2

APH07CH04 

R2000EN

Mechanical design

Thermostat appearnce

Function

Temperature display

The displayed temperature can be set to acquired room 

temperature or setpoint. The setting can be made during 

Installer Set-Up process.

Keypad lock

Keypad lock can be set in ISU with default status is all 

keys available. You may change into all buttons locked 

out.

Ventilation mode

Press mode button to enter ventilation mode. In 

ventilation mode, no output for valve while the fan will 

operate according to selected fan speed.

Technical specification

Power supply 

T6811DP08: 110(+20%,-10%)VAC

 

T6812DP08: 220(+/-10%)VAC

Frequency 

50/60Hz

Input Current 

4(2)A

Control algorithm 

PI, On/off output

Accuracy 

+/-1

o

C at 21

o

C

Rating capacity 

 220V: 4(2)A for fan load, 2(1)A for 

zone valve;

 

 110V: 4(2)A for fan load, 2(1)A for 

zone valve

Cycle times 

100,000

Setpoint range 

10~32

o

C

Installation 

Installed on 86×86mm junction

 

box or US2×4 inch.

Protection Class 

IP20

Environmental 

Operation temperature -18~49

o

C

Conditions 

Shipping temperature -35~65

o

C

 

Relative humidity 5~90%

Action Type 

Action Type 1

Maximum 

155

o

C

Temperature 

for Relay Wiring

Terminal Designations

Terminal

Description

L

Line Voltage Power

Ch/Cc

Heating close/Cooling close

W/Y

Heating open/Cooling open

N

Line Voltage Ground

Gl

Low speed fan 

Gm

Medium speed fan 

Gh

High speed fan 

DOWN BUTTON

FAN BUTTON

UP BUTTON

MODE BUTTON

POWER BUTTON

Wiring diagrams

Typical wiring for ON/OFF control in 2 pipes Heat/Cool/
1H1C (VC4013)

Typical wiring for ON/OFF control in 2 pipes Heat/Cool/
1H1C (VC6013)

Содержание T6812DP08

Страница 1: ...et Features Super modern appearance design suitable for office hotel and residential building Independant installation on 86 size box directly Big LCD with English and icon display Easy to install and set up Selectable room temperature or setpoint display Manual fan speed selection Adjustment of display room temperature Temperature unit either o C or o F User setting can be kept when power off Loc...

Страница 2: ...f output Accuracy 1o C at 21o C Rating capacity 220V 4 2 A for fan load 2 1 A for zone valve 110V 4 2 A for fan load 2 1 A for zone valve Cycle times 100 000 Setpoint range 10 32o C Installation Installed on 86 86mm junction box or US2 4 inch Protection Class IP20 Environmental Operation temperature 18 49o C Conditions Shipping temperature 35 65o C Relative humidity 5 90 Action Type Action Type 1 ...

Страница 3: ...ton Check that the heat temperature setting is set above the room temperature and Heat On shows solidly in the display Wait five minutes for the heating system to respond Cooling system does not turn on Set the mode to Cool by pressing the Mode button Check that the cool temperature setting is set below the room temperature and Cool On shows solidly in the display Wait five minutes for the cooling...

Страница 4: ...o F 0o C 0o F Default 0 5 o C 1o F 1o C 2o F 1 5o C 3o F 2o C 4 o F 19 Temperature Display mode 0 Display Room Temperature Default 1 Display Setpoint 20 Heating Range Stops 10 32o C Default 32o C 21 Cooling Range Stops 10 32o C Default 10o C 22 Keypad Lockout 0 All keys available Default 1 All keys Locked out Installer setup Press and hold UP and MODE buttons 3 seconds to enter setup mode Press UP...

Отзывы: