background image

T7270B1009 WIRELESS WALL MODULE 

EN1B-0241GE51 R0106C 

3

OPERATING MODE 

Selecting Functions / Adjusting Settings 

The user can select the LIGHT, SUNBLINDS, OCCUPANCY, 
or FAN functions by pressing the "

F

" button, whereupon the 

current room temperature will disappear from the LCD and be 
replaced by the corresponding function symbol. The setting of 
the selected function can then be adjusted as desired using 
the UP button and the DOWN button. 
To adjust a setting, press, as often as necessary (referred to 
as "cycling"), the "

F

" button until the symbol representing the 

desired function appears in the LCD. Once selected, this 
symbol will be displayed for 4 sec. During this time, the user 
can use the UP or DOWN buttons to adjust the setting. If 
there is no user action for more than 4 sec, the function 
symbol will disappear, and the wall module will revert to the 
default display and the default function. 
The SETPOINT OFFSET function is selected and its settings 
adjusted using the large setpoint wheel located on the right 
side of the wall module (see section "SETPOINT OFFSET 
Function" below). 
 

SETPOINT OFFSET Function 

If the SETPOINT OFFSET function is selected (by rotating 
the setpoint wheel), the current temperature setpoint offset, 
accompanied by the degree symbol and corresponding tem-
perature unit (°C or °F), will appear in the LCD. 

NOTE:

  The SETPOINT OFFSET function can be configured 

so as to be disabled whenever the user has used the 
OCCUPANCY function to manually force the 
controller into the "unoccupied" state and parameter 
P8 (see page 6) has been set to 2 or 4. In this case, 
the setpoint offset is fixed to 0.0 °. 

 

Adjusting the Setting 

The SETPOINT OFFSET function setting can be adjusted by 
rotating the setpoint wheel clockwise or counterclockwise, 
thus increasing or decreasing (respectively) the setpoint offset 
over a range of max. -5...+5 K in steps of 0.5 K. 
The setpoint offset range may be adjusted via parameter P4 
(see page 6). 

NOTE:

  A snowflake displayed in the lower right corner of the 

LCD indicates that the wall module is transmitting 
data. During transmission, the function keys are 
disabled; you will thus have to wait approx. 1 sec 
between e.g. switching a light ON and then OFF. 

 

LIGHT Function 

The LIGHT function is the default function (see section 
“Default Function” page 5). The LIGHT function can be 
selected by pressing the "

F

" button until the letters “”LI” are 

displayed in the LCD and the function indication bar

 

appears 

underneath the light symbol imprinted on the housing. 

NOTE:

  See also section "Default Function" on page 5. 

 

Controlling a Single Light Group (P6:1) 

If the wall module has been configured to control only a single 
group of lights (see section "P6: Light Groups" on page 6), the 

LIGHT function settings are performed as described in the 
following sections. 
 

Pressing the UP Button 

  Briefly pressing the UP button once turns the light group 

ON and causes the word "O

n

" to appear in the LCD. 

  Pressing the UP button for more than 2 sec turns the light 

ON and starts dimming the light group. Once 0% is 
reached, it starts brightening from 0% to 100% 
(100%…0%…100%….). In the LCD, a vertical bar next to 
the word "O

n

" moves continuously from the left to the 

right. Releasing the UP button stops the process and 
causes the LCD to revert to the default display mode. 

 

Pressing the DOWN Button 

  Briefly pressing the DOWN button once turns the light 

group OFF and causes the word "O

ff

" to appear in the 

LCD. 

  Pressing the DOWN button for more than 2 sec turns the 

light OFF and starts brightening the light group. “O

n

” is 

displayed once the brightening starts. Brightening 
continues until 100% is reached. Then it starts dimming 
from 100% to 0% (0%…100%…0%….). In the LCD, a 
vertical bar next to the word "O

n

" moves continuously 

from the right to the left. Releasing the DOWN button 
stops the process and causes the LCD to revert to the 
default display mode. 

NOTE:

  If, after dimming / brightening the light group, the 

user uses the DOWN button to turn it OFF and sub-
sequently back ON, it will be turned back ON at a 
brightness level of 100%. 

 

Controlling Two Light Groups (P6:2 and P6:3) 

Dimming / brightening is not possible if the wall module has 
been configured to control two light groups (see section "P6: 
Light Groups" on page 6). In this case, it is possible only to 
turn each group of lights ON or OFF. 
The UP and DOWN buttons can be configured by setting 
parameter P6 to 2 or 3. 

NOTE:

  The UP and DOWN buttons can also be configured 

by setting parameter P6 to 4 or 5 (special custom 
models, only). 

 

“UP” = ON and “DOWN” = OFF usage (P6:2) 

Pressing the UP Button 

Pressing the UP button will turn ON the two light groups as 
follows: 

  Pressing the UP button once turns ON light group 1, and 

the characters "O

n

 1" appear in the LCD. 

  Pressing the UP button twice turns ON light group 2, and 

the characters "O

n

 2" appear in the LCD. 

NOTE:

  The corresponding ON command is sent only after 

the UP button is finally released. Thus, only one light 
group can be turned ON/OFF at a time. 

 

Содержание T7270B1009

Страница 1: ... U S Registered Trademark EN1B 0241GE51 R0106C Copyright 2006 Honeywell Inc All rights reserved T7270B1009 WIRELESS WALL MODULE HONEYWELL EXCEL 5000 OPEN SYSTEM INSTALLATION AND OPERATING INSTRUCTIONS ...

Страница 2: ...llowing six basic functions LIGHT SUNBLINDS OCCUPANCY FAN SETPOINT OFFSET and TEMPERATURE DISPLAY TRANSMIT function NOTE The LIGHT function is the default function see also section Default Function on page 5 and Fig 2 Controls The wall module features three control buttons and a large setpoint wheel They are used in the operating mode to select individual functions and to adjust their respective s...

Страница 3: ...s LI are displayed in the LCD and the function indication bar appears underneath the light symbol imprinted on the housing NOTE See also section Default Function on page 5 Controlling a Single Light Group P6 1 If the wall module has been configured to control only a single group of lights see section P6 Light Groups on page 6 the LIGHT function settings are performed as described in the following ...

Страница 4: ... the DOWN Button Briefly pressing the DOWN button will completely lower the sunblinds in the LCD the sunblinds symbol moves downwards Briefly pressing either the UP or the DOWN button while the sunblinds are descending will stop the sunblinds and the LCD will revert to the default display Pressing the DOWN button for more than 2 sec will lower the sunblinds only as long as it remains pressed in th...

Страница 5: ...through the other function symbols Power Up Teach Commands After power up an LCD test will be carried out i e all LCD segments will be activated for approx 1 sec Fig 3 LCD test after power up After that two teach commands will be triggered Please refer to W7070A Receiver System Engineering Product Literature No EN0B 0286GE51 on how to perform a teach in A special LCD sequence t 1 then t 2 will be ...

Страница 6: ...tion becomes the default function P7 Room Temperature Correction Value With this parameter the user can correct the room tem perature value displayed in the LCD and transmitted to the W7070A receiver A value of 50 means no change i e the temperatures measured by the wall module are displayed transmitted without correction This is the default configuration Values of 49 48 47 etc mean that the tempe...

Страница 7: ...ecified on the installation drawings to allow exposure to the average zone temperature Do not mount the wall module on an outside wall on a wall containing water pipes or near air ducts Avoid locations that are exposed to discharge air from registers or radiation from lights appliances or the sun Fig 4 Mounting Removing the Housing Cover The wall module comes with a sub base that mounts separately...

Страница 8: ...te du Bois 37 Switzerland by its Authorized Representative Automation and Control Solutions Honeywell GmbH Böblinger Straße 17 D 71101 Schönaich Phone 49 7031 63701 Fax 49 7031 637493 http europe hbc honeywell com Subject to change without notice Printed in Germany EN1B 0241GE51 R0106C DIMENSIONS F Honeywell 104 85 99 97 2 30 68 100 86 Fig 6 T7270B1009 dimensions in mm ...

Отзывы: