: ...s present proceed with troubleshooting Thermostat minimum off time is activated and wait indicator is displayed Wait up to five minutes for the system to respond Enter Installer Setup number 38 Reconfigure minimum off time if required System selection is not set to Heat Set system selection to Heat Cooling will not come on No power to the thermostat Check that X terminal is connected to the system...

Страница 10: ...62 0124 3 10 T7300E SERIES 2000 COMMERCIAL MICROELECTRONIC HEAT PUMP THERMOSTAT ...

Страница 11: ...62 0124 3 11 T7300E SERIES 2000 COMMERCIAL MICROELECTRONIC HEAT PUMP THERMOSTAT ...

Страница 12: ...AT PUMP THERMOSTAT Home and Building Control Honeywell Limited Honeywell Limitée 35 Dynamic Drive Scarorough Ontario M1V 4Z9 62 0124 3 L C Rev 12 98 www honeywell com yourhome Home and Building Control Honeywell 1985 Douglas Drive North Minneapolis MN 55422 4386 ...

Отзывы: